  "version": "v1",
  "source": "https://craftquantities.com",
  "licence": "CC BY 4.0",
  "licenceUrl": "https://creativecommons.org/licenses/by/4.0/",
  "attribution": "Craft Quantities — craftquantities.com",
  "documentation": "https://craftquantities.com/api/",
  "versioning": "Fields are added, never removed or repurposed, within a version. A breaking change becomes /api/v2/ and v1 keeps being built.",
  "slug": "trapeze-hanger-rod-sizing-calculator",
  "category": "materials-quantities",
  "title": "Cable Tray Trapeze Hanger Rod Sizing Calculator",
  "description": "Size the threaded hanger rod under a cable tray trapeze from the loaded tray and the trapeze spacing, and see how hard your chosen rod works in tension.",
  "url": "https://craftquantities.com/calculators/materials-quantities/trapeze-hanger-rod-sizing-calculator/",
  "json": "https://craftquantities.com/api/v1/calculators/trapeze-hanger-rod-sizing-calculator.json",
  "inputCount": 6,
  "testCaseCount": 2,
  "sourceCount": 4,
  "lastVerified": "2026-08-30",
  "citation": {
    "author": "Craft Quantities",
    "title": "Cable Tray Trapeze Hanger Rod Sizing Calculator",
    "version": "1.0.0",
    "sourcesChecked": "2026-08-30",
    "url": "https://craftquantities.com/calculators/materials-quantities/trapeze-hanger-rod-sizing-calculator/",
    "accessDate": null,
    "accessDateNote": "Add the date you retrieved this. It is deliberately absent: a static file cannot know when you read it, and the build date would be wrong.",
    "permanentVersionedUrl": null,
    "permanentVersionedUrlNote": "Not offered. This site keeps no archive of previous builds, so any such URL would resolve to the current page or to nothing. The version and sourcesChecked fields identify the calculation instead.",
    "formats": {
      "plain": "Craft Quantities. Cable Tray Trapeze Hanger Rod Sizing Calculator. Version 1.0.0. Sources checked 2026-08-30. https://craftquantities.com/calculators/materials-quantities/trapeze-hanger-rod-sizing-calculator/",
      "apa": "Craft Quantities. (2026). Cable Tray Trapeze Hanger Rod Sizing Calculator (Version 1.0.0) [Web calculator]. Retrieved from https://craftquantities.com/calculators/materials-quantities/trapeze-hanger-rod-sizing-calculator/",
      "harvard": "Craft Quantities (2026) Cable Tray Trapeze Hanger Rod Sizing Calculator (Version 1.0.0). Available at: https://craftquantities.com/calculators/materials-quantities/trapeze-hanger-rod-sizing-calculator/",
      "bibtex": "@misc{craftquantities-calculators-materials-quantities-trapeze-hanger-rod-sizing-calculator,\n  author       = {{Craft Quantities}},\n  title        = {Cable Tray Trapeze Hanger Rod Sizing Calculator},\n  version      = {1.0.0},\n  year         = {2026},\n  howpublished = {\\url{https://craftquantities.com/calculators/materials-quantities/trapeze-hanger-rod-sizing-calculator/}},\n}"
    }
  },
  "inputs": [
    {
      "id": "loadPerLength",
      "label": "Loaded Tray Weight per Unit Length",
      "type": "number",
      "dimension": "lineardensity",
      "defaultValue": 60,
      "min": 1,
      "max": 600,
      "step": 1,
      "help": "The weight the trapeze carries for each unit of run — cables, tray and anything hung off the rails."
    },
    {
      "id": "supportSpacing",
      "label": "Spacing Between Trapezes",
      "type": "number",
      "dimension": "length",
      "defaultValue": 3,
      "min": 0.5,
      "max": 12,
      "step": 0.1,
      "help": "The distance between this trapeze and the next one along the run."
    },
    {
      "id": "rodCount",
      "label": "Rods per Trapeze",
      "type": "number",
      "defaultValue": 2,
      "min": 1,
      "max": 6,
      "step": 1,
      "help": "How many hanger rods share the load at this trapeze."
