  "slug": "wire-gauge-voltage-drop-calculator",
  "category": "electrical",
  "title": "Wire Gauge Voltage Drop Calculator (Copper or Aluminum, AWG to 1,000 kcmil)",
  "description": "How much voltage a copper or aluminum run loses over distance — 14 AWG to 1,000 kcmil, single or three phase — against the 3% and 5% the NEC suggests.",
  "url": "https://craftquantities.com/calculators/electrical/wire-gauge-voltage-drop-calculator/",
  "json": "https://craftquantities.com/api/v1/calculators/wire-gauge-voltage-drop-calculator.json",
  "inputCount": 7,
  "testCaseCount": 25,
  "sourceCount": 4,
  "lastVerified": "2026-10-05",
  "translations": {
    "es-US": "https://craftquantities.com/es/calculators/electrical/wire-gauge-voltage-drop-calculator/"
  },
  "citation": {
    "author": "Craft Quantities",
    "title": "Wire Gauge Voltage Drop Calculator (Copper or Aluminum, AWG to 1,000 kcmil)",
    "version": "1.1.0",
    "sourcesChecked": "2026-10-05",
    "url": "https://craftquantities.com/calculators/electrical/wire-gauge-voltage-drop-calculator/",
    "accessDate": null,
    "accessDateNote": "Add the date you retrieved this. It is deliberately absent: a static file cannot know when you read it, and the build date would be wrong.",
    "permanentVersionedUrl": null,
    "permanentVersionedUrlNote": "Not offered. This site keeps no archive of previous builds, so any such URL would resolve to the current page or to nothing. The version and sourcesChecked fields identify the calculation instead.",
    "formats": {
      "plain": "Craft Quantities. Wire Gauge Voltage Drop Calculator (Copper or Aluminum, AWG to 1,000 kcmil). Version 1.1.0. Sources checked 2026-10-05. https://craftquantities.com/calculators/electrical/wire-gauge-voltage-drop-calculator/",
      "apa": "Craft Quantities. (2026). Wire Gauge Voltage Drop Calculator (Copper or Aluminum, AWG to 1,000 kcmil) (Version 1.1.0) [Web calculator]. Retrieved from https://craftquantities.com/calculators/electrical/wire-gauge-voltage-drop-calculator/",
      "harvard": "Craft Quantities (2026) Wire Gauge Voltage Drop Calculator (Copper or Aluminum, AWG to 1,000 kcmil) (Version 1.1.0). Available at: https://craftquantities.com/calculators/electrical/wire-gauge-voltage-drop-calculator/",
      "bibtex": "@misc{craftquantities-calculators-electrical-wire-gauge-voltage-drop-calculator,\n  author       = {{Craft Quantities}},\n  title        = {Wire Gauge Voltage Drop Calculator (Copper or Aluminum, AWG to 1,000 kcmil)},\n  version      = {1.1.0},\n  year         = {2026},\n  howpublished = {\\url{https://craftquantities.com/calculators/electrical/wire-gauge-voltage-drop-calculator/}},\n}"
    }
  },
  "inputs": [
    {
      "id": "material",
      "label": "Conductor metal",
      "type": "select",
      "defaultValue": "copper",
      "options": [
        {
          "value": "copper",
          "label": "Copper (uncoated)"
        },
        {
          "value": "aluminum",
          "label": "Aluminum"
        }
      ],
      "help": "Copper, or aluminum — the metal printed on the jacket (CU or AL)."
