# Single-Phase Motor Full-Load Current Calculator (Amps from hp or kW)

> The running current a single-phase motor draws at full load, from its rating in hp or kW, the voltage, and its efficiency and power factor.

Page: https://craftquantities.com/calculators/electrical/single-phase-motor-full-load-current-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.0.0, sources checked 2026-10-05, 12 published test vectors.

Full-load running current: 5.3 A for Motor rating 0.75, Efficiency at full load 68.5 and Power factor at full load 0.67, the page's opening figures. Source: WEG Rolled Steel General Purpose 1-phase Motors, performance data (AutomationDirect catalogue page tMTR-54).

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Motor rating | `rating` | 0.75 | 0.75 | range 0.05–20 |
| Rated in | `ratingUnit` | Horsepower (hp) | Horsepower (hp) | `hp`, `kw` |
| Voltage the motor is connected for | `voltage` | 230 V (UK, European and Australian supply; North American motor rating on 240 V) | 230 V (UK, European and Australian supply; North American motor rating on 240 V) | `115`, `120`, `200`, `208`, `220`, `230`, `240`, `other` |
| Voltage you are working at (V) | `customVoltage` | 220 | 220 | range 12–600 |
| Efficiency at full load (%) | `efficiency` | 68.5 | 68.5 | range 30–98 |
| Power factor at full load | `powerFactor` | 0.67 | 0.67 | range 0.3–1 |

- **Motor rating**: The rated output on the nameplate — the shaft power, in the unit chosen below.
- **Rated in**: The unit the nameplate states the rating in.
- **Voltage the motor is connected for**: The rated voltage the motor runs at, as connected.
- **Voltage you are working at (V)**: The motor's rated voltage, when the list does not have it.
- **Efficiency at full load (%)**: From the nameplate or the maker's data sheet; it opens on a real motor's figure — 68.5% in North America, 70% elsewhere.
- **Power factor at full load**: From the nameplate or the maker's data sheet; it opens on the same motor's figure — 0.67 in North America, 0.92 elsewhere.

`customVoltage` applies only when `voltage` is `other`.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Full-load running current** | 5.3 A |
| Rated output at the shaft | 0.56 kW |
| Rated output in watts | 559.27 W |
| Electrical input, output ÷ efficiency | 0.82 kW |
| Apparent power drawn, volts × amps | 1.22 kVA |
| Voltage used | 230 V |

### US customary

| Result | Value |
|---|---|
| **Full-load running current** | 5.3 A |
| Rated output at the shaft | 0.56 kW |
| Rated output in watts | 559.27 W |
| Electrical input, output ÷ efficiency | 0.82 kW |
| Apparent power drawn, volts × amps | 1.22 kVA |
| Voltage used | 230 V |

- Confidence: medium.

## How it is worked out

Full-load running current = rated output ÷ (volts × efficiency × power factor). Worked from WEG's own efficiency and power factor, it comes within 2% of the current WEG lists for 13 of its 15 general-purpose US motors and within 5% for the other two, the smallest. It is only as good as the efficiency and power factor entered, and it is not the figure a US circuit is sized from: the National Electrical Code's own single-phase motor table governs that for most motors, and the nameplate for some — a sealed (hermetic) refrigeration or air-conditioning compressor among them — and the table is not reproduced here.

The working the page shows, in order: Rated output at the shaft; Rated output in watts; Electrical input, output ÷ efficiency; Apparent power drawn, volts × amps; Voltage used; then full-load running current.

The method, derived in full:

- [Electrical Demand, Three-Phase Power and Panel Capacity](https://craftquantities.com/methodology/electrical-demand-and-panel-capacity/): Why the sum of every nameplate is a load no building ever draws, why a motor's conductors are sized from a table rather than from its nameplate, and why a dark room needs far more light than a pale one for the same lux.

