# Cable Voltage Drop Calculator (mm², Copper or Aluminium)

> The voltage a copper or aluminium cable loses on a run, worked from its IEC 60228 resistance at the conductor temperature, single or three phase.

Page: https://craftquantities.com/calculators/electrical/cable-voltage-drop-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.0.0, sources checked 2026-10-05, 39 published test vectors.

Voltage drop: 7.25 V for Length of run 66 ft, the page's opening figures; on the metric page, 20 m gives 7.21 V. Source: Bayerische Kabelwerke AG (Bayka), Conductor resistance at 20 °C (68 °F) acc. to EN 60228.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| Conductor | `material` | Copper | Copper | `copper`, `aluminium` |
| Conductor size (mm²) | `size` | 2.5 mm² | 2.5 mm² | `1`, `1.5`, `2.5`, `4`, `6`, `10`, `16`, `25`, `35`, `50`, `70`, `95`, `120`, `150`, `185`, `240`, `300` |
| Conductor temperature | `conductorTemp` | 75 °C (167 °F) — cable whose insulation carries that rating | 75 °C (167 °F) — cable whose insulation carries that rating | `70`, `75`, `90` |
| Circuit | `phase` | Single phase or DC, out and back | Single phase or DC, out and back | `single`, `three` |
| Length of run (one way) | `length` | 20 m | 66 ft | mm, cm, m, in, ft, yd; range 0.1–2000 m |
| Current (A) | `current` | 20 | 20 | range 0.1–2000 |
| Supply voltage | `voltage` | 230 V single phase | 230 V single phase | `230`, `240`, `400`, `415`, `other` |
| Voltage you are working at (V) | `customVoltage` | 48 | 48 | range 6–1500 |

- **Conductor**: Copper, or aluminium — the conductor metal on the cable's data sheet.
- **Conductor size (mm²)**: The cross-section of one conductor, as printed on the cable.
- **Conductor temperature**: The cable's maximum operating temperature, from its data sheet.
- **Circuit**: A single-phase or DC circuit, or a balanced three-phase one.
- **Length of run (one way)**: The route length from the origin of the circuit to the load, one way.
- **Current (A)**: The circuit's design current, in amps.
- **Supply voltage**: The nominal supply voltage — line to line for three phase.
- **Voltage you are working at (V)**: Any nominal voltage the list does not carry.

`customVoltage` applies only when `voltage` is `other`.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Voltage drop** | 7.21 V |
| Voltage drop as a share of the supply | 3.13 % |
| Voltage at the load | 222.79 V |
| Conductor size in mm² | 2.5 mm² |
| Voltage drop per amp per metre (mV/A/m) | 18.02 |
| Conductor resistance at the chosen temperature (Ω/km) | 9.01 |
| IEC 60228 resistance at 20 °C (68 °F), Ω/km | 7.41 |

### US customary

| Result | Value |
|---|---|
| **Voltage drop** | 7.25 V |
| Voltage drop as a share of the supply | 3.15 % |
| Voltage at the load | 222.75 V |
| Conductor size in mm² | 2.5 mm² |
| Voltage drop per amp per metre (mV/A/m) | 18.02 |
| Conductor resistance at the chosen temperature (Ω/km) | 9.01 |
| IEC 60228 resistance at 20 °C (68 °F), Ω/km | 7.41 |

## How it is worked out

Worked from the conductor's IEC 60228 resistance at the chosen temperature: the same quantity the published mV/A/m tables give for a cable this size, where reactance is negligible. Compare the percentage with the limit your wiring rules set.

The working the page shows, in order: Voltage drop as a share of the supply; Voltage at the load; Conductor size in mm²; Voltage drop per amp per metre (mV/A/m); Conductor resistance at the chosen temperature (Ω/km); IEC 60228 resistance at 20 °C (68 °F), Ω/km; then voltage drop.