    },
    {
      "id": "wireGauge",
      "label": "Conductor size (AWG or kcmil)",
      "type": "select",
      "defaultValue": "12",
      "options": [
        {
          "value": "14",
          "label": "14 AWG"
        },
        {
          "value": "12",
          "label": "12 AWG"
        },
        {
          "value": "10",
          "label": "10 AWG"
        },
        {
          "value": "8",
          "label": "8 AWG"
        },
        {
          "value": "6",
          "label": "6 AWG"
        },
        {
          "value": "4",
          "label": "4 AWG"
        },
        {
          "value": "3",
          "label": "3 AWG"
        },
        {
          "value": "2",
          "label": "2 AWG"
        },
        {
          "value": "1",
          "label": "1 AWG"
        },
        {
          "value": "1/0",
          "label": "1/0 AWG"
        },
        {
          "value": "2/0",
          "label": "2/0 AWG"
        },
        {
          "value": "3/0",
          "label": "3/0 AWG"
        },
        {
          "value": "4/0",
          "label": "4/0 AWG"
        },
        {
          "value": "250",
          "label": "250 kcmil"
        },
        {
          "value": "300",
          "label": "300 kcmil"
        },
        {
          "value": "350",
          "label": "350 kcmil"
        },
        {
          "value": "400",
          "label": "400 kcmil"
        },
        {
          "value": "500",
          "label": "500 kcmil"
        },
        {
          "value": "600",
          "label": "600 kcmil"
        },
        {
          "value": "750",
          "label": "750 kcmil"
        },
        {
          "value": "1000",
          "label": "1,000 kcmil"
        }
      ],
      "help": "The size printed on the jacket: an AWG number up to 4/0, then kcmil."
    },
    {
      "id": "phase",
      "label": "Circuit",
      "type": "select",
      "defaultValue": "single",
      "options": [
        {
          "value": "single",
          "label": "Single phase (or DC), out and back"
        },
        {
          "value": "three",
          "label": "Three phase, balanced"
        }
      ],
      "help": "Single phase — including a 240 V circuit and DC — or a balanced three-phase circuit."
    },
    {
      "id": "oneWayLength",
      "label": "One-Way Wire Run Length",
      "type": "number",
      "dimension": "length",
      "defaultValue": 15,
      "min": 0.01,
      "max": 600,
      "step": 0.5,
      "help": "The distance from the panel to the load, one direction only."
    },
    {
      "id": "currentAmps",
      "label": "Current Draw",
      "type": "number",
      "defaultValue": 10,
      "min": 0.5,
      "max": 2000,
      "step": 0.5,
      "help": "The expected current draw of the load in amps."
    },
    {
      "id": "circuitVoltage",
      "label": "Circuit Voltage",
      "type": "select",
      "defaultValue": "120",
      "options": [
        {
          "value": "120",
          "label": "120 V"
        },
        {
          "value": "208",
          "label": "208 V (three phase, or two lines of 208Y/120)"
        },
        {
          "value": "240",
          "label": "240 V"
        },
        {
          "value": "277",
          "label": "277 V (line to neutral of 480Y/277)"
        },
        {
          "value": "480",
          "label": "480 V (three phase)"
        },
        {
          "value": "other",
          "label": "Another voltage — type it"
        }
      ],
      "help": "The nominal circuit voltage — line to line for three phase."
    },
    {
      "id": "customVoltage",
      "label": "Voltage you are working at (V)",
      "type": "number",
      "defaultValue": 600,
      "min": 6,
      "max": 1000,
      "step": 1,
      "help": "Any nominal voltage the list does not carry."