    },
    {
      "id": "allowableStress",
      "label": "Allowable Tensile Stress for the Rod",
      "type": "number",
      "dimension": "pressure",
      "defaultValue": 150000000,
      "min": 40000000,
      "max": 400000000,
      "step": 5000000,
      "help": "The tensile stress the rod is permitted to work at under the design method you are using."
    },
    {
      "id": "threadAreaRatio",
      "label": "Thread Stress Area as a Fraction of Plain-Shank Area",
      "type": "number",
      "defaultValue": 0.75,
      "min": 0.55,
      "max": 1,
      "step": 0.01,
      "help": "How much of the rod's plain cross-section survives once the thread is cut into it."
    },
    {
      "id": "rodDiameter",
      "label": "Diameter of the Rod You Intend to Use",
      "type": "number",
      "dimension": "length",
      "defaultValue": 0.012,
      "min": 0.005,
      "max": 0.05,
      "step": 0.001,
      "help": "The outside diameter of the rod you are proposing, so its utilisation can be reported."
    }
  ],
  "sources": [
    {
      "label": "Direct tension check: rod tension = (load per unit length × support spacing) ÷ rods per trapeze; required tensile stress area = tension ÷ allowable tensile stress; diameter follows from area for a round section"
    },
    {
      "label": "RULE OF THUMB, stated as one: the default thread stress-area ratio of 0.75 is the approximate relationship between a threaded rod's tensile stress area and its plain-shank area across the common sizes. It is an approximation for a first pass — the exact stress area for the size you are using is published in its own thread standard and should be entered here once you have chosen a size."
    },
    {
      "label": "RULE OF THUMB, stated as one: the default allowable tensile stress of 150 MPa is a round working figure for ordinary carbon-steel hanger rod, not a code value. Take the governing allowable stress from the rod's material standard and the design method in force before relying on the answer."
    },
    {
      "label": "ASCE/SEI 7, Minimum Design Loads and Associated Criteria for Buildings and Other Structures — where the building code adopts seismic requirements, unbraced hanger rod needs bracing designed under that standard, which this tension check does not cover"
    }
  ],
  "testCases": [
    {
      "name": "60 kg/m of loaded tray, 3 m spacing, two rods at 150 MPa allowable",
      "inputs": {
        "loadPerLength": 60,
        "supportSpacing": 3,
        "rodCount": 2,
        "allowableStress": 150000000,
        "threadAreaRatio": 0.75,
        "rodDiameter": 0.012
      },
      "expected": 3.1605,
      "toleranceDecimalPlaces": 3,
      "unit": "mm",
      "confidence": "medium",
      "steps": [
        {
          "label": "Load carried by the whole trapeze",
          "value": 1765.1970000000001,
          "unit": "N"
        },
        {
          "label": "Tension carried by each rod",
          "value": 882.5985000000001,
          "unit": "N"
        },
        {
          "label": "Required tensile stress area",
          "value": 5.88399,
          "unit": "mm²"
        },
        {
          "label": "Stress area of the rod you entered",
          "value": 84.82300164692441,
          "unit": "mm²"
        },
        {
          "label": "Utilisation of the rod you entered",
          "value": 6.936785878542826,
          "unit": "%"
        }
      ],
      "basis": "ambiguous"
    },
    {
      "name": "100 kg/m at 2.4 m spacing shared by four rods at 200 MPa allowable",
      "inputs": {
        "loadPerLength": 100,
        "supportSpacing": 2.4,
        "rodCount": 4,
        "allowableStress": 200000000,
        "threadAreaRatio": 0.75,
        "rodDiameter": 0.016
      },
      "expected": 2.2348,
      "toleranceDecimalPlaces": 3,
      "unit": "mm",
      "confidence": "medium",
      "steps": [
        {
          "label": "Load carried by the whole trapeze",
          "value": 2353.596,
          "unit": "N"
        },
        {
          "label": "Tension carried by each rod",
          "value": 588.399,
          "unit": "N"
        },
        {
          "label": "Required tensile stress area",
          "value": 2.941995,
          "unit": "mm²"
        },
        {
          "label": "Stress area of the rod you entered",
          "value": 150.79644737231007,
          "unit": "mm²"
        },
        {
          "label": "Utilisation of the rod you entered",
          "value": 1.9509710283401693,
          "unit": "%"
        }
      ],
      "basis": "ambiguous"
    }
  ]
}