  "version": "v1",
  "source": "https://craftquantities.com",
  "licence": "CC BY 4.0",
  "licenceUrl": "https://creativecommons.org/licenses/by/4.0/",
  "attribution": "Craft Quantities — craftquantities.com",
  "documentation": "https://craftquantities.com/api/",
  "versioning": "Fields are added, never removed or repurposed, within a version. A breaking change becomes /api/v2/ and v1 keeps being built.",
  "slug": "manual-j-screening-calculator",
  "category": "plumbing-hvac",
  "title": "Heating & Cooling Load Screening Calculator",
  "description": "Estimate whole-house heating and cooling loads from envelope areas and U-values — a screening check against a contractor's figure.",
  "url": "https://craftquantities.com/calculators/plumbing-hvac/manual-j-screening-calculator/",
  "json": "https://craftquantities.com/api/v1/calculators/manual-j-screening-calculator.json",
  "inputCount": 5,
  "testCaseCount": 4,
  "sourceCount": 3,
  "lastVerified": "2026-10-31",
  "translations": {
    "es-US": "https://craftquantities.com/es/calculators/plumbing-hvac/manual-j-screening-calculator/"
  },
  "citation": {
    "author": "Craft Quantities",
    "title": "Heating & Cooling Load Screening Calculator",
    "version": "1.1.0",
    "sourcesChecked": "2026-10-31",
    "url": "https://craftquantities.com/calculators/plumbing-hvac/manual-j-screening-calculator/",
    "accessDate": null,
    "accessDateNote": "Add the date you retrieved this. It is deliberately absent: a static file cannot know when you read it, and the build date would be wrong.",
    "permanentVersionedUrl": null,
    "permanentVersionedUrlNote": "Not offered. This site keeps no archive of previous builds, so any such URL would resolve to the current page or to nothing. The version and sourcesChecked fields identify the calculation instead.",
    "formats": {
      "plain": "Craft Quantities. Heating & Cooling Load Screening Calculator. Version 1.1.0. Sources checked 2026-10-31. https://craftquantities.com/calculators/plumbing-hvac/manual-j-screening-calculator/",
      "apa": "Craft Quantities. (2026). Heating & Cooling Load Screening Calculator (Version 1.1.0) [Web calculator]. Retrieved from https://craftquantities.com/calculators/plumbing-hvac/manual-j-screening-calculator/",
      "harvard": "Craft Quantities (2026) Heating & Cooling Load Screening Calculator (Version 1.1.0). Available at: https://craftquantities.com/calculators/plumbing-hvac/manual-j-screening-calculator/",
      "bibtex": "@misc{craftquantities-calculators-plumbing-hvac-manual-j-screening-calculator,\n  author       = {{Craft Quantities}},\n  title        = {Heating & Cooling Load Screening Calculator},\n  version      = {1.1.0},\n  year         = {2026},\n  howpublished = {\\url{https://craftquantities.com/calculators/plumbing-hvac/manual-j-screening-calculator/}},\n}"
    }
  },
  "inputs": [
    {
      "id": "envelopeArea",
      "label": "Total envelope area",
      "type": "number",
      "dimension": "area",
      "defaultValue": 300,
      "min": 0.01,
      "max": 10000,
      "step": 5,
      "help": "Walls, roof, floor and glazing combined."
    },
    {
      "id": "averageUValue",
      "label": "Average U-value (W/m²K)",
      "type": "number",
      "defaultValue": 0.6,
      "min": 0.08,
      "max": 5,
      "step": 0.05,
      "help": "Area-weighted average through the whole envelope."
    },
    {
      "id": "volume",
      "label": "Internal volume",
      "type": "number",
      "dimension": "volume",
      "defaultValue": 250000,
      "min": 0.1,
      "max": 20000000,
      "step": 5000,
      "help": "Floor area times ceiling height."
    },
    {
      "id": "airChangesPerHour",
      "label": "Air changes per hour",
      "type": "number",
      "defaultValue": 0.7,
      "min": 0.1,
      "max": 10,
      "step": 0.1,
      "help": "Infiltration and ventilation rate."
    },
    {
      "id": "deltaT",
      "label": "Design temperature difference",
      "type": "number",
      "dimension": "tempdelta",
      "defaultValue": 24,
      "min": 5,
      "max": 60,
      "step": 1,
      "help": "Internal design temperature minus external design temperature."