    }
  ],
  "sources": [
    {
      "label": "Standard single-phase voltage drop formula: Vdrop = (2 x K x one-way length in ft x amps) / circular mils, K=12.9 for copper"
    },
    {
      "label": "NEC recommends keeping voltage drop to 3% or less for branch circuits (and 5% total including feeders) for reasonable efficiency, though it is a recommendation, not a hard code violation"
    },
    {
      "label": "IAEI Magazine, \"Voltage Drop Formulas\" (March/April 2017): K is a conductor's resistance per foot times its area in circular mils — the resistance of a conductor one circular mil in area and one foot long — at 75 °C (167 °F), from NEC Chapter 9 Table 8: 1,000 kcmil uncoated copper at 0.0129 Ω per 1,000 ft (0.0423 Ω/km) gives 12.9, 1,000 kcmil aluminum at 0.0212 Ω per 1,000 ft (0.0696 Ω/km) gives 21.2, and every size in the table works out close to these; the single-phase multiplier 2 becomes 1.732 for three phase",
      "url": "https://iaeimagazine.org/electrical-fundamentals/voltage-drop-formulas/"
    },
    {
      "label": "EC&M, \"Stumped by the Code? NEC Requirements for Conductor Material Types and Sizing Requirements\" (Mike Holt, 9 February 2023, on the 2023 NEC): Section 310.3(A) sets the smallest conductors at 14 AWG for copper and 12 AWG for aluminum or copper-clad aluminum, except where the code permits otherwise",
      "url": "https://www.ecmweb.com/home/article/21259364/stumped-by-the-code-nec-requirements-for-conductor-material-types-and-sizing-requirements"
    }
  ],
  "testCases": [
    {
      "name": "12 AWG, 15 m (49.2 ft) run, 10 A, 120 V",
      "inputs": {
        "wireGauge": "12",
        "oneWayLength": 15,
        "currentAmps": 10,
        "circuitVoltage": "120"
      },
      "expected": 1.945,
      "toleranceDecimalPlaces": 1,
      "unit": "V",
      "confidence": "high",
      "steps": [
        {
          "label": "Voltage drop",
          "value": 1.620322919053189,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 118.05561249713617,
          "unit": "V"
        },
        {
          "label": "K constant, Ω·cmil per ft",
          "value": 12.9
        },
        {
          "label": "Conductor area, circular mils",
          "value": 6530
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "14 AWG, 30 m (98.4 ft) run, 15 A, 120 V",
      "inputs": {
        "wireGauge": "14",
        "oneWayLength": 30,
        "currentAmps": 15,
        "circuitVoltage": "120"
      },
      "expected": 9.27,
      "toleranceDecimalPlaces": 0.2,
      "unit": "V",
      "confidence": "low",
      "steps": [
        {
          "label": "Voltage drop",
          "value": 7.7231450083338125,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 110.73222598999942,
          "unit": "V"
        },
        {
          "label": "K constant, Ω·cmil per ft",
          "value": 12.9
        },
        {
          "label": "Conductor area, circular mils",
          "value": 4110
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "aluminum at the same size drops 21.2/12.9 times as much: 12 AWG, 15 m (49.2 ft), 10 A is 3.195 V",
      "inputs": {
        "material": "aluminum",
        "wireGauge": "12",
        "phase": "single",
        "oneWayLength": 15,
        "currentAmps": 10,
        "circuitVoltage": "120"
      },
      "expected": 3.19542,
      "toleranceDecimalPlaces": 3,
      "unit": "V",
      "confidence": "medium",
      "steps": [
        {
          "label": "Voltage drop",
          "value": 2.662856270071907,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 116.80457247591372,
          "unit": "V"
        },
        {
          "label": "K constant, Ω·cmil per ft",
          "value": 21.2
        },
        {
          "label": "Conductor area, circular mils",
          "value": 6530
        }
      ],
      "basis": "cited",
      "sourceIndex": 2
    },
    {
      "name": "three phase at 480 V: 250 kcmil copper, 100 ft (30.48 m), 200 A drops 1.787 V",
      "inputs": {
        "material": "copper",
        "wireGauge": "250",
        "phase": "three",
        "oneWayLength": 30.48,
        "currentAmps": 200,
        "circuitVoltage": "480"
      },
      "expected": 1.787424,
      "toleranceDecimalPlaces": 4,
      "unit": "V",
      "confidence": "high",
      "steps": [
        {
          "label": "Voltage drop",