The method, derived in full:

- [Voltage Drop and Conductor Sizing](https://craftquantities.com/methodology/voltage-drop-and-conductor-sizing/): Why the run length doubles, why a 12 V circuit suffers a hundred times the percentage loss of a 120 V one, and why ampacity answers a different question entirely.

What this calculation does not cover:

- Resistance only. BS 7671's Appendix 4 and AS/NZS 3008.1.1 tabulate an impedance for the larger cables, which adds the conductor's reactance to its resistance; from about 25 mm² that reactive part is a growing share of the drop and this page leaves it out, so for a large cable the published table's figure is the one to use. Neither table is reproduced here.
- The conductor temperature is the one chosen, held along the whole run. The published tables assume the cable is at its maximum operating temperature; a lightly loaded cable runs cooler and drops a little less, and one bunched or in hot surroundings may sit at its limit sooner than the current suggests.
- The √3 for three phase holds only while the three line currents are equal and the neutral carries nothing. A load fed from one line and the neutral of a 400 V supply is a 230 V single-phase circuit, and should be entered as one; an unbalanced three-phase load needs each line worked on its own.
- The current used is the one entered. The wiring rules say which current a calculation should use — the design current, or for a circuit whose load is spread along it, a figure they set — and which length; this page takes both as typed.
- Voltage drop is not current-carrying capacity. A cable inside the voltage-drop limit can still be too small for the current once its installation method, grouping and surroundings are applied, and that is a separate selection under the wiring rules, made by the electrician who designs and certifies the circuit.
- The limit the drop is judged against belongs to the wiring rules in force — BS 7671's Appendix 4 in the UK and, in Australia and New Zealand, AS/NZS 3000 — and to any tighter figure an equipment maker sets. The page reports the percentage and does not judge it.
- The resistances are IEC 60228's for plain conductors of class 1 and 2, the solid and stranded conductors of fixed wiring. Bayka lists flexible conductors (classes 5 and 6) and tinned ones at a higher resistance for most sizes — flexible 2.5 mm² copper 7.7% above the plain figure, flexible 1.5 mm² 9.9%, tinned flexible 2.5 mm² 10.8% — so a flexible cord or an extension lead drops more than this page shows.

A professional must decide:

- Voltage drop is not current-carrying capacity. A cable inside the voltage-drop limit can still be too small for the current once its installation method, grouping and surroundings are applied, and that is a separate selection under the wiring rules, made by the electrician who designs and certifies the circuit.
- Electrics: circuit design, protection, cable sizing and the work itself are for a qualified or licensed electrician, under the rules where you build.

## Sources

As the calculator cites them (sources checked 2026-10-05):

- Bayerische Kabelwerke AG (Bayka), Conductor resistance at 20 °C (68 °F) acc. to EN 60228: maximum DC resistance of plain copper and aluminium conductors, class 1 and 2 — 2.5 mm² copper 7.41 Ω/km (2.26 Ω per 1,000 ft), 16 mm² copper 1.15 (0.351), 25 mm² aluminium 1.20 (0.366) — and of flexible (class 5 and 6) and tinned copper, mostly higher: flexible 2.5 mm² copper 7.98 (2.43), tinned and flexible 8.21 (2.50) <https://www.bayka.de/en/service/technical-information/conductor-resistance>
- Prysmian 6242Y data sheet (BS 6004 flat twin and earth): maximum conductor temperature 70 °C (158 °F); conductor resistance at 20 °C (68 °F) 18.1, 12.1, 7.41, 4.61, 3.08, 1.83 and 1.15 Ω/km for 1 to 16 mm² (5.52, 3.69, 2.26, 1.41, 0.939, 0.558 and 0.351 Ω per 1,000 ft); current ratings referred to BS 7671 Table 4D5 <https://datasheet.prysmian.com/pdf/datasheet/en-GB/312416/GB00_6242Y>
- NBS Handbook 100, Copper Wire Tables (National Bureau of Standards): the annealed copper standard, 0.017241 Ω·mm²/m (10.371 Ω·cmil/ft) at 20 °C (68 °F), with a temperature coefficient of 0.00393 per °C (0.00218 per °F) at 20 °C <https://nvlpubs.nist.gov/nistpubs/Legacy/hb/nbshandbook100.pdf>
- NBS Handbook 109, Aluminum Wire Tables (National Bureau of Standards with The Aluminum Association), Table 1: EC-H19 aluminium at 61.0% IACS, 0.028264 Ω·mm²/m (17.002 Ω·cmil/ft) at 20 °C (68 °F), temperature coefficient 0.00403 per °C (0.00224 per °F) at 20 °C <https://nvlpubs.nist.gov/nistpubs/Legacy/hb/nbshandbook109.pdf>
- Voltage drop from resistance: a single-phase or DC circuit loses I × R on the way out and again on the way back, 2 × R per metre; a balanced three-phase circuit loses √3 × R per metre between lines. Ω/km is numerically mV/A per metre, and 0.3048 times it is mV/A per foot

