  "slug": "mini-split-line-length-derating-calculator",
  "category": "materials-quantities",
  "title": "Mini-Split/VRF Line Set Length Derating Calculator",
  "description": "A mini-split or VRF system's derated capacity for line set length beyond the base allowance and for vertical rise, at the rates in the maker's manual.",
  "url": "https://craftquantities.com/calculators/materials-quantities/mini-split-line-length-derating-calculator/",
  "json": "https://craftquantities.com/api/v1/calculators/mini-split-line-length-derating-calculator.json",
  "inputCount": 5,
  "testCaseCount": 2,
  "sourceCount": 1,
  "lastVerified": "2026-09-06",
  "citation": {
    "author": "Craft Quantities",
    "title": "Mini-Split/VRF Line Set Length Derating Calculator",
    "version": "1.1.1",
    "sourcesChecked": "2026-09-06",
    "url": "https://craftquantities.com/calculators/materials-quantities/mini-split-line-length-derating-calculator/",
    "accessDate": null,
    "accessDateNote": "Add the date you retrieved this. It is deliberately absent: a static file cannot know when you read it, and the build date would be wrong.",
    "permanentVersionedUrl": null,
    "permanentVersionedUrlNote": "Not offered. This site keeps no archive of previous builds, so any such URL would resolve to the current page or to nothing. The version and sourcesChecked fields identify the calculation instead.",
    "formats": {
      "plain": "Craft Quantities. Mini-Split/VRF Line Set Length Derating Calculator. Version 1.1.1. Sources checked 2026-09-06. https://craftquantities.com/calculators/materials-quantities/mini-split-line-length-derating-calculator/",
      "apa": "Craft Quantities. (2026). Mini-Split/VRF Line Set Length Derating Calculator (Version 1.1.1) [Web calculator]. Retrieved from https://craftquantities.com/calculators/materials-quantities/mini-split-line-length-derating-calculator/",
      "harvard": "Craft Quantities (2026) Mini-Split/VRF Line Set Length Derating Calculator (Version 1.1.1). Available at: https://craftquantities.com/calculators/materials-quantities/mini-split-line-length-derating-calculator/",
      "bibtex": "@misc{craftquantities-calculators-materials-quantities-mini-split-line-length-derating-calculator,\n  author       = {{Craft Quantities}},\n  title        = {Mini-Split/VRF Line Set Length Derating Calculator},\n  version      = {1.1.1},\n  year         = {2026},\n  howpublished = {\\url{https://craftquantities.com/calculators/materials-quantities/mini-split-line-length-derating-calculator/}},\n}"
    }
  },
  "inputs": [
    {
      "id": "ratedCapacity",
      "label": "Manufacturer's Rated Capacity",
      "type": "number",
      "dimension": "thermal",
      "defaultValue": 7033.705684133281,
      "min": 1758.4264210333201,
      "max": 17584.2642103332,
      "step": 293.07107017222,
      "help": "The system's nameplate cooling/heating capacity at the manufacturer's base (included) line length."
    },
    {
      "id": "extraHorizontalLength",
      "label": "Additional Horizontal Line Length Beyond Base Allowance",
      "type": "number",
      "dimension": "length",
      "defaultValue": 6,
      "min": 0,
      "max": 30,
      "step": 0.5,
      "help": "The horizontal refrigerant line run beyond the manufacturer's base length allowance."
    },
    {
      "id": "horizontalDerateRate",
      "label": "Manufacturer's Horizontal Derate Rate (% per ft)",
      "type": "number",
      "defaultValue": 0.5,
      "min": 0,
      "max": 3,
      "step": 0.05,
      "help": "The percentage of rated capacity lost per foot of horizontal line beyond the base allowance."
    },
    {
      "id": "verticalRise",
      "label": "Vertical Rise",
      "type": "number",
      "dimension": "length",
      "defaultValue": 3,
      "min": 0,
      "max": 15,
      "step": 0.5,
      "help": "The total vertical elevation change between indoor and outdoor units."
    },
    {
      "id": "verticalDerateRate",
      "label": "Manufacturer's Vertical Derate Rate (% per ft)",
      "type": "number",
      "defaultValue": 1,
      "min": 0,
      "max": 5,
      "step": 0.1,
      "help": "The percentage of rated capacity lost per foot of vertical rise."
    }
  ],
  "sources": [
    {
      "label": "Manufacturers of mini-split and VRF systems publish a base line length included at 100% rated capacity, then apply a percentage capacity derate per foot of additional horizontal run and per foot of vertical rise beyond that allowance — this calculator applies user-supplied derate rates (from the specific manufacturer's engineering/installation manual) rather than a universal constant, since these rates vary significantly by manufacturer and model."
    }
  ],
  "testCases": [
    {
      "name": "24,000 BTU/hr (7.03 kW), 20ft extra horizontal, 10ft rise",
      "inputs": {
        "ratedCapacity": 7033.705684133281,
        "extraHorizontalLength": 6.096,
        "horizontalDerateRate": 0.5,
        "verticalRise": 3.048,
        "verticalDerateRate": 1
      },
      "expected": 19200,
      "toleranceDecimalPlaces": -1,
      "unit": "BTU/hr",
      "confidence": "medium",
      "steps": [
        {
          "label": "Total capacity derate",
          "value": 19.999999999999996,
          "unit": "%"
        }
      ],
      "basis": "sole-source",
      "sourceIndex": 0
    },
    {
      "name": "36,000 BTU/hr (10.55 kW), 30ft extra horizontal, 15ft rise",
      "inputs": {
        "ratedCapacity": 10550.55852619992,
        "extraHorizontalLength": 9.144,
        "horizontalDerateRate": 0.4,
        "verticalRise": 4.572,
        "verticalDerateRate": 0.8
      },
      "expected": 27360,
      "toleranceDecimalPlaces": -1,
      "unit": "BTU/hr",
      "confidence": "medium",
      "steps": [
        {
          "label": "Total capacity derate",
          "value": 24,
          "unit": "%"
        }
      ],
      "basis": "sole-source",
      "sourceIndex": 0
    }
  ]
}