  "version": "v1",
  "source": "https://craftquantities.com",
  "licence": "CC BY 4.0",
  "licenceUrl": "https://creativecommons.org/licenses/by/4.0/",
  "attribution": "Craft Quantities — craftquantities.com",
  "documentation": "https://craftquantities.com/api/",
  "versioning": "Fields are added, never removed or repurposed, within a version. A breaking change becomes /api/v2/ and v1 keeps being built.",
  "slug": "membrane-penetration-box-area-calculator",
  "category": "materials-quantities",
  "title": "Firestop Membrane Penetration Box Area Calculator",
  "description": "Check the electrical boxes in a fire-rated wall against the opening-area cap for that wall area and the separation between boxes on opposite faces.",
  "url": "https://craftquantities.com/calculators/materials-quantities/membrane-penetration-box-area-calculator/",
  "json": "https://craftquantities.com/api/v1/calculators/membrane-penetration-box-area-calculator.json",
  "inputCount": 6,
  "testCaseCount": 3,
  "sourceCount": 3,
  "lastVerified": "2026-09-02",
  "translations": {
    "es-US": "https://craftquantities.com/es/calculators/materials-quantities/membrane-penetration-box-area-calculator/"
  },
  "citation": {
    "author": "Craft Quantities",
    "title": "Firestop Membrane Penetration Box Area Calculator",
    "version": "1.0.1",
    "sourcesChecked": "2026-09-02",
    "url": "https://craftquantities.com/calculators/materials-quantities/membrane-penetration-box-area-calculator/",
    "accessDate": null,
    "accessDateNote": "Add the date you retrieved this. It is deliberately absent: a static file cannot know when you read it, and the build date would be wrong.",
    "permanentVersionedUrl": null,
    "permanentVersionedUrlNote": "Not offered. This site keeps no archive of previous builds, so any such URL would resolve to the current page or to nothing. The version and sourcesChecked fields identify the calculation instead.",
    "formats": {
      "plain": "Craft Quantities. Firestop Membrane Penetration Box Area Calculator. Version 1.0.1. Sources checked 2026-09-02. https://craftquantities.com/calculators/materials-quantities/membrane-penetration-box-area-calculator/",
      "apa": "Craft Quantities. (2026). Firestop Membrane Penetration Box Area Calculator (Version 1.0.1) [Web calculator]. Retrieved from https://craftquantities.com/calculators/materials-quantities/membrane-penetration-box-area-calculator/",
      "harvard": "Craft Quantities (2026) Firestop Membrane Penetration Box Area Calculator (Version 1.0.1). Available at: https://craftquantities.com/calculators/materials-quantities/membrane-penetration-box-area-calculator/",
      "bibtex": "@misc{craftquantities-calculators-materials-quantities-membrane-penetration-box-area-calculator,\n  author       = {{Craft Quantities}},\n  title        = {Firestop Membrane Penetration Box Area Calculator},\n  version      = {1.0.1},\n  year         = {2026},\n  howpublished = {\\url{https://craftquantities.com/calculators/materials-quantities/membrane-penetration-box-area-calculator/}},\n}"
    }
  },
  "inputs": [
    {
      "id": "wallRating",
      "label": "Fire-Resistance Rating of the Wall",
      "type": "select",
      "defaultValue": "2",
      "options": [
        {
          "value": "1",
          "label": "1 hour"
        },
        {
          "value": "2",
          "label": "2 hours"
        },
        {
          "value": "3",
          "label": "3 hours"
        },
        {
          "value": "4",
          "label": "4 hours"
        }
      ],
      "help": "The rating of the assembly the boxes are being cut into. The box allowance stops at 2 hours."
    },
    {
      "id": "boxFaceArea",
      "label": "Face Area of a Single Box Opening",
      "type": "number",
      "dimension": "area",
      "defaultValue": 0.01032256,
      "min": 0.001,
      "max": 0.05,
      "step": 0.0005,
      "help": "The opening one box cuts through the board, not the volume of the box."
    },
    {
      "id": "boxCount",
      "label": "Number of Boxes in That Wall Area",
      "type": "number",
      "defaultValue": 6,
      "min": 1,
      "max": 200,
      "step": 1,
      "help": "How many boxes are set into the area of wall you entered below."
    },
    {
      "id": "wallArea",
      "label": "Wall Area Under Consideration",
      "type": "number",
      "dimension": "area",
      "defaultValue": 9.290304,
      "min": 1,
      "max": 500,
      "step": 0.5,
      "help": "The area of rated wall the boxes above are distributed across."
    },
    {
      "id": "oppositeFaceSeparation",
      "label": "Horizontal Separation Between Boxes on Opposite Faces",
      "type": "number",
      "dimension": "length",
      "defaultValue": 0.6096,
      "min": 0,
      "max": 3,
      "step": 0.01,
      "help": "The closest horizontal offset between a box on one side and a box on the other."
