  "version": "v1",
  "source": "https://craftquantities.com",
  "licence": "CC BY 4.0",
  "licenceUrl": "https://creativecommons.org/licenses/by/4.0/",
  "attribution": "Craft Quantities — craftquantities.com",
  "documentation": "https://craftquantities.com/api/",
  "versioning": "Fields are added, never removed or repurposed, within a version. A breaking change becomes /api/v2/ and v1 keeps being built.",
  "slug": "short-circuit-current-calculator",
  "category": "materials-quantities",
  "title": "Transformer-Limited Short-Circuit Current Calculator",
  "description": "Estimate the maximum available short-circuit current at a transformer's secondary, limited by transformer impedance alone.",
  "url": "https://craftquantities.com/calculators/materials-quantities/short-circuit-current-calculator/",
  "json": "https://craftquantities.com/api/v1/calculators/short-circuit-current-calculator.json",
  "inputCount": 3,
  "testCaseCount": 2,
  "sourceCount": 1,
  "lastVerified": "2026-09-05",
  "citation": {
    "author": "Craft Quantities",
    "title": "Transformer-Limited Short-Circuit Current Calculator",
    "version": "1.0.1",
    "sourcesChecked": "2026-09-05",
    "url": "https://craftquantities.com/calculators/materials-quantities/short-circuit-current-calculator/",
    "accessDate": null,
    "accessDateNote": "Add the date you retrieved this. It is deliberately absent: a static file cannot know when you read it, and the build date would be wrong.",
    "permanentVersionedUrl": null,
    "permanentVersionedUrlNote": "Not offered. This site keeps no archive of previous builds, so any such URL would resolve to the current page or to nothing. The version and sourcesChecked fields identify the calculation instead.",
    "formats": {
      "plain": "Craft Quantities. Transformer-Limited Short-Circuit Current Calculator. Version 1.0.1. Sources checked 2026-09-05. https://craftquantities.com/calculators/materials-quantities/short-circuit-current-calculator/",
      "apa": "Craft Quantities. (2026). Transformer-Limited Short-Circuit Current Calculator (Version 1.0.1) [Web calculator]. Retrieved from https://craftquantities.com/calculators/materials-quantities/short-circuit-current-calculator/",
      "harvard": "Craft Quantities (2026) Transformer-Limited Short-Circuit Current Calculator (Version 1.0.1). Available at: https://craftquantities.com/calculators/materials-quantities/short-circuit-current-calculator/",
      "bibtex": "@misc{craftquantities-calculators-materials-quantities-short-circuit-current-calculator,\n  author       = {{Craft Quantities}},\n  title        = {Transformer-Limited Short-Circuit Current Calculator},\n  version      = {1.0.1},\n  year         = {2026},\n  howpublished = {\\url{https://craftquantities.com/calculators/materials-quantities/short-circuit-current-calculator/}},\n}"
    }
  },
  "inputs": [
    {
      "id": "transformerKVA",
      "label": "Transformer Rating (kVA)",
      "type": "number",
      "defaultValue": 500,
      "min": 15,
      "max": 2500,
      "step": 5,
      "help": "The transformer's nameplate kVA rating."
    },
    {
      "id": "secondaryVoltage",
      "label": "Secondary Voltage (V, Line-to-Line)",
      "type": "number",
      "defaultValue": 480,
      "min": 120,
      "max": 600,
      "step": 1,
      "help": "The three-phase line-to-line secondary voltage."
    },
    {
      "id": "impedancePercent",
      "label": "Transformer Impedance (%, from Nameplate)",
      "type": "number",
      "defaultValue": 5.5,
      "min": 2,
      "max": 8,
      "step": 0.05,
      "help": "The transformer's nameplate percent impedance."
    }
  ],
  "sources": [
    {
      "label": "Simplified transformer-only fault current estimate: full-load amps = (transformer kVA × 1000) ÷ (voltage × √3) for three-phase; available fault current = full-load amps ÷ (transformer impedance percentage ÷ 100) — this is the classical 'infinite source' approximation used for preliminary screening. It ignores upstream utility source impedance and downstream conductor impedance, which reduce the current available at a given point — and it also ignores motor contribution and the tolerance on nameplate impedance, which raise it"
    }
  ],
  "testCases": [
    {
      "name": "500 kVA, 480V, 5.5% Z",
      "inputs": {
        "transformerKVA": 500,
        "secondaryVoltage": 480,
        "impedancePercent": 5.5
      },
      "expected": 10934.66,
      "toleranceDecimalPlaces": -1,
      "unit": "A",
      "confidence": "low",
      "steps": [
        {
          "label": "Transformer full-load amps",
          "value": 601.4065304058603,
          "unit": "A"
        }
      ],
      "basis": "sole-source",
      "sourceIndex": 0
    },
    {
      "name": "750 kVA, 480V, 5.75% Z",
      "inputs": {
        "transformerKVA": 750,
        "secondaryVoltage": 480,
        "impedancePercent": 5.75
      },
      "expected": 15688.87,
      "toleranceDecimalPlaces": -1,
      "unit": "A",
      "confidence": "low",
      "steps": [
        {
          "label": "Transformer full-load amps",
          "value": 902.1097956087904,
          "unit": "A"
        }
      ],
      "basis": "sole-source",
      "sourceIndex": 0
    }
  ]
}