# Emergency Escape Lighting Spacing Calculator

> How many emergency luminaires an escape route needs: the spacing that holds EN 1838's minimum on its centre line, plus one at each point of emphasis.

Page: https://craftquantities.com/calculators/electrical/emergency-lighting-spacing-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.0.1, sources checked 2026-09-02, 5 published test vectors.

Emergency luminaires required: 8 luminaires for Escape route length 98 ft and Mounting height 8 ft, the page's opening figures; on the metric page, 30 m and 2.5 m give 7 luminaires. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Escape route length | `routeLength` | 30 m | 98 ft | mm, cm, m, in, ft, yd; range 1–500 m |
| Mounting height | `mountingHeight` | 2.5 m | 8 ft | mm, cm, m, in, ft, yd; range 1.8–12 m |
| Spacing-to-height ratio at 1 lux | `spacingRatio` | 4 | 4 | range 1–12 |
| Points of emphasis on this route | `pointsOfEmphasis` | 3 | 3 | range 0–50 |

- **Escape route length**: The length of the escape route this run of luminaires covers.
- **Mounting height**: Height of the luminaire above the floor.
- **Spacing-to-height ratio at 1 lux**: From the luminaire's own spacing table — how many times its mounting height it may be spaced.
- **Points of emphasis on this route**: Exits, stair flights, changes of direction and level, call points and firefighting equipment.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Emergency luminaires required** | 7 luminaires |
| Maximum spacing at this height and ratio | 10 m |
| Actual spacing once the run is divided evenly | 10 m |
| Luminaires from spacing alone | 4 fittings |
| Added for points of emphasis | 3 fittings |

### US customary

| Result | Value |
|---|---|
| **Emergency luminaires required** | 8 luminaires |
| Maximum spacing at this height and ratio | 32 ft |
| Actual spacing once the run is divided evenly | 24.5 ft |
| Luminaires from spacing alone | 5 fittings |
| Added for points of emphasis | 3 fittings |

- Confidence: medium.

## How it is worked out

This holds 1 lux (0.09 fc) on the centre line of a route up to 2 m (6.5 ft) wide, using the spacing ratio you entered. That ratio is the whole calculation — it belongs to a specific fitting at a specific mounting height, and taking it from a different luminaire's data sheet invalidates the answer.

The working the page shows, in order: Maximum spacing at this height and ratio; Actual spacing once the run is divided evenly; Luminaires from spacing alone; Added for points of emphasis; then emergency luminaires required.

The method, derived in full:

- [Electrical Demand, Three-Phase Power and Panel Capacity](https://craftquantities.com/methodology/electrical-demand-and-panel-capacity/): Why the sum of every nameplate is a load no building ever draws, why a motor's conductors are sized from a table rather than from its nameplate, and why a dark room needs far more light than a pale one for the same lux.

What this calculation does not cover:

- Escape routes only, up to 2 m (6.5 ft) wide. An open area needs 0.5 lux (0.05 fc) over the empty floor EXCLUDING a 0.5 m (1.6 ft) border, and a high-risk task area needs 10% of its normal maintained illuminance or 15 lux (1.4 fc), whichever is greater — both are different calculations.
- Does not check uniformity. EN 1838 limits the ratio of maximum to minimum illuminance along the centre line to 40:1, and a run that meets the minimum at every point can still fail that if the fittings are unevenly placed.
- Does not address duration, which is the other half of the specification: one hour or three depending on the premises and how it is evacuated, and it is the battery rather than the layout that delivers it.
- Does not check disability glare, which limits luminous intensity within the field of view and bites hardest on high mounting in a low-ceilinged space.

A professional must decide:

- Electrics: circuit design, protection, cable sizing and the work itself are for a qualified or licensed electrician, under the rules where you build.

## Sources

As the calculator cites them (sources checked 2026-09-02):

- EN 1838 / BS 5266-7, Lighting applications — emergency lighting: escape routes up to 2 m wide require a minimum of 1 lux on the centre line, with uniformity along that line no worse than 40:1
- BS 5266-1, Code of practice for the emergency escape lighting of premises: a luminaire is required at each exit door, at each stair flight so every flight receives direct light, at every change of direction and change of level, at intersections of corridors, outside each final exit, and at fire alarm call points and firefighting equipment — conventionally within 2 m horizontally of each
- Spacing is taken as the mounting height multiplied by the luminaire's published spacing-to-height ratio for the target illuminance; that ratio comes from the manufacturer's photometric data and is specific to the fitting

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**Why is the answer bigger than the spacing calculation gives?**

Because BS 5266-1 requires luminaires at places the spacing grid knows nothing about. A luminaire is needed at each exit door and outside each final exit, at each flight of stairs so the flight itself receives direct light, at every change of direction and every change of level, at corridor intersections, and at fire alarm call points and firefighting equipment. These are where people stop, turn or reach for something in the dark, and none of them cares how the spacing worked out. A corridor that computes as four luminaires routinely installs as seven, which is one of the most common under-quotes on a small emergency lighting job.

**Is an average of 1 lux good enough?**

No, and this is the distinction that matters most on the page. EN 1838 sets 1 lux as a MINIMUM on the centre line of the escape route, not an average across it. A corridor averaging five lux can still have a 0.2 lux hole between two widely spaced fittings, and the hole will be where the light from neither reaches — often exactly at a turn or a stair head. That is also why the standard limits the maximum-to-minimum ratio along the centre line to 40:1: an even one lux is safe to walk, and a bright patch beside a dark one is worse than either, because eyes adapting to the bright part cannot see into the dark part at all.

**Where does the spacing ratio come from?**

The luminaire's own data sheet. Every emergency fitting is published with a spacing table derived from its photometric file, listing the axial and transverse spacing that still delivers one lux at a given mounting height. It is a property of that fitting's light distribution, so it varies enormously: a bulkhead throwing light along a corridor can exceed six times its mounting height, and a decorative fitting that puts most of its output on the ceiling can be under two. The default here is a placeholder for an ordinary recessed emergency downlight and should be replaced with the real figure before anything is ordered.

**Does this cover an open area or a plant room?**

No — it covers escape routes up to 2 m wide, which is one of three cases EN 1838 treats separately. An open or anti-panic area needs 0.5 lux over the empty floor while EXCLUDING a border 0.5 m wide around it, which is a different geometry rather than a different number. A high-risk task area needs 10% of the maintained illuminance the task normally gets, with a floor of 15 lux, because the point there is not escaping but shutting something down safely first.

**How long do they have to stay lit?**

One hour or three, and the layout does not decide it — the battery does. Three hours is usual where the premises sleeps people, where evacuation may be phased, or where the building will not be re-occupied until the supply is restored; one hour suits a premises that empties quickly and can be checked before anyone returns. It is worth settling early, because the duration changes the battery and therefore the fitting, and the fitting is what carries the spacing ratio this calculation depends on.

## Related calculators

- [Lighting Illuminance (Lux) Calculator](https://craftquantities.com/calculators/materials-quantities/lighting-illuminance-calculator/)
- [Lighting Circuit Connected Load Calculator](https://craftquantities.com/calculators/materials-quantities/lighting-circuit-load-calculator/)
- [Smoke Detector Placement Calculator](https://craftquantities.com/calculators/electrical/smoke-detector-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/emergency-lighting-spacing-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/emergency-lighting-spacing-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `emergency-lighting-spacing-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/emergency-lighting-spacing-calculator.json

---
Source: https://craftquantities.com/calculators/electrical/emergency-lighting-spacing-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.