# Copper to Aluminum Wire Size Calculator (Aluminium Equivalent, AWG and mm²)

> What aluminum wire size equals a copper one? The smallest aluminum conductor with no more resistance, in AWG, kcmil or mm², and how near the size below is.

Page: https://craftquantities.com/calculators/electrical/copper-aluminum-wire-equivalent-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.0.0, sources checked 2026-10-05, 37 published test vectors.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Copper conductor | `copperSize` | 2/0 AWG copper | 2/0 AWG copper | `1.5mm2`, `2.5mm2`, `4mm2`, `6mm2`, `10mm2`, `16mm2`, `25mm2`, `35mm2`, `50mm2`, `70mm2`, `95mm2`, `120mm2`, `150mm2`, `185mm2`, `240mm2`, `300mm2`, `14`, `12`, `10`, `8`, `6`, `4`, `3`, `2`, `1`, `1/0`, `2/0`, `3/0`, `4/0`, `250`, `300`, `350`, `400`, `500`, `600`, `750`, `1000` |

- **Copper conductor**: The copper size you want an aluminum equal for: AWG and kcmil, or mm².

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Smallest aluminium (aluminum) size with no more resistance, in kcmil or mm²** | 250 kcmil |
| Copper conductor area (kcmil) | 133.1 |
| Aluminum area for equal resistance (kcmil) | 218.74 |
| The same area in mm² | 110.84 mm² |
| This aluminum size's resistance against the copper's (%) | 87.5 |
| The size below it, 4/0 AWG: area (kcmil) | 211.6 |
| The size below it: resistance against the copper's (%) | 103.37 |
| Aluminum's resistance per circular mil against copper's, 21.2 ÷ 12.9 | 1.64 |

### US customary

| Result | Value |
|---|---|
| **Smallest aluminium (aluminum) size with no more resistance, in kcmil or mm²** | 250 kcmil |
| Copper conductor area (kcmil) | 133.1 |
| Aluminum area for equal resistance (kcmil) | 218.74 |
| The same area in mm² | 110.84 mm² |
| This aluminum size's resistance against the copper's (%) | 87.5 |
| The size below it, 4/0 AWG: area (kcmil) | 211.6 |
| The size below it: resistance against the copper's (%) | 103.37 |
| Aluminum's resistance per circular mil against copper's, 21.2 ÷ 12.9 | 1.64 |

## How it is worked out

The smallest aluminum size with no more resistance than the copper, on the 75 °C (167 °F) K constants of the US voltage-drop method. The size below it carries a few percent more resistance than the copper, as the row shows; it is often the size an ampacity table pairs with this copper, which is a different basis. Minnesota's 2023 NEC checklist pairs 2/0 AWG copper with 4/0 AWG aluminum for a 200 A dwelling service (NEC 310.12) — an ampacity pairing, not an equal-resistance one.

The working the page shows, in order: Copper conductor area (kcmil); Aluminum area for equal resistance (kcmil); The same area in mm²; This aluminum size's resistance against the copper's (%); The size below it, 4/0 AWG: area (kcmil); The size below it: resistance against the copper's (%); Aluminum's resistance per circular mil against copper's, 21.2 ÷ 12.9; then smallest aluminium (aluminum) size with no more resistance, in kcmil or mm².

The method, derived in full:

- [Voltage Drop and Conductor Sizing](https://craftquantities.com/methodology/voltage-drop-and-conductor-sizing/): Why the run length doubles, why a 12 V circuit suffers a hundred times the percentage loss of a 120 V one, and why ampacity answers a different question entirely.

What this calculation does not cover:

- The basis is resistance, not ampacity. The aluminium size given drops no more voltage than the copper and wastes no more power in the run; whether it may carry the circuit's current is a separate lookup in the ampacity tables of the code in force, at the temperature rating of the terminations, which this page does not make and does not reproduce.
- Nothing here sizes a circuit. A substitution is the designer's decision, made with the overcurrent device, the terminations and the run's voltage drop in view, and in most places it is notifiable or licensed work.
- Aluminium needs terminations, lugs and connectors listed or rated for it, and the code does not let the two metals be joined except in a device listed for the purpose. The larger aluminium conductor may also need a larger conduit, gland or lug than the copper it replaces.
- The AWG and kcmil comparison uses one constant per metal, the figure the US circular-mil method uses; the size-by-size resistances of NEC Chapter 9 Table 8 differ from it by a percent or so either way, and the table is not reproduced here. The mm² comparison uses IEC 60228's maximum resistances at 20 °C (68 °F) for each size.
- Above 1,000 kcmil there is no single aluminium conductor in this list; feeders that large are a design question, not a substitution.

A professional must decide:

- Nothing here sizes a circuit. A substitution is the designer's decision, made with the overcurrent device, the terminations and the run's voltage drop in view, and in most places it is notifiable or licensed work.
- Electrics: circuit design, protection, cable sizing and the work itself are for a qualified or licensed electrician, under the rules where you build.

