  "version": "v1",
  "source": "https://craftquantities.com",
  "licence": "CC BY 4.0",
  "licenceUrl": "https://creativecommons.org/licenses/by/4.0/",
  "attribution": "Craft Quantities — craftquantities.com",
  "documentation": "https://craftquantities.com/api/",
  "versioning": "Fields are added, never removed or repurposed, within a version. A breaking change becomes /api/v2/ and v1 keeps being built.",
  "slug": "refrigerant-line-charge-adjustment-calculator",
  "category": "materials-quantities",
  "title": "Refrigerant Line Length Charge Adjustment Calculator",
  "description": "How much refrigerant to weigh in beyond the factory charge when the liquid line runs past the length the unit ships charged for, at the maker's rate.",
  "url": "https://craftquantities.com/calculators/materials-quantities/refrigerant-line-charge-adjustment-calculator/",
  "json": "https://craftquantities.com/api/v1/calculators/refrigerant-line-charge-adjustment-calculator.json",
  "inputCount": 4,
  "testCaseCount": 3,
  "sourceCount": 3,
  "lastVerified": "2026-08-30",
  "citation": {
    "author": "Craft Quantities",
    "title": "Refrigerant Line Length Charge Adjustment Calculator",
    "version": "1.0.0",
    "sourcesChecked": "2026-08-30",
    "url": "https://craftquantities.com/calculators/materials-quantities/refrigerant-line-charge-adjustment-calculator/",
    "accessDate": null,
    "accessDateNote": "Add the date you retrieved this. It is deliberately absent: a static file cannot know when you read it, and the build date would be wrong.",
    "permanentVersionedUrl": null,
    "permanentVersionedUrlNote": "Not offered. This site keeps no archive of previous builds, so any such URL would resolve to the current page or to nothing. The version and sourcesChecked fields identify the calculation instead.",
    "formats": {
      "plain": "Craft Quantities. Refrigerant Line Length Charge Adjustment Calculator. Version 1.0.0. Sources checked 2026-08-30. https://craftquantities.com/calculators/materials-quantities/refrigerant-line-charge-adjustment-calculator/",
      "apa": "Craft Quantities. (2026). Refrigerant Line Length Charge Adjustment Calculator (Version 1.0.0) [Web calculator]. Retrieved from https://craftquantities.com/calculators/materials-quantities/refrigerant-line-charge-adjustment-calculator/",
      "harvard": "Craft Quantities (2026) Refrigerant Line Length Charge Adjustment Calculator (Version 1.0.0). Available at: https://craftquantities.com/calculators/materials-quantities/refrigerant-line-charge-adjustment-calculator/",
      "bibtex": "@misc{craftquantities-calculators-materials-quantities-refrigerant-line-charge-adjustment-calculator,\n  author       = {{Craft Quantities}},\n  title        = {Refrigerant Line Length Charge Adjustment Calculator},\n  version      = {1.0.0},\n  year         = {2026},\n  howpublished = {\\url{https://craftquantities.com/calculators/materials-quantities/refrigerant-line-charge-adjustment-calculator/}},\n}"
    }
  },
  "inputs": [
    {
      "id": "liquidLineLength",
      "label": "Measured Liquid Line Length",
      "type": "number",
      "dimension": "length",
      "defaultValue": 20,
      "min": 1,
      "max": 90,
      "step": 0.5,
      "help": "The liquid line as installed, measured along the route rather than point to point."
    },
    {
      "id": "standardLineLength",
      "label": "Standard Line Length the Model Ships Charged For",
      "type": "number",
      "dimension": "length",
      "defaultValue": 7.62,
      "min": 0,
      "max": 30,
      "step": 0.1,
      "help": "The line length already covered by the factory charge, from the model's own document."
    },
    {
      "id": "chargeRate",
      "label": "Published Charge Rate per Unit of Liquid Line",
      "type": "number",
      "dimension": "lineardensity",
      "defaultValue": 0.0558,
      "min": 0.005,
      "max": 0.5,
      "step": 0.001,
      "help": "The refrigerant mass the manufacturer adds for each unit of liquid line beyond the standard length."
    },
    {
      "id": "liquidLineInnerDiameter",
      "label": "Liquid Line Inside Diameter",
      "type": "number",
      "dimension": "length",
      "defaultValue": 0.008,
      "min": 0.003,
      "max": 0.03,
      "step": 0.0005,
      "help": "The bore of the liquid line, used to report the volume of the extra run as a cross-check."
    }
  ],
  "sources": [
    {
      "label": "Manufacturer installation instructions: additional charge = (measured liquid line length − the standard line length the unit ships charged for) × the published charge rate per unit of liquid line. Both the standard length and the rate are model-specific and are entered here from that document"
    },
    {
      "label": "AHRI 210/240, Performance Rating of Unitary Air-Conditioning and Air-Source Heat Pump Equipment — split systems are rated with a standard length of interconnecting tubing, which is why a longer field run needs charge added rather than being an equivalent installation"
    },
    {
      "label": "The default charge rate and standard length are PLACEHOLDERS of the right order, not published values. Replace both with the figures printed for the model being installed"
    }
  ],
  "testCases": [
    {
      "name": "20 m run against a 7.62 m standard at 0.0558 kg/m",
      "inputs": {
        "liquidLineLength": 20,
        "standardLineLength": 7.62,
        "chargeRate": 0.0558,
        "liquidLineInnerDiameter": 0.008
      },
      "expected": 0.690804,
      "toleranceDecimalPlaces": 4,
      "unit": "kg",
      "confidence": "high",
      "steps": [
        {
          "label": "Line length beyond the factory-charge standard",
          "value": 12.379999999999999,
          "unit": "m"
        },
        {
          "label": "Internal volume of the run beyond standard",
          "value": 622.2866728230663,
          "unit": "cm³"
        },
        {
          "label": "Charge rate applied",
          "value": 0.0558,
          "unit": "kg/m"
        }
      ],
      "basis": "ambiguous"
    },
    {
      "name": "30 m run against the same standard",
      "inputs": {
        "liquidLineLength": 30,
        "standardLineLength": 7.62,
        "chargeRate": 0.0558,
        "liquidLineInnerDiameter": 0.008
      },
      "expected": 1.248804,
      "toleranceDecimalPlaces": 4,
      "unit": "kg",
      "confidence": "high",
      "steps": [
        {
          "label": "Line length beyond the factory-charge standard",
          "value": 22.38,
          "unit": "m"
        },
        {
          "label": "Internal volume of the run beyond standard",
          "value": 1124.941497397433,
          "unit": "cm³"
        },
        {
          "label": "Charge rate applied",
          "value": 0.0558,
          "unit": "kg/m"
        }
      ],
      "basis": "ambiguous"
    },
    {
      "name": "Run shorter than standard — charge comes out, not in",
      "inputs": {
        "liquidLineLength": 5,
        "standardLineLength": 7.62,
        "chargeRate": 0.0558,
        "liquidLineInnerDiameter": 0.008
      },
      "expected": -0.146196,
      "toleranceDecimalPlaces": 4,
      "unit": "kg",
      "confidence": "medium",
      "steps": [
        {
          "label": "Line length beyond the factory-charge standard",
          "value": -2.62,
          "unit": "m"
        },
        {
          "label": "Internal volume of the run beyond standard",
          "value": 0,
          "unit": "cm³"
        },
        {
          "label": "Charge rate applied",
          "value": 0.0558,
          "unit": "kg/m"
        }
      ],
      "basis": "ambiguous"
    }
  ]
}