          "value": 0.37238000000000004,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 478.212576,
          "unit": "V"
        },
        {
          "label": "K constant, Ω·cmil per ft",
          "value": 12.9
        },
        {
          "label": "Conductor area, circular mils",
          "value": 250000
        }
      ],
      "basis": "cited",
      "sourceIndex": 2
    },
    {
      "name": "the same run single phase drops 2/1.732 times as much: 2.064 V",
      "inputs": {
        "material": "copper",
        "wireGauge": "250",
        "phase": "single",
        "oneWayLength": 30.48,
        "currentAmps": 200,
        "circuitVoltage": "240"
      },
      "expected": 2.064,
      "toleranceDecimalPlaces": 4,
      "unit": "V",
      "confidence": "high",
      "steps": [
        {
          "label": "Voltage drop",
          "value": 0.86,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 237.936,
          "unit": "V"
        },
        {
          "label": "K constant, Ω·cmil per ft",
          "value": 12.9
        },
        {
          "label": "Conductor area, circular mils",
          "value": 250000
        }
      ],
      "basis": "cited",
      "sourceIndex": 2
    },
    {
      "name": "aluminum 4/0, 150 ft (45.72 m), 150 A single phase drops 4.509 V",
      "inputs": {
        "material": "aluminum",
        "wireGauge": "4/0",
        "phase": "single",
        "oneWayLength": 45.72,
        "currentAmps": 150,
        "circuitVoltage": "240"
      },
      "expected": 4.508507,
      "toleranceDecimalPlaces": 4,
      "unit": "V",
      "confidence": "high",
      "steps": [
        {
          "label": "Voltage drop",
          "value": 1.8785444234404536,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 235.49149338374292,
          "unit": "V"
        },
        {
          "label": "K constant, Ω·cmil per ft",
          "value": 21.2
        },
        {
          "label": "Conductor area, circular mils",
          "value": 211600
        }
      ],
      "basis": "cited",
      "sourceIndex": 2
    },
    {
      "name": "1,000 kcmil aluminum is the article's own row: 1,000 ft (304.8 m) at 100 A three phase drops 3.672 V",
      "inputs": {
        "material": "aluminum",
        "wireGauge": "1000",
        "phase": "three",
        "oneWayLength": 304.8,
        "currentAmps": 100,
        "circuitVoltage": "other",
        "customVoltage": 600
      },
      "expected": 3.67184,
      "toleranceDecimalPlaces": 4,
      "unit": "V",
      "confidence": "high",
      "steps": [
        {
          "label": "Voltage drop",
          "value": 0.6119733333333333,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 596.32816,
          "unit": "V"
        },
        {
          "label": "K constant, Ω·cmil per ft",
          "value": 21.2
        },
        {
          "label": "Conductor area, circular mils",
          "value": 1000000
        }
      ],
      "basis": "cited",
      "sourceIndex": 2
    },
    {
      "name": "14 AWG aluminum is below the NEC's 12 AWG minimum for aluminum: no drop is given",
      "inputs": {
        "material": "aluminum",
        "wireGauge": "14",
        "phase": "single",
        "oneWayLength": 15,
        "currentAmps": 10,
        "circuitVoltage": "120"
      },
      "expected": 0,
      "toleranceDecimalPlaces": 6,
      "unit": "V",
      "confidence": "low",
      "steps": [
        {
          "label": "Conductor area, circular mils",
          "value": 4110
        }
      ],
      "basis": "cited",
      "sourceIndex": 3
    },
    {
      "name": "a 277 V lighting circuit: 12 AWG, 100 ft (30.48 m), 10 A drops 3.951 V",
      "inputs": {
        "material": "copper",
        "wireGauge": "12",
        "phase": "single",
        "oneWayLength": 30.48,
        "currentAmps": 10,
        "circuitVoltage": "277"
      },
      "expected": 3.950995,
      "toleranceDecimalPlaces": 4,
      "unit": "V",
      "confidence": "high",
      "steps": [
        {
          "label": "Voltage drop",
          "value": 1.4263521320647277,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 273.0490045941807,
          "unit": "V"
        },
        {
          "label": "K constant, Ω·cmil per ft",
          "value": 12.9
        },
        {
          "label": "Conductor area, circular mils",
