# kVA to kW Calculator

> Convert apparent power in kVA into real power in kW at the power factor you enter: 0.8 for a three-phase generator's badge, 1 for a single-phase one's.

Page: https://craftquantities.com/calculators/electrical/kva-to-kw-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.1.0, sources checked 2026-10-05, 5 published test vectors.

Real power: 80 kW for Apparent power 100 and Power factor 0.8, the page's opening figures. Source: Cummins Inc., 2022 Global Product Guide.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Apparent power (kVA) | `kva` | 100 | 100 | range 0–10000 |
| Power factor | `powerFactor` | 0.8 | 0.8 | range 0.2–1 |

- **Apparent power (kVA)**: The apparent power rating in kilovolt-amperes.
- **Power factor**: The ratio of real to apparent power: 1 for a heater, about 0.8 to 0.9 for a loaded three-phase motor. It opens on 0.8, the factor three-phase generator sets are rated at; a single-phase set is rated at 1.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Real power** | 80 kW |
| Power factor applied | 0.8 |
| Reactive power, kVA × √(1 − PF²) | 60 kvar |

### US customary

| Result | Value |
|---|---|
| **Real power** | 80 kW |
| Power factor applied | 0.8 |
| Reactive power, kVA × √(1 − PF²) | 60 kvar |

## How it is worked out

kW = kVA × power factor. The kVA, kW and kvar are the three sides of the power triangle; the kvar is the part of the current that flows without doing work, which is what correction equipment cancels. The result scales directly with the power factor entered.

The working the page shows, in order: Power factor applied; Reactive power, kVA × √(1 − PF²); then real power.

The method, derived in full:

- [Unit Conversion, Exactness and Rounding](https://craftquantities.com/methodology/unit-conversion-and-rounding/): Why most conversion factors carry no uncertainty at all, which ones hide a material assumption, and why converting a measurement can never make it more precise than it was.

What this calculation does not cover:

- The answer is only as right as the power factor entered. Three-phase generator sets are conventionally rated at 0.8 — Cummins lists the C20D6 at 25 kVA and 20 kWe — while single-phase sets are rated at 1, where kVA and kW are the same number. The field opens on the three-phase figure, not because any installation runs at it: a motor-heavy site runs lower and a corrected or largely resistive one higher, and the kW figure moves in direct proportion with whatever goes in the box.
- This is a rating conversion, not a load calculation. It does not establish connected load or maximum demand, apply diversity or demand factors, or size a supply, cable or protective device. Those remain separate calculations under the wiring regulations in force for the job.
- Steady state only. Motor starting current can be several times the running figure, and on a generator that transient frequently determines the set size rather than anything this conversion produces.
- A single power factor covers displacement only. Non-linear loads such as variable-speed drives, switch-mode supplies and some LED drivers draw distorted current, so the true power factor sits below the displacement figure and the supply carries more apparent power than one number suggests.
- Nameplate kVA is quoted at the manufacturer's reference conditions. Altitude, ambient temperature and duty rating all reduce what a generator or transformer can actually deliver on site, and none of that derating is in this conversion.

A professional must decide:

- Electrics: circuit design, protection, cable sizing and the work itself are for a qualified or licensed electrician, under the rules where you build.

## Sources

As the calculator cites them (sources checked 2026-10-05):

- Real power = apparent power x power factor; kW = kVA x PF, and the reactive part is kVA x √(1 − PF²)
- Cummins Inc., 2022 Global Product Guide — Power Generation Products (GLM-5763-EN): the diesel sets are listed with their kWe at 0.8 of their kVA (the C20D6 at 25 kVA and 20 kWe standby, the C30D6 at 37.5 kVA and 30 kWe), the three-phase convention the opening 0.8 follows; the single-phase sets are listed in kW with a current that is the kW divided by the volts, so their kVA and kW are the same number (the RV QG 2800 at 2.8 kW and 23.3 A on 120 V, the RV QG 2300 at 2.3 kW and 10 A on 230 V, the QD5000 at 4.8 kW and 21 A on 230 V) <https://mart.cummins.com/imagelibrary/data/assetfiles/0058677.pdf>
- Cummins Inc., Pre-Configured Diesel generator sets, specification sheet NAS-6437-EN (12/19): the C20 D6 set for 120/240 V, 1 phase, is 20 kW and 20 kVA standby at 60 Hz — the model the 2022 guide lists at 25 kVA and 20 kWe

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**Why does the power factor open on 0.8?**

Because of how generator sets are badged. Three-phase generator sets are conventionally rated at 0.8 — Cummins lists the C20D6 at 25 kVA and 20 kWe — while single-phase sets are rated at 1, where kVA and kW are the same number. So 0.8 converts a three-phase set's own badge as it stands; for a single-phase set enter 1 — the same C20D6 built for 120/240 V single phase is listed at 20 kW and 20 kVA. It is the wrong number to leave in place for a load you know: replace it with the load's figure from its nameplate or a power-quality meter, and the answer follows it in direct proportion.

**Which figure do generators use?**

Both, and it matters. Generator sets are rated in kVA for their alternator capacity and kW for their engine capacity. Sizing on the kW figure alone can leave the alternator overloaded by a poor power factor even though the engine has capacity to spare.

**Can power factor be improved?**

Yes, with correction equipment, and it is often worth doing where supply charges are based on kVA. Correction reduces the apparent power drawn for the same useful work, freeing capacity and sometimes reducing the tariff.

## Related calculators

- [kW to kVA Calculator](https://craftquantities.com/calculators/electrical/kw-to-kva-calculator/)
- [Watts, Amps and kVA Calculator (Any Voltage, AC or DC)](https://craftquantities.com/calculators/electrical/watts-amps-kva-calculator/)
- [Electrical Circuit Load Calculator](https://craftquantities.com/calculators/electrical/electrical-load-calculator/)
- [Horsepower to kW Calculator](https://craftquantities.com/calculators/electrical/hp-to-kw-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/kva-to-kw-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/kva-to-kw-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `kva-to-kw-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/kva-to-kw-calculator.json

---