    },
    {
      "id": "listedPads",
      "label": "Listed Putty Pads or Equivalent Listed Protection",
      "type": "select",
      "defaultValue": "no",
      "options": [
        {
          "value": "no",
          "label": "No listed protection — the separation distance governs"
        },
        {
          "value": "yes",
          "label": "Both boxes protected by a listed putty pad or other listed method"
        }
      ],
      "help": "Whether a listed protection method is used in place of the separation distance."
    }
  ],
  "sources": [
    {
      "label": "International Building Code, fire and smoke protection features — membrane penetrations of MAXIMUM 2-HOUR fire-resistance-rated walls and partitions by steel electrical boxes: individual face area not exceeding 16 in² (0.0103 m²), with the aggregate area of such openings not exceeding 100 in² (0.0645 m²) in any 100 sq ft (9.29 m²) of wall area. The allowance does not extend to walls rated above 2 hours"
    },
    {
      "label": "Same provision, boxes on opposite sides of a rated wall: separated by a horizontal distance of not less than 24 in (610 mm), unless separated by the insulation the code describes, by solid fireblocking, or protected by a listed putty pad or other listed material. Confirm against the edition your jurisdiction has adopted and any local amendment"
    },
    {
      "label": "The wall's fire-resistance rating itself comes from a tested assembly under ASTM E119 or UL 263. This page checks the openings cut through the membrane against the code's limits; it does not establish or verify the rating"
    }
  ],
  "testCases": [
    {
      "name": "Twelve 16 in² boxes in 100 sq ft of wall",
      "inputs": {
        "boxFaceArea": 0.01032256,
        "boxCount": 12,
        "wallArea": 9.290304,
        "oppositeFaceSeparation": 0.6096,
        "listedPads": "no"
      },
      "expected": 192,
      "toleranceDecimalPlaces": 1,
      "unit": "% of the cap",
      "confidence": "low",
      "steps": [
        {
          "label": "Aggregate box opening area",
          "value": 0.12387071999999999,
          "unit": "m²"
        },
        {
          "label": "Cap for the wall area entered",
          "value": 0.064516,
          "unit": "m²"
        },
        {
          "label": "Boxes this wall area can carry at that size",
          "value": 6,
          "unit": "boxes"
        },
        {
          "label": "Largest single box allowed without a listed system",
          "value": 0.01032256,
          "unit": "m²"
        },
        {
          "label": "Separation required between opposing boxes",
          "value": 609.5999999999999,
          "unit": "mm"
        },
        {
          "label": "Separation entered",
          "value": 609.6,
          "unit": "mm"
        }
      ],
      "basis": "ambiguous"
    },
    {
      "name": "a 3-hour wall gets no prescriptive allowance, however small the boxes",
      "inputs": {
        "wallRating": "3",
        "boxFaceArea": 0.0064516,
        "boxCount": 2,
        "wallArea": 9.290304,
        "oppositeFaceSeparation": 0.6096,
        "listedPads": "no"
      },
      "expected": 20,
      "toleranceDecimalPlaces": 1,
      "unit": "% of the cap",
      "confidence": "low",
      "steps": [
        {
          "label": "Aggregate box opening area",
          "value": 0.0129032,
          "unit": "m²"
        },
        {
          "label": "Cap for the wall area entered",
          "value": 0.064516,
          "unit": "m²"
        },
        {
          "label": "Boxes this wall area can carry at that size",
          "value": 10,
          "unit": "boxes"
        },
        {
          "label": "Largest single box allowed without a listed system",
          "value": 0.01032256,
          "unit": "m²"
        },
        {
          "label": "Separation required between opposing boxes",
          "value": 609.5999999999999,
          "unit": "mm"
        },
        {
          "label": "Separation entered",
          "value": 609.6,
          "unit": "mm"
        }
      ],
      "basis": "ambiguous"
    },
    {
      "name": "Six 16 in² boxes spread over 200 sq ft of wall",
      "inputs": {
        "boxFaceArea": 0.01032256,
        "boxCount": 6,
        "wallArea": 18.580608,
        "oppositeFaceSeparation": 0.6096,
        "listedPads": "no"
      },
      "expected": 48,
      "toleranceDecimalPlaces": 1,
      "unit": "% of the cap",
      "confidence": "medium",
      "steps": [
        {
          "label": "Aggregate box opening area",
          "value": 0.061935359999999995,
          "unit": "m²"
        },
        {
          "label": "Cap for the wall area entered",
          "value": 0.129032,
          "unit": "m²"
        },
        {
          "label": "Boxes this wall area can carry at that size",
          "value": 12,
          "unit": "boxes"
        },
        {
          "label": "Largest single box allowed without a listed system",
          "value": 0.01032256,
          "unit": "m²"
        },
        {
          "label": "Separation required between opposing boxes",
          "value": 609.5999999999999,
          "unit": "mm"
        },
        {
          "label": "Separation entered",
          "value": 609.6,
          "unit": "mm"
        }
      ],
      "basis": "ambiguous"
    }
  ]
}