# kW to kVA Calculator

> Convert real power in kW into the apparent power in kVA a generator, transformer or supply has to carry, at the load's power factor.

Page: https://craftquantities.com/calculators/electrical/kw-to-kva-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.1.0, sources checked 2026-10-05, 5 published test vectors.

Apparent power: 100 kVA for Real power 80 and Power factor 0.8, the page's opening figures. Source: Cummins Inc., 2022 Global Product Guide.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Real power (kW) | `kw` | 80 | 80 | range 0–10000 |
| Power factor | `powerFactor` | 0.8 | 0.8 | range 0.2–1 |

- **Real power (kW)**: The real power demand in kilowatts.
- **Power factor**: The load's power factor: 1 for resistive heating, lower for motors. It opens on 0.8, the factor three-phase generator sets are rated at; a single-phase set is rated at 1.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Apparent power** | 100 kVA |
| Real power entered | 80 kW |
| Power factor applied | 0.8 |
| Reactive power, kW × tan(arccos PF) | 60 kvar |

### US customary

| Result | Value |
|---|---|
| **Apparent power** | 100 kVA |
| Real power entered | 80 kW |
| Power factor applied | 0.8 |
| Reactive power, kW × tan(arccos PF) | 60 kvar |

## How it is worked out

kVA = kW ÷ power factor. The kvar row is the reactive part the supply carries on top of the working current; a generator has to be checked against its kVA as well as its kW, taking whichever binds first. Motor inrush frequently determines generator size rather than running load, so check starting current separately.

The working the page shows, in order: Real power entered; Power factor applied; Reactive power, kW × tan(arccos PF); then apparent power.

The method, derived in full:

- [Unit Conversion, Exactness and Rounding](https://craftquantities.com/methodology/unit-conversion-and-rounding/): Why most conversion factors carry no uncertainty at all, which ones hide a material assumption, and why converting a measurement can never make it more precise than it was.

What this calculation does not cover:

- The answer scales inversely with the power factor entered, and the field opens on 0.8 for a set's badge, not because any load runs there. Three-phase generator sets are conventionally rated at 0.8 — Cummins lists the C20D6 at 25 kVA and 20 kWe — while single-phase sets are rated at 1, where kVA and kW are the same number. A motor-heavy site below 0.8 needs more kVA than the opening answer shows, and a corrected or largely resistive one needs less.
- This is a unit conversion, not a load calculation. It takes the kW figure you type at face value and applies no diversity, no demand factors and no maximum-demand assessment, so it does not stand in for a proper load assessment before ordering a supply, transformer or generator set.
- Steady-state only. Motor inrush, step-load acceptance and transient voltage dip are not modelled, and on a generator these frequently set the machine size well above the running kVA calculated here.
- No voltage, current or phase comes out of this. The result does not size conductors, protective devices or switchgear; the current at a given voltage, single-phase or three-phase, is a separate step on the watts, amps and kVA page.
- Distorting loads such as variable-speed drives, UPS and some LED and IT supplies draw harmonic current that a single power factor does not describe. Nothing here derates the machine for that content, or for altitude and ambient temperature on a generator.

A professional must decide:

- Electrics: circuit design, protection, cable sizing and the work itself are for a qualified or licensed electrician, under the rules where you build.

## Sources

As the calculator cites them (sources checked 2026-10-05):

- Apparent power = real power / power factor; kVA = kW / PF, and the reactive part is kW x tan(arccos PF)
- Cummins Inc., 2022 Global Product Guide — Power Generation Products (GLM-5763-EN): the diesel sets are listed with their kWe at 0.8 of their kVA (the C20D6 at 25 kVA and 20 kWe standby, the C30D6 at 37.5 kVA and 30 kWe), the three-phase convention the opening 0.8 follows; the single-phase sets are listed in kW with a current that is the kW divided by the volts, so their kVA and kW are the same number (the RV QG 2800 at 2.8 kW and 23.3 A on 120 V, the RV QG 2300 at 2.3 kW and 10 A on 230 V, the QD5000 at 4.8 kW and 21 A on 230 V) <https://mart.cummins.com/imagelibrary/data/assetfiles/0058677.pdf>
- Cummins Inc., Pre-Configured Diesel generator sets, specification sheet NAS-6437-EN (12/19): the C20 D6 set for 120/240 V, 1 phase, is 20 kW and 20 kVA standby at 60 Hz — the model the 2022 guide lists at 25 kVA and 20 kWe

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**Why does a worse power factor need a bigger supply?**

Because the supply has to carry the current, and a poor power factor means more current for the same useful work. The conductors, switchgear and transformer all size on apparent power, so a low power factor consumes capacity without doing anything with it.

**Should I size a generator on this figure?**

On this figure and the kW figure both, then take the more demanding. Check starting loads separately — motor inrush can far exceed running apparent power and is often what actually determines the set size.

**Do electronics have a poor power factor?**

Older switch-mode supplies often did. Modern equipment above a modest power threshold generally has correction built in, so a contemporary IT or LED load is usually better behaved than its reputation suggests. Measure rather than assume on a large installation.

## Related calculators

- [kVA to kW Calculator](https://craftquantities.com/calculators/electrical/kva-to-kw-calculator/)
- [Watts, Amps and kVA Calculator (Any Voltage, AC or DC)](https://craftquantities.com/calculators/electrical/watts-amps-kva-calculator/)
- [Electrical Circuit Load Calculator](https://craftquantities.com/calculators/electrical/electrical-load-calculator/)
- [Amps to Watts Calculator (230 V)](https://craftquantities.com/calculators/electrical/amps-to-watts-230v-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/kw-to-kva-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/kw-to-kva-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `kw-to-kva-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/kw-to-kva-calculator.json

---
Source: https://craftquantities.com/calculators/electrical/kw-to-kva-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.