    }
  ],
  "sources": [
    {
      "label": "Steady-state fabric heat loss: Q = Σ(U × A × ΔT), the basis of every load method including ACCA Manual J and CIBSE Guide A"
    },
    {
      "label": "Ventilation heat loss: Q = 0.33 × n × V × ΔT (W), CIBSE Guide A — 0.33 Wh/m³K is the volumetric heat capacity of air"
    },
    {
      "label": "ACCA Manual J (8th ed.) for the full room-by-room procedure this approximates"
    }
  ],
  "testCases": [
    {
      "name": "300 m² at U 0.6, 250 m³ at 0.7 ACH, ΔT 24",
      "inputs": {
        "envelopeArea": 300,
        "averageUValue": 0.6,
        "volume": 250000,
        "airChangesPerHour": 0.7,
        "deltaT": 24
      },
      "expected": 5706,
      "toleranceDecimalPlaces": -1,
      "unit": "W",
      "confidence": "medium",
      "steps": [
        {
          "label": "Fabric loss",
          "value": 4320,
          "unit": "W"
        },
        {
          "label": "Ventilation loss",
          "value": 1385.9999999999998,
          "unit": "W"
        },
        {
          "label": "Kilowatts",
          "value": 5.706,
          "unit": "kW"
        },
        {
          "label": "BTU/h",
          "value": 19469.680158628184,
          "unit": "BTU/h"
        },
        {
          "label": "Ventilation as a share of the total",
          "value": 24.29022082018927,
          "unit": "%"
        }
      ],
      "basis": "ambiguous"
    },
    {
      "name": "Halving the U-value cuts fabric loss in half",
      "inputs": {
        "envelopeArea": 300,
        "averageUValue": 0.3,
        "volume": 250000,
        "airChangesPerHour": 0.7,
        "deltaT": 24
      },
      "expected": 3546,
      "toleranceDecimalPlaces": -1,
      "unit": "W",
      "confidence": "medium",
      "steps": [
        {
          "label": "Fabric loss",
          "value": 2160,
          "unit": "W"
        },
        {
          "label": "Ventilation loss",
          "value": 1385.9999999999998,
          "unit": "W"
        },
        {
          "label": "Kilowatts",
          "value": 3.546,
          "unit": "kW"
        },
        {
          "label": "BTU/h",
          "value": 12099.454231071773,
          "unit": "BTU/h"
        },
        {
          "label": "Ventilation as a share of the total",
          "value": 39.086294416243646,
          "unit": "%"
        }
      ],
      "basis": "ambiguous"
    },
    {
      "name": "A draughty house at 2.5 ACH",
      "inputs": {
        "envelopeArea": 300,
        "averageUValue": 0.6,
        "volume": 250000,
        "airChangesPerHour": 2.5,
        "deltaT": 24
      },
      "expected": 9270,
      "toleranceDecimalPlaces": -1,
      "unit": "W",
      "confidence": "medium",
      "steps": [
        {
          "label": "Fabric loss",
          "value": 4320,
          "unit": "W"
        },
        {
          "label": "Ventilation loss",
          "value": 4950.000000000001,
          "unit": "W"
        },
        {
          "label": "Kilowatts",
          "value": 9.27,
          "unit": "kW"
        },
        {
          "label": "BTU/h",
          "value": 31630.552939096262,
          "unit": "BTU/h"
        },
        {
          "label": "Ventilation as a share of the total",
          "value": 53.39805825242719,
          "unit": "%"
        }
      ],
      "basis": "ambiguous"
    },
    {
      "name": "Zero temperature difference is zero loss",
      "inputs": {
        "envelopeArea": 300,
        "averageUValue": 0.6,
        "volume": 250000,
        "airChangesPerHour": 0.7,
        "deltaT": 0
      },
      "expected": 0,
      "toleranceDecimalPlaces": 8,
      "unit": "W",
      "confidence": "medium",
      "steps": [
        {
          "label": "Fabric loss",
          "value": 0,
          "unit": "W"
        },
        {
          "label": "Ventilation loss",
          "value": 0,
          "unit": "W"
        },
        {
          "label": "Kilowatts",
          "value": 0,
          "unit": "kW"
        },
        {
          "label": "BTU/h",
          "value": 0,
          "unit": "BTU/h"
        },
        {
          "label": "Ventilation as a share of the total",
          "value": 0,
          "unit": "%"
        }
      ],
      "basis": "ambiguous"
    }
  ]
}