What this calculation does not cover:

- This is the RUNNING current at rated load, worked from the efficiency and power factor you enter. A single-phase motor starting across the line draws several times this for the first moments — the nameplate's locked-rotor figure or code letter says how much — and that inrush is what decides how a starter, a breaker's trip curve or a generator copes with it.
- Efficiency and power factor are full-load figures, and a single-phase motor's change sharply with load. Lightly loaded, its power factor falls and the current stays well above the share of rated output it is delivering, so a clamp reading on an oversized motor will not scale with the load.
- In the United States, motor branch-circuit conductors and short-circuit protection are sized from the National Electrical Code's own full-load current table for single-phase motors, Table 430.248, not from this calculation or the nameplate — except where the code sends a motor to its nameplate instead. The 1968 text this page cites already does so for a sealed (hermetic-type) motor-compressor, such as the compressor in refrigeration or air-conditioning equipment, using the current marked on that equipment's nameplate (430-6(b)), and gives torque and multispeed motors rules of their own; the edition in force sets the list, and the electrician applies it. The table is not reproduced here, and its figures are not the ones this page prints. Overload protection, by contrast, follows the nameplate current.
- Nothing here sizes a cable, a breaker, a fuse, an overload or a starter. In the UK that is BS 7671 and the motor maker's instructions, in Australia AS/NZS 3000, and in North America NEC Article 430 or Canada's own electrical code — each applied by the electrician who designs and certifies the circuit.
- The voltage is the motor's rated voltage, assumed to arrive at its terminals. On a long run the voltage at the motor is lower, and a motor asked for the same torque at a lower voltage draws more current; check the run's voltage drop separately.
- A dual-voltage motor draws twice the current when connected for the lower voltage: the same 3/4 hp motor that draws 5.3 A on 230 V draws about 10.6 A on 115 V. Enter the voltage it is actually connected for.

A professional must decide:

- In the United States, motor branch-circuit conductors and short-circuit protection are sized from the National Electrical Code's own full-load current table for single-phase motors, Table 430.248, not from this calculation or the nameplate — except where the code sends a motor to its nameplate instead. The 1968 text this page cites already does so for a sealed (hermetic-type) motor-compressor, such as the compressor in refrigeration or air-conditioning equipment, using the current marked on that equipment's nameplate (430-6(b)), and gives torque and multispeed motors rules of their own; the edition in force sets the list, and the electrician applies it.
- Structure: sizes, thicknesses, spans, reinforcement and bearing are a structural engineer's or the building official's decision. This is a quantity, not a design.
- Electrics: circuit design, protection, cable sizing and the work itself are for a qualified or licensed electrician, under the rules where you build.

## Sources

As the calculator cites them (sources checked 2026-10-05):

- Single-phase motor input current from rated output: I = P(out) ÷ (V × efficiency × power factor), the electrical input being the shaft output divided by the efficiency, and single-phase current that input divided by volts times power factor
- WEG Rolled Steel General Purpose 1-phase Motors, performance data (AutomationDirect catalogue page tMTR-54): full-load amps, efficiency and power factor per motor — 3/4 hp 1,745 rpm .7518ES1B56C-S at 10.6/5.86-5.3 A (115/208-230 V), 68.5% and 0.67, the figures this page opens on; 1 hp 1,745 rpm 00118ES1B56C-S at 13.6/7.52-6.8 A, 71.0% and 0.68; 1 hp 3,500 rpm 00136ES1B56C-S at 10.1/5.64-5.06 A, 70.0% and 0.92 <https://cdn.automationdirect.com/static/specs/weg1phmotor.pdf>
- Mechanical horsepower is 550 ft·lbf/s = 745.699872 W exactly
- NFPA 70-1968, the National Electrical Code, Section 430-6(a) (reprinted with permission by the US Mine Safety and Health Administration): where a motor's current is used to size conductors, switches and branch-circuit protection, the code's full-load current tables are used instead of the nameplate current, and running overload protection is based on the nameplate. Its exceptions in the same section: 430-6(b), a sealed (hermetic-type) motor-compressor takes the full-load current marked on the nameplate of the equipment it is in, for the branch-circuit conductors, the controller and the protection; 430-6(c), a torque motor its nameplate locked-rotor current; and multispeed motors their own rules. Current editions number it 430.6(A)(1) and the single-phase table 430.248, which this page does not reproduce <https://arlweb.msha.gov/District/DIST_09/Electrical%20test%20materials/ART430.pdf>
- WEG W22 Single-Phase Electric Motor, Commercial Catalogue, European Market (Cod. 50069268, Rev. 00, 01/2017), page 5, Electrical Data, W22 Single-Phase CSR (starting and run capacitor), IV pole, 50 Hz: 0.75 kW (1 HP), frame 80, 1,435 rpm, efficiency 70.0% and power factor 0.92 at full load, 5.06 A at 230 V — the motor a UK, Australian or international reader opens on; II pole 0.75 kW, 2,915 rpm, 75.0% and 0.91, 4.78 A <https://static.weg.net/medias/downloadcenter/h52/h99/WEG-w22-single-phase-european-market-50069268-brochure-english-web.pdf>