          "value": 6530
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "a 208 V three-phase circuit: 10 AWG, 100 ft (30.48 m), 10 A drops 2.152 V",
      "inputs": {
        "material": "copper",
        "wireGauge": "10",
        "phase": "three",
        "oneWayLength": 30.48,
        "currentAmps": 10,
        "circuitVoltage": "208"
      },
      "expected": 2.152486,
      "toleranceDecimalPlaces": 4,
      "unit": "V",
      "confidence": "high",
      "steps": [
        {
          "label": "Voltage drop",
          "value": 1.0348488216985328,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 205.84751445086704,
          "unit": "V"
        },
        {
          "label": "K constant, Ω·cmil per ft",
          "value": 12.9
        },
        {
          "label": "Conductor area, circular mils",
          "value": 10380
        }
      ],
      "basis": "cited",
      "sourceIndex": 2
    },
    {
      "name": "8 AWG copper, 100 ft (30.48 m) at 10 A: 1.562689 V",
      "inputs": {
        "material": "copper",
        "wireGauge": "8",
        "phase": "single",
        "oneWayLength": 30.48,
        "currentAmps": 10,
        "circuitVoltage": "120"
      },
      "expected": 1.562689,
      "toleranceDecimalPlaces": 5,
      "unit": "V",
      "confidence": "high",
      "steps": [
        {
          "label": "Voltage drop",
          "value": 1.3022410660205934,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 118.43731072077529,
          "unit": "V"
        },
        {
          "label": "K constant, Ω·cmil per ft",
          "value": 12.9
        },
        {
          "label": "Conductor area, circular mils",
          "value": 16510
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "6 AWG copper, 100 ft (30.48 m) at 10 A: 0.983232 V",
      "inputs": {
        "material": "copper",
        "wireGauge": "6",
        "phase": "single",
        "oneWayLength": 30.48,
        "currentAmps": 10,
        "circuitVoltage": "120"
      },
      "expected": 0.983232,
      "toleranceDecimalPlaces": 5,
      "unit": "V",
      "confidence": "high",
      "steps": [
        {
          "label": "Voltage drop",
          "value": 0.819359756097561,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 119.01676829268293,
          "unit": "V"
        },
        {
          "label": "K constant, Ω·cmil per ft",
          "value": 12.9
        },
        {
          "label": "Conductor area, circular mils",
          "value": 26240
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "4 AWG copper, 100 ft (30.48 m) at 10 A: 0.618112 V",
      "inputs": {
        "material": "copper",
        "wireGauge": "4",
        "phase": "single",
        "oneWayLength": 30.48,
        "currentAmps": 10,
        "circuitVoltage": "120"
      },
      "expected": 0.618112,
      "toleranceDecimalPlaces": 5,
      "unit": "V",
      "confidence": "high",
      "steps": [
        {
          "label": "Voltage drop",
          "value": 0.515093435553426,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 119.38188787733588,
          "unit": "V"
        },
        {
          "label": "K constant, Ω·cmil per ft",
          "value": 12.9
        },
        {
          "label": "Conductor area, circular mils",
          "value": 41740
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "3 AWG copper, 100 ft (30.48 m) at 10 A: 0.490308 V",
      "inputs": {
        "material": "copper",
        "wireGauge": "3",
        "phase": "single",
        "oneWayLength": 30.48,
        "currentAmps": 10,
        "circuitVoltage": "120"
      },
      "expected": 0.490308,
      "toleranceDecimalPlaces": 5,
      "unit": "V",
      "confidence": "high",
      "steps": [
        {
          "label": "Voltage drop",
          "value": 0.40858988977575067,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 119.5096921322691,
          "unit": "V"
        },
        {
          "label": "K constant, Ω·cmil per ft",
          "value": 12.9
        },
        {
          "label": "Conductor area, circular mils",
          "value": 52620
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "2 AWG copper, 100 ft (30.48 m) at 10 A: 0.388788 V",
      "inputs": {
        "material": "copper",
        "wireGauge": "2",
        "phase": "single",