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**Why doesn't the page show BS 7671's mV/A/m figure?**

Because BS 7671 is sold by the IET and its tables cannot be reproduced. The page works the same quantity from the conductor's published IEC 60228 resistance at the cable's maximum operating temperature, which for cables up to 16 mm² is the whole of what the table's figure contains. For 2.5 mm² copper at 70 °C (158 °F) that is 17.73 mV/A/m, or 5.40 mV per amp per foot of run; from 25 mm² up the table adds reactance, so use its impedance figure for big cables.

**How is this different from the AWG voltage drop page?**

That page is the US method: conductor areas in circular mils, a K constant at 75 °C (167 °F) taken from the NEC's Chapter 9, and the code's 3% and 5% suggestions. This one works in square millimetres from the IEC 60228 resistances British, European and Australian cables are made to, at the temperature you choose, and leaves the limit to the wiring rules you work under.

**Which temperature should I choose?**

The cable's maximum operating temperature, from its data sheet, because that is what the published tables assume and it gives the larger, safer drop. Prysmian's 6242Y twin and earth is 70 °C (158 °F); thermosetting cables such as XLPE run to 90 °C (194 °F). Between the two the same copper conductor's resistance, and so its drop, differs by about 7%.

**Why does aluminium drop so much more?**

Its resistance is about 1.6 times copper's for the same area — 1.20 Ω/km (0.366 Ω per 1,000 ft) for 25 mm² aluminium against 0.727 (0.222) for copper at 20 °C (68 °F) — and it rises slightly faster with temperature. To hold the same drop, the aluminium conductor is two sizes larger than copper of 10 to 70 mm², and three sizes larger from 95 mm² up; the copper-to-aluminium page finds the size with no more resistance than a given copper one.

**What does mV/A/m mean?**

Millivolts lost per amp of current per metre of run. Multiply it by the current and by the length in metres, and divide by 1,000 to get volts; for a run measured in feet, multiply the feet by 0.3048 first. It is the same number as the conductor's resistance in Ω/km, doubled for a single-phase circuit or multiplied by √3 for a three-phase one.

## Related calculators

- [Wire Gauge Voltage Drop Calculator (Copper or Aluminum, AWG to 1,000 kcmil)](https://craftquantities.com/calculators/electrical/wire-gauge-voltage-drop-calculator/)
- [Copper to Aluminum Wire Size Calculator (Aluminium Equivalent, AWG and mm²)](https://craftquantities.com/calculators/electrical/copper-aluminum-wire-equivalent-calculator/)
- [AWG to mm² Wire Size Calculator](https://craftquantities.com/calculators/electrical/awg-to-mm2-calculator/)
- [Watts, Amps and kVA Calculator (Any Voltage, AC or DC)](https://craftquantities.com/calculators/electrical/watts-amps-kva-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/cable-voltage-drop-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/cable-voltage-drop-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `cable-voltage-drop-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/cable-voltage-drop-calculator.json

---
Source: https://craftquantities.com/calculators/electrical/cable-voltage-drop-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.