The site's pages for the documents these name:

- [National Electrical Code (NFPA 70)](https://craftquantities.com/standards/nfpa/nec/)

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**Why does a small single-phase motor draw so much more current than its rating suggests?**

Because two losses stack. Its efficiency is low — a 3/4 hp general-purpose motor in WEG's range is 68.5% — so it draws more power than it delivers, and its power factor is low too, 0.67 for the same motor, so the supply carries more current than that power needs. Divided out, 559 W at the shaft becomes 5.3 A at 230 V, where shaft watts over volts alone would say 2.4 A.

**Can I size the breaker or the cable from this figure?**

No. In the United States the National Electrical Code sizes a motor's conductors and short-circuit protection from its own single-phase motor table rather than from the nameplate or a calculation — save where it sends the motor to its nameplate instead, as it does a sealed (hermetic) motor-compressor in refrigeration or air-conditioning equipment — and its overload protection from the nameplate; elsewhere the wiring rules and the motor maker's instructions set it. The circuit is the electrician's design. This page tells you what the motor itself draws while running, which is what a generator, an inverter or an energy estimate needs.

**Why doesn't the page show the NEC's table figure?**

The table is printed in the NEC, which is sold by its publisher, and no reproduction that names the edition it copies could be read for this page. Rather than print figures nobody can trace, the page works the current from the motor's own data and says plainly that the code's table is a different number, to be read in the edition your jurisdiction adopted.

**My motor is rated in kW but the plate also shows hp. Which do I use?**

Either — choose the matching unit. A horsepower is 745.7 W, so 0.75 kW is 1.006 hp and a plate can carry both figures for the same motor. The current comes out the same as long as the rating and its unit agree; mixing them, a 0.75 entered as kW for a 3/4 hp motor, overstates it by about a third.

**Why do two motors of the same rating draw different currents?**

Because their power factor and efficiency differ with the design. In WEG's table the 1 hp, 3,500 rpm motor runs at 70% and 0.92 and lists 5.06 A at 230 V, while the 1 hp, 1,745 rpm motor runs at 71% and 0.68 and lists 6.8 A — a third more current for the same output. The rating alone cannot tell the page which kind you have, so enter the efficiency and power factor from your own motor's plate or data sheet.

## Related calculators

- [Three-Phase Motor Full-Load Amperage Calculator](https://craftquantities.com/calculators/materials-quantities/motor-full-load-amps-calculator/)
- [Watts, Amps and kVA Calculator (Any Voltage, AC or DC)](https://craftquantities.com/calculators/electrical/watts-amps-kva-calculator/)
- [Horsepower to kW Calculator](https://craftquantities.com/calculators/electrical/hp-to-kw-calculator/)
- [Wire Gauge Voltage Drop Calculator (Copper or Aluminum, AWG to 1,000 kcmil)](https://craftquantities.com/calculators/electrical/wire-gauge-voltage-drop-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/single-phase-motor-full-load-current-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/single-phase-motor-full-load-current-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `single-phase-motor-full-load-current-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/single-phase-motor-full-load-current-calculator.json

---
Source: https://craftquantities.com/calculators/electrical/single-phase-motor-full-load-current-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.