        "oneWayLength": 30.48,
        "currentAmps": 10,
        "circuitVoltage": "120"
      },
      "expected": 0.388788,
      "toleranceDecimalPlaces": 5,
      "unit": "V",
      "confidence": "high",
      "steps": [
        {
          "label": "Voltage drop",
          "value": 0.32399035563592526,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 119.61121157323689,
          "unit": "V"
        },
        {
          "label": "K constant, Ω·cmil per ft",
          "value": 12.9
        },
        {
          "label": "Conductor area, circular mils",
          "value": 66360
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "1 AWG copper, 100 ft (30.48 m) at 10 A: 0.308281 V",
      "inputs": {
        "material": "copper",
        "wireGauge": "1",
        "phase": "single",
        "oneWayLength": 30.48,
        "currentAmps": 10,
        "circuitVoltage": "120"
      },
      "expected": 0.308281,
      "toleranceDecimalPlaces": 5,
      "unit": "V",
      "confidence": "high",
      "steps": [
        {
          "label": "Voltage drop",
          "value": 0.25690046600549643,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 119.6917194407934,
          "unit": "V"
        },
        {
          "label": "K constant, Ω·cmil per ft",
          "value": 12.9
        },
        {
          "label": "Conductor area, circular mils",
          "value": 83690
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "1/0 AWG copper, 100 ft (30.48 m) at 10 A: 0.244318 V",
      "inputs": {
        "material": "copper",
        "wireGauge": "1/0",
        "phase": "single",
        "oneWayLength": 30.48,
        "currentAmps": 10,
        "circuitVoltage": "120"
      },
      "expected": 0.244318,
      "toleranceDecimalPlaces": 5,
      "unit": "V",
      "confidence": "high",
      "steps": [
        {
          "label": "Voltage drop",
          "value": 0.20359848484848486,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 119.75568181818181,
          "unit": "V"
        },
        {
          "label": "K constant, Ω·cmil per ft",
          "value": 12.9
        },
        {
          "label": "Conductor area, circular mils",
          "value": 105600
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "2/0 AWG copper, 100 ft (30.48 m) at 10 A: 0.193839 V",
      "inputs": {
        "material": "copper",
        "wireGauge": "2/0",
        "phase": "single",
        "oneWayLength": 30.48,
        "currentAmps": 10,
        "circuitVoltage": "120"
      },
      "expected": 0.193839,
      "toleranceDecimalPlaces": 5,
      "unit": "V",
      "confidence": "high",
      "steps": [
        {
          "label": "Voltage drop",
          "value": 0.1615326821938392,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 119.8061607813674,
          "unit": "V"
        },
        {
          "label": "K constant, Ω·cmil per ft",
          "value": 12.9
        },
        {
          "label": "Conductor area, circular mils",
          "value": 133100
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "3/0 AWG copper, 100 ft (30.48 m) at 10 A: 0.153754 V",
      "inputs": {
        "material": "copper",
        "wireGauge": "3/0",
        "phase": "single",
        "oneWayLength": 30.48,
        "currentAmps": 10,
        "circuitVoltage": "120"
      },
      "expected": 0.153754,
      "toleranceDecimalPlaces": 5,
      "unit": "V",
      "confidence": "high",
      "steps": [
        {
          "label": "Voltage drop",
          "value": 0.12812872467222883,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 119.84624553039333,
          "unit": "V"
        },
        {
          "label": "K constant, Ω·cmil per ft",
          "value": 12.9
        },
        {
          "label": "Conductor area, circular mils",
          "value": 167800
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "300 kcmil copper, 100 ft (30.48 m) at 10 A: 0.086 V",
      "inputs": {
        "material": "copper",
        "wireGauge": "300",
        "phase": "single",
        "oneWayLength": 30.48,
        "currentAmps": 10,
        "circuitVoltage": "120"
      },
      "expected": 0.086,
      "toleranceDecimalPlaces": 5,
      "unit": "V",
      "confidence": "high",
      "steps": [
        {
          "label": "Voltage drop",
          "value": 0.07166666666666666,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 119.914,