## Sources

As the calculator cites them (sources checked 2026-10-05):

- IAEI Magazine, "Voltage Drop Formulas" (March/April 2017): K constants at 75 °C (167 °F) read off NEC Chapter 9 Table 8 — 12.9 for uncoated copper (1,000 kcmil at 0.0129 Ω per 1,000 ft, 0.0423 Ω/km) and 21.2 for aluminum (0.0212 Ω per 1,000 ft, 0.0696 Ω/km) — with every size in the table close to them <https://iaeimagazine.org/electrical-fundamentals/voltage-drop-formulas/>
- Bayerische Kabelwerke AG (Bayka), Conductor resistance at 20 °C (68 °F) acc. to EN 60228: plain copper and aluminium, class 1 and 2 — 16 mm² copper 1.15 Ω/km (0.351 Ω per 1,000 ft) against 25 mm² aluminium 1.20 (0.366) and 35 mm² aluminium 0.868 (0.265) <https://www.bayka.de/en/service/technical-information/conductor-resistance>
- NBS Handbook 109, Aluminum Wire Tables: EC-H19 aluminum at 61.0% IACS, 17.002 Ω·cmil/ft (0.028264 Ω·mm²/m) at 20 °C (68 °F), against the International Annealed Copper Standard's 10.371 (0.017241) — a ratio of 1.639 <https://nvlpubs.nist.gov/nistpubs/Legacy/hb/nbshandbook109.pdf>
- Minnesota Department of Labor and Industry, Electrical Inspection Checklist for One-Family Dwellings based on the 2023 NEC (revised 2023-05-06): dwelling service conductors under NEC 310.12 — 4 AWG copper or 2 AWG aluminum at 100 A, 1 AWG or 2/0 at 150 A, 2/0 or 4/0 at 200 A, 400 or 600 kcmil at 400 A; and dissimilar metals not intermixed unless the device is listed for it (NEC 110.14) <https://www.dli.mn.gov/sites/default/files/pdf/eli_inspection_checklist2023NEC.pdf>

The site's pages for the documents these name:

- [National Electrical Code (NFPA 70)](https://craftquantities.com/standards/nfpa/nec/)

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**Why does the page say 250 kcmil when a 200 A service uses 4/0 aluminum with 2/0 copper?**

Because the two answers stand on different bases. The pairing of 2/0 copper with 4/0 aluminum for a 200 A dwelling service is the code's ampacity rule for services and main feeders, as Minnesota's 2023 NEC checklist reproduces it. This page matches resistance: 4/0 aluminum has about 3% more resistance than 2/0 copper, so on the same run it drops about 3% more voltage, and 250 kcmil is the first size that does not. Both facts are true at once; the code decides what may be installed.

**How much bigger does aluminum have to be?**

About 1.64 times the area of the copper for the same resistance — 21.2 against 12.9 in the US constants, and 1.639 from first principles in the National Bureau of Standards' aluminum wire tables. In AWG that is a little more than two gauge steps, which is why two steps up usually comes out a few percent short and the page names both sizes.

**Can I use this to swap copper for aluminum on my circuit?**

Not on its own. It answers one question — which aluminum size has no more resistance — and a substitution also has to satisfy the ampacity tables at the termination temperature rating, the overcurrent device, terminations listed for aluminum and the run's voltage drop. That is the electrician's design to make, under the code in force.

**Why are mm² answers sometimes equal and sometimes a size over?**

Because the comparison is of IEC 60228's tabulated maximum resistances, size by size, and the two metals' series do not line up evenly. Copper at 6 mm² and aluminium at 10 mm² are both listed at 3.08 Ω/km (0.939 Ω per 1,000 ft), so they are equal; 150 mm² copper is 0.124 and 240 mm² aluminium 0.125 (0.0378 and 0.0381 Ω per 1,000 ft), so the larger 300 mm² is the first that is not over, though 240 is within 1%.

## Related calculators

- [Wire Gauge Voltage Drop Calculator (Copper or Aluminum, AWG to 1,000 kcmil)](https://craftquantities.com/calculators/electrical/wire-gauge-voltage-drop-calculator/)
- [Cable Voltage Drop Calculator (mm², Copper or Aluminium)](https://craftquantities.com/calculators/electrical/cable-voltage-drop-calculator/)
- [AWG to mm² Wire Size Calculator](https://craftquantities.com/calculators/electrical/awg-to-mm2-calculator/)
- [Wire Gauge to Amperage Calculator](https://craftquantities.com/calculators/electrical/wire-gauge-to-amperage-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/copper-aluminum-wire-equivalent-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/copper-aluminum-wire-equivalent-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `copper-aluminum-wire-equivalent-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/copper-aluminum-wire-equivalent-calculator.json

---
Source: https://craftquantities.com/calculators/electrical/copper-aluminum-wire-equivalent-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.