  "version": "v1",
  "source": "https://craftquantities.com",
  "licence": "CC BY 4.0",
  "licenceUrl": "https://creativecommons.org/licenses/by/4.0/",
  "attribution": "Craft Quantities — craftquantities.com",
  "documentation": "https://craftquantities.com/api/",
  "versioning": "Fields are added, never removed or repurposed, within a version. A breaking change becomes /api/v2/ and v1 keeps being built.",
  "slug": "motor-full-load-amps-calculator",
  "category": "materials-quantities",
  "title": "Three-Phase Motor Full-Load Amperage Calculator",
  "description": "Estimate a three-phase motor's full-load current draw from its horsepower, voltage, and efficiency.",
  "url": "https://craftquantities.com/calculators/materials-quantities/motor-full-load-amps-calculator/",
  "json": "https://craftquantities.com/api/v1/calculators/motor-full-load-amps-calculator.json",
  "inputCount": 4,
  "testCaseCount": 2,
  "sourceCount": 1,
  "lastVerified": "2026-09-06",
  "citation": {
    "author": "Craft Quantities",
    "title": "Three-Phase Motor Full-Load Amperage Calculator",
    "version": "1.0.1",
    "sourcesChecked": "2026-09-06",
    "url": "https://craftquantities.com/calculators/materials-quantities/motor-full-load-amps-calculator/",
    "accessDate": null,
    "accessDateNote": "Add the date you retrieved this. It is deliberately absent: a static file cannot know when you read it, and the build date would be wrong.",
    "permanentVersionedUrl": null,
    "permanentVersionedUrlNote": "Not offered. This site keeps no archive of previous builds, so any such URL would resolve to the current page or to nothing. The version and sourcesChecked fields identify the calculation instead.",
    "formats": {
      "plain": "Craft Quantities. Three-Phase Motor Full-Load Amperage Calculator. Version 1.0.1. Sources checked 2026-09-06. https://craftquantities.com/calculators/materials-quantities/motor-full-load-amps-calculator/",
      "apa": "Craft Quantities. (2026). Three-Phase Motor Full-Load Amperage Calculator (Version 1.0.1) [Web calculator]. Retrieved from https://craftquantities.com/calculators/materials-quantities/motor-full-load-amps-calculator/",
      "harvard": "Craft Quantities (2026) Three-Phase Motor Full-Load Amperage Calculator (Version 1.0.1). Available at: https://craftquantities.com/calculators/materials-quantities/motor-full-load-amps-calculator/",
      "bibtex": "@misc{craftquantities-calculators-materials-quantities-motor-full-load-amps-calculator,\n  author       = {{Craft Quantities}},\n  title        = {Three-Phase Motor Full-Load Amperage Calculator},\n  version      = {1.0.1},\n  year         = {2026},\n  howpublished = {\\url{https://craftquantities.com/calculators/materials-quantities/motor-full-load-amps-calculator/}},\n}"
    }
  },
  "inputs": [
    {
      "id": "horsepower",
      "label": "Motor Horsepower (HP)",
      "type": "number",
      "defaultValue": 10,
      "min": 0.5,
      "max": 500,
      "step": 0.5,
      "help": "The motor's rated output horsepower."
    },
    {
      "id": "voltage",
      "label": "Voltage (V, Line-to-Line)",
      "type": "number",
      "defaultValue": 480,
      "min": 120,
      "max": 690,
      "step": 1,
      "help": "The three-phase line-to-line supply voltage."
    },
    {
      "id": "efficiency",
      "label": "Motor Efficiency (%)",
      "type": "number",
      "defaultValue": 90,
      "min": 50,
      "max": 98,
      "step": 0.5,
      "help": "The motor's rated efficiency at full load."
    },
    {
      "id": "powerFactor",
      "label": "Power Factor",
      "type": "number",
      "defaultValue": 0.85,
      "min": 0.5,
      "max": 1,
      "step": 0.01,
      "help": "The motor's rated power factor at full load."
    }
  ],
  "sources": [
    {
      "label": "Standard three-phase motor FLA formula: FLA = (HP × 746) ÷ (√3 × voltage × efficiency × power factor), derived from the electrical power relationship P = √3 × V × I × PF applied to motor output power converted to input electrical power via efficiency"
    }
  ],
  "testCases": [
    {
      "name": "10 HP, 480V, 90% eff, 0.85 PF",
      "inputs": {
        "horsepower": 10,
        "voltage": 480,
        "efficiency": 90,
        "powerFactor": 0.85
      },
      "expected": 11.73,
      "toleranceDecimalPlaces": 1,
      "unit": "A",
      "confidence": "medium",
      "steps": [],
      "basis": "sole-source",
      "sourceIndex": 0
    },
    {
      "name": "25 HP, 480V, 92% eff, 0.87 PF",
      "inputs": {
        "horsepower": 25,
        "voltage": 480,
        "efficiency": 92,
        "powerFactor": 0.87
      },
      "expected": 28.03,
      "toleranceDecimalPlaces": 1,
      "unit": "A",
      "confidence": "medium",
      "steps": [],
      "basis": "sole-source",
      "sourceIndex": 0
    }
  ]
}