# Breaker Size Calculator

> Find the smallest standard breaker rating for a load in watts or amps, with the continuous-load rule applied and the conductor ampacity it then demands.

Page: https://craftquantities.com/calculators/electrical/breaker-size-calculator/ (calculator). This is the page's Markdown copy; the HTML page is the canonical version.

Version 1.0.0, sources checked 2026-09-11, 5 published test vectors.

Minimum breaker size: 25 A for Load 4800, the page's opening figures. Sources are cited below.

## Inputs

A length, area or volume is entered with its unit. The page opens on the values below: a metric reader sees the metric column, a US customary reader the other.

| Input | id | Opens at (metric) | Opens at (US customary) | Accepts |
|---|---|---|---|---|
| I know the load as | `loadMode` | Watts (or VA) from the nameplate | Watts (or VA) from the nameplate | `watts`, `amps` |
| Load (W or VA) | `loadWatts` | 4800 | 4800 | range 1–200000 |
| Load current (A) | `loadAmps` | 20 | 20 | range 0.1–800 |
| Circuit voltage | `voltage` | 240 V (North American large appliance) | 240 V (North American large appliance) | `120`, `208`, `230`, `240`, `277`, `400`, `480` |
| Phase | `phase` | Single phase | Single phase | `single`, `three` |
| Continuous load | `continuous` | Yes — runs three hours or more at a time | Yes — runs three hours or more at a time | `yes`, `no` |

- **I know the load as**: Whether the appliance's rating plate gives you power or current.
- **Load (W or VA)**: The nameplate power rating of the equipment on this circuit.
- **Load current (A)**: The nameplate current draw of the equipment on this circuit.
- **Circuit voltage**: The nominal voltage of the circuit the equipment is connected to.
- **Phase**: Whether the circuit is single or three phase.
- **Continuous load**: Whether the load runs for three hours or more at maximum current.

`loadWatts` applies only when `loadMode` is `watts`.
`loadAmps` applies only when `loadMode` is `amps`.

## The answer on the opening values

Worked exactly as the page works it, on the values each system opens on.

### Metric

| Result | Value |
|---|---|
| **Minimum breaker size** | 25 A |
| Load current | 20 A |
| Required minimum at 125% (continuous) | 25 A |
| Minimum conductor ampacity after corrections | 25 A |
| Headroom to the next trip point | 0 % |
| Load as a share of the breaker | 80 % |

### US customary

| Result | Value |
|---|---|
| **Minimum breaker size** | 25 A |
| Load current | 20 A |
| Required minimum at 125% (continuous) | 25 A |
| Minimum conductor ampacity after corrections | 25 A |
| Headroom to the next trip point | 0 % |
| Load as a share of the breaker | 80 % |

- Confidence: medium.

## How it is worked out

The arithmetic is the code's and it is exact. What makes this a screening figure rather than a design is everything it cannot see: the conductor's insulation rating, the ambient temperature, how many conductors share the raceway, the length of the run, and what the terminals at each end are listed for. Any of those can move the required conductor — and therefore the acceptable device — by a size or more.

The working the page shows, in order: Load current; Required minimum at 125% (continuous); Minimum conductor ampacity after corrections; Headroom to the next trip point; Load as a share of the breaker; then minimum breaker size.

The method, derived in full:

- [Electrical Demand, Three-Phase Power and Panel Capacity](https://craftquantities.com/methodology/electrical-demand-and-panel-capacity/): Why the sum of every nameplate is a load no building ever draws, why a motor's conductors are sized from a table rather than from its nameplate, and why a dark room needs far more light than a pale one for the same lux.

What this calculation does not cover:

- A breaker protects the conductor, not the appliance. The rating above is the minimum the LOAD demands; it is only the right breaker if the conductor behind it is rated to carry it after every applicable correction. Fitting a larger breaker to stop a circuit tripping, without changing the wire, removes the protection the wire depends on and is the most common serious mistake made in a domestic panel.
- Motors are not sized this way. NEC Article 430 sizes motor branch-circuit short-circuit and ground-fault protection from Table 430.52, and an inverse-time breaker on a motor is routinely rated well above the motor's full-load current so that starting inrush does not trip it — while the overload protection is a separate device sized much closer to the running current. Putting a motor's nameplate current into this page gives a breaker that will trip on starting.
- Converting watts to amps assumes a power factor of one. That is correct for resistive loads — heaters, hobs, water heaters, incandescent lighting — and optimistic for motors, welders, electronic supplies and anything with a substantial inductive component, where the real current is higher than the power rating alone suggests. Where the plate gives amps, use amps.
- Conductor ampacity has not been calculated here, only stated as a minimum. The actual conductor is chosen from the ampacity tables at the insulation's temperature rating, then corrected for ambient temperature and for the number of current-carrying conductors bundled together, and finally limited by the temperature rating of the terminations at both ends — which on most equipment is 75 °C regardless of what the cable itself can take.
- Voltage drop is a separate constraint and often the binding one. On a long run the conductor that satisfies ampacity may still deliver too little voltage at the load, and the fix is a larger conductor — which does not change the breaker, because the breaker still has to match the load it protects.
- This is NEC arithmetic. Circuit protection outside North America follows BS 7671, the relevant IEC standards or the local equivalent, which use different device characteristics, different standard ratings and a different treatment of continuous duty. The voltages offered here include European and Australian values because the load arithmetic is universal; the 125% rule and the standard rating list are not.