          "unit": "V"
        },
        {
          "label": "K constant, Ω·cmil per ft",
          "value": 12.9
        },
        {
          "label": "Conductor area, circular mils",
          "value": 300000
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "350 kcmil copper, 100 ft (30.48 m) at 10 A: 0.073714 V",
      "inputs": {
        "material": "copper",
        "wireGauge": "350",
        "phase": "single",
        "oneWayLength": 30.48,
        "currentAmps": 10,
        "circuitVoltage": "120"
      },
      "expected": 0.073714,
      "toleranceDecimalPlaces": 5,
      "unit": "V",
      "confidence": "high",
      "steps": [
        {
          "label": "Voltage drop",
          "value": 0.06142857142857144,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 119.92628571428571,
          "unit": "V"
        },
        {
          "label": "K constant, Ω·cmil per ft",
          "value": 12.9
        },
        {
          "label": "Conductor area, circular mils",
          "value": 350000
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "400 kcmil copper, 100 ft (30.48 m) at 10 A: 0.0645 V",
      "inputs": {
        "material": "copper",
        "wireGauge": "400",
        "phase": "single",
        "oneWayLength": 30.48,
        "currentAmps": 10,
        "circuitVoltage": "120"
      },
      "expected": 0.0645,
      "toleranceDecimalPlaces": 5,
      "unit": "V",
      "confidence": "high",
      "steps": [
        {
          "label": "Voltage drop",
          "value": 0.05375,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 119.9355,
          "unit": "V"
        },
        {
          "label": "K constant, Ω·cmil per ft",
          "value": 12.9
        },
        {
          "label": "Conductor area, circular mils",
          "value": 400000
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "500 kcmil copper, 100 ft (30.48 m) at 10 A: 0.0516 V",
      "inputs": {
        "material": "copper",
        "wireGauge": "500",
        "phase": "single",
        "oneWayLength": 30.48,
        "currentAmps": 10,
        "circuitVoltage": "120"
      },
      "expected": 0.0516,
      "toleranceDecimalPlaces": 5,
      "unit": "V",
      "confidence": "high",
      "steps": [
        {
          "label": "Voltage drop",
          "value": 0.043,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 119.9484,
          "unit": "V"
        },
        {
          "label": "K constant, Ω·cmil per ft",
          "value": 12.9
        },
        {
          "label": "Conductor area, circular mils",
          "value": 500000
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "600 kcmil copper, 100 ft (30.48 m) at 10 A: 0.043 V",
      "inputs": {
        "material": "copper",
        "wireGauge": "600",
        "phase": "single",
        "oneWayLength": 30.48,
        "currentAmps": 10,
        "circuitVoltage": "120"
      },
      "expected": 0.043,
      "toleranceDecimalPlaces": 5,
      "unit": "V",
      "confidence": "high",
      "steps": [
        {
          "label": "Voltage drop",
          "value": 0.03583333333333333,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 119.957,
          "unit": "V"
        },
        {
          "label": "K constant, Ω·cmil per ft",
          "value": 12.9
        },
        {
          "label": "Conductor area, circular mils",
          "value": 600000
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "750 kcmil copper, 100 ft (30.48 m) at 10 A: 0.0344 V",
      "inputs": {
        "material": "copper",
        "wireGauge": "750",
        "phase": "single",
        "oneWayLength": 30.48,
        "currentAmps": 10,
        "circuitVoltage": "120"
      },
      "expected": 0.0344,
      "toleranceDecimalPlaces": 5,
      "unit": "V",
      "confidence": "high",
      "steps": [
        {
          "label": "Voltage drop",
          "value": 0.028666666666666667,
          "unit": "%"
        },
        {
          "label": "Voltage at the load",
          "value": 119.9656,
          "unit": "V"
        },
        {
          "label": "K constant, Ω·cmil per ft",
          "value": 12.9
        },
        {
          "label": "Conductor area, circular mils",
          "value": 750000
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    }
  ]
}