# Fire Detector Spacing and Count Calculator (BS 5839-1 and NFPA 72)

> How many point smoke or heat detectors a flat ceiling needs so no point is farther from one than BS 5839-1 or NFPA 72 allows, with their spacing.

Page: https://craftquantities.com/calculators/electrical/point-detector-coverage-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.0.0, sources checked 2026-09-22, 5 published test vectors.

Detectors needed: 12 detectors for Listed Spacing of the Detector 30 ft, Room Length 98 ft and Room Width 79 ft, the page's opening figures; on the metric page, 9.14 m, 30 m and 24 m give 12 detectors. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Standard and Detector Type | `standard` | NFPA 72 — spot detectors at their listed spacing | NFPA 72 — spot detectors at their listed spacing | `bs5839-smoke`, `bs5839-heat`, `nfpa72` |
| Listed Spacing of the Detector | `listedSpacing` | 9.144 m | 30 ft | mm, cm, m, in, ft, yd; range 1–30 m |
| Room Length | `roomLength` | 30 m | 98 ft | mm, cm, m, in, ft, yd; range 0.5–1000 m |
| Room Width | `roomWidth` | 24 m | 79 ft | mm, cm, m, in, ft, yd; range 0.5–1000 m |

- **Standard and Detector Type**: Sets the coverage: BS 5839-1 gives a radius per detector type; NFPA 72 works from the detector's listed spacing.
- **Listed Spacing of the Detector**: The spacing the detector is listed for — a nominal 30 ft (9.1 m) for smoke detectors on a smooth ceiling.
- **Room Length**: The room's longer dimension, wall to wall.
- **Room Width**: The shorter dimension, wall to wall.

`listedSpacing` applies only when `standard` is `nfpa72`.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Detectors needed** | 12 detectors |
| Coverage radius | 6.4 m |
| Detectors along the length | 4 |
| Detectors across the width | 3 |
| Spacing along the length | 7.5 m |
| Spacing across the width | 8 m |
| Farthest point from a detector (a cell's corner) | 5.48 m |
| Floor area each detector covers on this grid | 60 m² |

### US customary

| Result | Value |
|---|---|
| **Detectors needed** | 12 detectors |
| Coverage radius | 21 ft |
| Detectors along the length | 4 |
| Detectors across the width | 3 |
| Spacing along the length | 24.5 ft |
| Spacing across the width | 26.33 ft |
| Farthest point from a detector (a cell's corner) | 17.98 ft |
| Floor area each detector covers on this grid | 645.17 sq ft |

## How it is worked out

The fewest detectors in rows that keep a cell's farthest corner within the coverage radius for NFPA 72 spot detectors at their listed spacing.

The working the page shows, in order: Coverage radius; Detectors along the length; Detectors across the width; Spacing along the length; Spacing across the width; Farthest point from a detector (a cell's corner); Floor area each detector covers on this grid; then detectors needed.

The method, derived in full:

- [Clearances, Layout and Accessibility Dimensions](https://craftquantities.com/methodology/clearances-layout-and-accessibility/): Why an accessible dimension is a measured anthropometric result rather than a round number, why a parking layout is set by the vehicle that turns worst, and why a door needs floor space on the side nobody draws.

What this calculation does not cover:

- A flat, smooth ceiling of one height. Pitched ceilings, beams deeper than a tenth of the ceiling height, and walls or partitions near the ceiling each change the layout, and each space is laid out on its own.
- Ceiling height limits apply: BS 5839-1 gives 10.5 m (34 ft 5 in) for point smoke detectors in general, 7.5 m (24 ft 7 in) for fixed-temperature heat detectors and 9 m (29 ft 6 in) for rate-of-rise; NFPA 72 reduces heat detector spacing on high ceilings.
- Detectors are kept at least 500 mm (20 in) from walls and obstructions under BS 5839-1 and away from air supply points; the grid positions are the arithmetic before those rules move them.
- The system category, which decides which rooms are covered at all, comes first and is not part of this count.

A professional must decide:

- Electrics: circuit design, protection, cable sizing and the work itself are for a qualified or licensed electrician, under the rules where you build.

## Sources

As the calculator cites them (sources checked 2026-09-22):

- BS 5839-1:2025, clause 21: on a flat ceiling no point more than 7.5 m horizontally from the nearest point smoke detector or 5.3 m from the nearest point heat detector; in corridors under 2 m wide the coverage need not overlap
- NFPA 72, National Fire Alarm and Signaling Code, Chapter 17: spot detectors at their listed spacing (a nominal 30 ft, 9.1 m, for smoke on a smooth ceiling), with every point within 0.7 times the spacing of a detector
- Grid geometry: a rectangular cell's farthest point is its corner, at √((sx ÷ 2)² + (sy ÷ 2)²) from the detector

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**Why not divide the floor area by the area of the circle?**

Because circles do not tile. A 7.5 m (24 ft 7 in) radius traces a circle of about 177 m² (1,900 sq ft), but detectors go on a grid, and the largest square whose corners stay inside that circle is 10.6 m (34 ft 10 in) a side — 112.5 m² (1,211 sq ft), about 64 per cent of the circle. Dividing by the circle buys too few detectors.

**Does the grid have to be square?**

No. The only condition is that each cell's corner stays within the radius, so the two half-spacings squared and added must not exceed the radius squared. On a long, narrow floor a rectangular grid often saves detectors.

**Why does a small store still need two detectors?**

Because the rule is a distance, not an area. A 4 × 26 m (13 × 85 ft) store is under the area one detector's square covers, but one detector in the middle leaves both ends 13 m (43 ft) away. Once a room's longest dimension is more than twice the radius, area stops mattering.

## Related calculators

- [Smoke Detector Placement Calculator](https://craftquantities.com/calculators/electrical/smoke-detector-calculator/)
- [Sprinkler Head Spacing and Count Calculator](https://craftquantities.com/calculators/landscaping-outdoor/sprinkler-head-spacing-calculator/)
- [Radius to Area Calculator](https://craftquantities.com/calculators/measurements-conversions/radius-to-area-calculator/)
- [Emergency Escape Lighting Spacing Calculator](https://craftquantities.com/calculators/electrical/emergency-lighting-spacing-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/point-detector-coverage-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/point-detector-coverage-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `point-detector-coverage-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/point-detector-coverage-calculator.json

---
Source: https://craftquantities.com/calculators/electrical/point-detector-coverage-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.