A professional must decide:

- Electrics: circuit design, protection, cable sizing and the work itself are for a qualified or licensed electrician, under the rules where you build.

## Sources

As the calculator cites them (sources checked 2026-09-11):

- NEC 240.6(A): standard ampere ratings for inverse-time circuit breakers and fuses — 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600 A
- NEC 210.20(A) and 215.3: the overcurrent device rating shall be not less than 100% of the noncontinuous load plus 125% of the continuous load
- NEC 210.19(A)(1): branch-circuit conductors shall have an ampacity not less than the same figure, before any temperature or conduit-fill correction
- NEC 240.4: conductors shall be protected at their ampacity — the device rating follows the conductor, not the load it happens to serve
- NEC Article 430 governs motor branch circuits: short-circuit and ground-fault protection is sized from Table 430.52 and may substantially exceed the motor's full-load current, so this page does not apply to motors

The site's pages for the documents these name:

- [National Electrical Code (NFPA 70)](https://craftquantities.com/standards/nfpa/nec/)

A code or standard has force only where a jurisdiction has adopted it, usually with local amendments; check what is in force with the authority where you build.

## Questions answered on the page

**My circuit keeps tripping. Can I just fit a bigger breaker?**

No — that is the one change that turns an inconvenience into a fire risk. The breaker is sized to the conductor, and a bigger breaker lets the same wire carry more current than it is rated for before anything intervenes. A circuit that trips is either overloaded, which means moving some of the load, or faulty, which means finding the fault. If the load genuinely belongs there, the wire has to grow before the breaker can.

**Why 125% for a continuous load?**

Because breakers and conductors are rated on the assumption that they get to cool down. A load that runs for three hours or more at full current never gives them that chance, so the code requires the device and the conductor to be sized at 125% of it — equivalently, a standard breaker is loaded to no more than 80% continuously. Three hours is the NEC's own dividing line, not a rule of thumb.

**What is the next-standard-size-up rule?**

NEC 240.4(B) lets you protect a conductor with the next larger standard device where the conductor's ampacity falls between two standard ratings, for circuits up to 800 A and where the circuit does not supply receptacles for cord-and-plug-connected portable loads. It is a rule about protecting a conductor, not about serving a load — and it is worth keeping the two apart, because the first says what a given wire may be protected at while the second says what a given load demands.

**Does this work for a motor?**

No, and putting a motor's full-load current in will give you a breaker that trips every time it starts. Article 430 sizes motor protection from Table 430.52, and an inverse-time breaker is commonly permitted at 250% of full-load current so that inrush passes without tripping. The motor's overload protection is a separate device sized close to the running current — the two jobs are split, which is exactly why the general rule does not apply.

**Can I use this outside North America?**

For the load arithmetic, yes — watts, volts and the square root of three do not change at a border. For the device, no. BS 7671 and the IEC standards use different standard ratings, different breaker curves (B, C and D types chosen by inrush rather than by a flat percentage) and a different treatment of continuous duty. Take the current from here and size the protective device to the local standard.

**Why is the breakdown showing the load as a percentage of the breaker?**

Because it is the number an inspector thinks in, and it makes the continuous rule visible. A continuous load correctly sized lands at or below 80% of the breaker; anything above that on a continuous circuit means the 125% has not been applied. On an intermittent circuit a higher figure is acceptable, which is exactly the distinction the percentage makes easy to see.

## Related calculators

- [Electrical Circuit Load Calculator](https://craftquantities.com/calculators/electrical/electrical-load-calculator/)
- [Amperage to Wire Gauge Calculator](https://craftquantities.com/calculators/electrical/amperage-to-wire-gauge-calculator/)
- [EV Charger Circuit Calculator](https://craftquantities.com/calculators/electrical/ev-charger-circuit-calculator/)

## Run it from a program

- REST: `GET https://api.craftquantities.com/v1/calculate/breaker-size-calculator` with each input as a query parameter, a length, area or volume with its unit; `https://api.craftquantities.com/v1/describe/breaker-size-calculator` lists the inputs.
- MCP: the `calculate` tool at https://api.craftquantities.com/mcp with `slug` `breaker-size-calculator`.
- Definition and test vectors: https://craftquantities.com/api/v1/calculators/breaker-size-calculator.json

---
Source: https://craftquantities.com/calculators/electrical/breaker-size-calculator/
Craft Quantities: free to read, cite and link to; the pages are not licensed for republication. Quantities only: no prices, no design and no certification.