  "version": "v1",
  "source": "https://craftquantities.com",
  "licence": "CC BY 4.0",
  "licenceUrl": "https://creativecommons.org/licenses/by/4.0/",
  "attribution": "Craft Quantities — craftquantities.com",
  "documentation": "https://craftquantities.com/api/",
  "versioning": "Fields are added, never removed or repurposed, within a version. A breaking change becomes /api/v2/ and v1 keeps being built.",
  "slug": "kw-to-kva-calculator",
  "category": "electrical",
  "title": "kW to kVA Calculator",
  "description": "Convert real power in kW into the apparent power in kVA a generator, transformer or supply has to carry, at the load's power factor.",
  "url": "https://craftquantities.com/calculators/electrical/kw-to-kva-calculator/",
  "json": "https://craftquantities.com/api/v1/calculators/kw-to-kva-calculator.json",
  "inputCount": 2,
  "testCaseCount": 5,
  "sourceCount": 3,
  "lastVerified": "2026-10-05",
  "citation": {
    "author": "Craft Quantities",
    "title": "kW to kVA Calculator",
    "version": "1.1.0",
    "sourcesChecked": "2026-10-05",
    "url": "https://craftquantities.com/calculators/electrical/kw-to-kva-calculator/",
    "accessDate": null,
    "accessDateNote": "Add the date you retrieved this. It is deliberately absent: a static file cannot know when you read it, and the build date would be wrong.",
    "permanentVersionedUrl": null,
    "permanentVersionedUrlNote": "Not offered. This site keeps no archive of previous builds, so any such URL would resolve to the current page or to nothing. The version and sourcesChecked fields identify the calculation instead.",
    "formats": {
      "plain": "Craft Quantities. kW to kVA Calculator. Version 1.1.0. Sources checked 2026-10-05. https://craftquantities.com/calculators/electrical/kw-to-kva-calculator/",
      "apa": "Craft Quantities. (2026). kW to kVA Calculator (Version 1.1.0) [Web calculator]. Retrieved from https://craftquantities.com/calculators/electrical/kw-to-kva-calculator/",
      "harvard": "Craft Quantities (2026) kW to kVA Calculator (Version 1.1.0). Available at: https://craftquantities.com/calculators/electrical/kw-to-kva-calculator/",
      "bibtex": "@misc{craftquantities-calculators-electrical-kw-to-kva-calculator,\n  author       = {{Craft Quantities}},\n  title        = {kW to kVA Calculator},\n  version      = {1.1.0},\n  year         = {2026},\n  howpublished = {\\url{https://craftquantities.com/calculators/electrical/kw-to-kva-calculator/}},\n}"
    }
  },
  "inputs": [
    {
      "id": "kw",
      "label": "Real power (kW)",
      "type": "number",
      "defaultValue": 80,
      "min": 0,
      "max": 10000,
      "step": 1,
      "help": "The real power demand in kilowatts."
    },
    {
      "id": "powerFactor",
      "label": "Power factor",
      "type": "number",
      "defaultValue": 0.8,
      "min": 0.2,
      "max": 1,
      "step": 0.01,
      "help": "The load's power factor: 1 for resistive heating, lower for motors. It opens on 0.8, the factor three-phase generator sets are rated at; a single-phase set is rated at 1."
    }
  ],
  "sources": [
    {
      "label": "Apparent power = real power / power factor; kVA = kW / PF, and the reactive part is kW x tan(arccos PF)"
    },
    {
      "label": "Cummins Inc., 2022 Global Product Guide — Power Generation Products (GLM-5763-EN): the diesel sets are listed with their kWe at 0.8 of their kVA (the C20D6 at 25 kVA and 20 kWe standby, the C30D6 at 37.5 kVA and 30 kWe), the three-phase convention the opening 0.8 follows; the single-phase sets are listed in kW with a current that is the kW divided by the volts, so their kVA and kW are the same number (the RV QG 2800 at 2.8 kW and 23.3 A on 120 V, the RV QG 2300 at 2.3 kW and 10 A on 230 V, the QD5000 at 4.8 kW and 21 A on 230 V)",
      "url": "https://mart.cummins.com/imagelibrary/data/assetfiles/0058677.pdf"
    },
    {
      "label": "Cummins Inc., Pre-Configured Diesel generator sets, specification sheet NAS-6437-EN (12/19): the C20 D6 set for 120/240 V, 1 phase, is 20 kW and 20 kVA standby at 60 Hz — the model the 2022 guide lists at 25 kVA and 20 kWe"
    }
  ],
  "testCases": [
    {
      "name": "80 kW at the opening 0.8 is 100 kVA",
      "inputs": {
        "kw": 80,
        "powerFactor": 0.8
      },
      "expected": 100,
      "toleranceDecimalPlaces": 6,
      "unit": "kVA",
      "confidence": "high",
      "steps": [
        {
          "label": "Real power entered",
          "value": 80,
          "unit": "kW"
        },
        {
          "label": "Power factor applied",
          "value": 0.8
        },
        {
          "label": "Reactive power, kW × tan(arccos PF)",
          "value": 59.99999999999998,
          "unit": "kvar"
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "a saved line with no power factor is still read at 0.8",
      "inputs": {
        "kw": 80
      },
      "expected": 100,
      "toleranceDecimalPlaces": 6,
      "unit": "kVA",
      "confidence": "high",
      "steps": [
        {
          "label": "Real power entered",
          "value": 80,
          "unit": "kW"
        },
        {
          "label": "Power factor applied",
          "value": 0.8
        },
        {
          "label": "Reactive power, kW × tan(arccos PF)",
          "value": 59.99999999999998,
          "unit": "kvar"
        }
      ],
      "basis": "cited",
      "sourceIndex": 1
    },
    {
      "name": "power factor 1: the kVA equal the kW",
      "inputs": {
        "kw": 45,
        "powerFactor": 1
      },
      "expected": 45,
      "toleranceDecimalPlaces": 6,
      "unit": "kVA",
      "confidence": "high",
      "steps": [
        {
          "label": "Real power entered",
          "value": 45,
          "unit": "kW"
        },
        {
          "label": "Power factor applied",
          "value": 1
        },
        {
          "label": "Reactive power, kW × tan(arccos PF)",
          "value": 0,
          "unit": "kvar"
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "a 20 kW load at 0.8 needs the 25 kVA a C20D6 is badged at",
      "inputs": {
        "kw": 20,
        "powerFactor": 0.8
      },
      "expected": 25,
      "toleranceDecimalPlaces": 6,
      "unit": "kVA",
      "confidence": "high",
      "steps": [
        {
          "label": "Real power entered",
          "value": 20,
          "unit": "kW"
        },
        {
          "label": "Power factor applied",
          "value": 0.8
        },
        {
          "label": "Reactive power, kW × tan(arccos PF)",
          "value": 14.999999999999995,
          "unit": "kvar"
        }
      ],
      "basis": "cited",
      "sourceIndex": 1
    },
    {
      "name": "50 kW at 0.7 is 71.43 kVA",
      "inputs": {
        "kw": 50,
        "powerFactor": 0.7
      },
      "expected": 71.428571,
      "toleranceDecimalPlaces": 5,
      "unit": "kVA",
      "confidence": "high",
      "steps": [
        {
          "label": "Real power entered",
          "value": 50,
          "unit": "kW"
        },
        {
          "label": "Power factor applied",
          "value": 0.7
        },
        {
          "label": "Reactive power, kW × tan(arccos PF)",
          "value": 51.010203061020356,
          "unit": "kvar"
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    }
  ]
}