# Electrical Circuit Load Calculator

> Check how much of a circuit's safe capacity your connected devices are using, based on the NEC 80% continuous-load rule.

Page: https://craftquantities.com/calculators/electrical/electrical-load-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.0.1, sources checked 2026-09-02, 2 published test vectors.

Current draw: 10 A for Total Connected Load 1200, the page's opening figures. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Breaker Rating | `breakerAmps` | 20 A | 20 A | `6`, `10`, `15`, `16`, `20`, `30`, `32`, `40`, `45`, `50` |
| Circuit Voltage | `circuitVoltage` | 120 V (US outlet) | 120 V (US outlet) | `120`, `230`, `240` |
| Total Connected Load (W) | `totalConnectedWatts` | 1200 | 1200 | range 0–15000 |

- **Breaker Rating**: The amp rating printed on the breaker in your panel.
- **Circuit Voltage**: Most household outlets in North America are 120V; large appliances (dryers, ranges, EV chargers) are often 240V.
- **Total Connected Load (W)**: The sum of the wattage of everything plugged into this circuit at once.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Current draw** | 10 A |
| Total connected load | 1,200 W |
| Safe continuous limit (80% rule) | 16 A |
| Safe continuous limit | 1,920 W |
| % of safe continuous capacity used | 62.5 % |

### US customary

| Result | Value |
|---|---|
| **Current draw** | 10 A |
| Total connected load | 1,200 W |
| Safe continuous limit (80% rule) | 16 A |
| Safe continuous limit | 1,920 W |
| % of safe continuous capacity used | 62.5 % |

## How it is worked out

The working the page shows, in order: Total connected load; Safe continuous limit (80% rule); Safe continuous limit; % of safe continuous capacity used; then current draw.

The method, derived in full:

- [Electrical Demand, Three-Phase Power and Panel Capacity](https://craftquantities.com/methodology/electrical-demand-and-panel-capacity/): Why the sum of every nameplate is a load no building ever draws, why a motor's conductors are sized from a table rather than from its nameplate, and why a dark room needs far more light than a pale one for the same lux.

What this calculation does not cover:

- ONE circuit, not the panel. Whether the service and the panel can carry everything together is a separate calculation under the code's demand-factor rules, and a house full of individually compliant circuits can still overload its supply.
- Says nothing about the WIRE. Conductor ampacity is set by the conductor, its insulation, the ambient temperature and how many current-carrying conductors share a raceway — a breaker rating does not guarantee the cable behind it, and a correctly sized breaker on undersized cable is the dangerous combination.
- Voltage drop over the run is not checked here. A circuit inside its current limit can still deliver too little voltage at the far end, which is a separate calculation.
- Motor and compressor loads draw several times their running current at start-up. Nameplate watts describe the running condition and understate what the breaker sees on a cold morning.
- The 80% figure applies to CONTINUOUS loads — three hours or more at full draw. A load that is genuinely intermittent may use more of the breaker's rating, and which of the two a given appliance is can be a judgement.

A professional must decide:

- Structure: sizes, thicknesses, spans, reinforcement and bearing are a structural engineer's or the building official's decision. This is a quantity, not a design.
- Electrics: circuit design, protection, cable sizing and the work itself are for a qualified or licensed electrician, under the rules where you build.

## Sources

As the calculator cites them (sources checked 2026-09-02):

- NEC 210.19(A)(1) and 210.20(A): branch circuit conductors and overcurrent protection must be sized so continuous loads (3+ hours) don't exceed 80% of the breaker's rating (equivalently, the 125% sizing rule)

The site's pages for the documents these name:

- [National Electrical Code (NFPA 70)](https://craftquantities.com/standards/nfpa/nec/)

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**What counts as a 'continuous' load?**

Per the NEC, any load expected to run for 3 hours or more at a stretch — space heaters, lighting left on for an evening, EV charging, etc. Brief loads like a toaster are non-continuous and can safely use up to 100% of the breaker rating.

**This is telling me I'm over the limit — what should I do?**

Move some devices to a different circuit, or have an electrician evaluate whether a dedicated higher-rated circuit is needed. Don't just install a larger breaker without also upgrading the wiring — the wire, not the breaker, is usually the real limit.

**Is this a substitute for an electrician's load calculation?**

No. This is an educational estimate of one circuit's headroom, not a full panel load calculation, which accounts for diversity factors and code requirements an electrician is trained to apply.

**Where do I find a device's wattage?**

It's usually printed on a label on the device itself or its power adapter. If only amps are listed, multiply by the voltage (usually 120V) to get watts.

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/electrical-load-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/electrical-load-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `electrical-load-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/electrical-load-calculator.json

---