  "version": "v1",
  "source": "https://craftquantities.com",
  "licence": "CC BY 4.0",
  "licenceUrl": "https://creativecommons.org/licenses/by/4.0/",
  "attribution": "Craft Quantities — craftquantities.com",
  "documentation": "https://craftquantities.com/api/",
  "versioning": "Fields are added, never removed or repurposed, within a version. A breaking change becomes /api/v2/ and v1 keeps being built.",
  "slug": "heating-circuit-flow-rate-calculator",
  "category": "plumbing-hvac",
  "title": "Heating Circuit Flow Rate Calculator (Heat Output, ΔT and Pipe Velocity)",
  "description": "The water flow a radiator, circuit or heating system needs to carry its heat at a design temperature drop, and its velocity in the pipe feeding it.",
  "url": "https://craftquantities.com/calculators/plumbing-hvac/heating-circuit-flow-rate-calculator/",
  "json": "https://craftquantities.com/api/v1/calculators/heating-circuit-flow-rate-calculator.json",
  "inputCount": 3,
  "testCaseCount": 3,
  "sourceCount": 3,
  "lastVerified": "2026-09-22",
  "citation": {
    "author": "Craft Quantities",
    "title": "Heating Circuit Flow Rate Calculator (Heat Output, ΔT and Pipe Velocity)",
    "version": "1.0.0",
    "sourcesChecked": "2026-09-22",
    "url": "https://craftquantities.com/calculators/plumbing-hvac/heating-circuit-flow-rate-calculator/",
    "accessDate": null,
    "accessDateNote": "Add the date you retrieved this. It is deliberately absent: a static file cannot know when you read it, and the build date would be wrong.",
    "permanentVersionedUrl": null,
    "permanentVersionedUrlNote": "Not offered. This site keeps no archive of previous builds, so any such URL would resolve to the current page or to nothing. The version and sourcesChecked fields identify the calculation instead.",
    "formats": {
      "plain": "Craft Quantities. Heating Circuit Flow Rate Calculator (Heat Output, ΔT and Pipe Velocity). Version 1.0.0. Sources checked 2026-09-22. https://craftquantities.com/calculators/plumbing-hvac/heating-circuit-flow-rate-calculator/",
      "apa": "Craft Quantities. (2026). Heating Circuit Flow Rate Calculator (Heat Output, ΔT and Pipe Velocity) (Version 1.0.0) [Web calculator]. Retrieved from https://craftquantities.com/calculators/plumbing-hvac/heating-circuit-flow-rate-calculator/",
      "harvard": "Craft Quantities (2026) Heating Circuit Flow Rate Calculator (Heat Output, ΔT and Pipe Velocity) (Version 1.0.0). Available at: https://craftquantities.com/calculators/plumbing-hvac/heating-circuit-flow-rate-calculator/",
      "bibtex": "@misc{craftquantities-calculators-plumbing-hvac-heating-circuit-flow-rate-calculator,\n  author       = {{Craft Quantities}},\n  title        = {Heating Circuit Flow Rate Calculator (Heat Output, ΔT and Pipe Velocity)},\n  version      = {1.0.0},\n  year         = {2026},\n  howpublished = {\\url{https://craftquantities.com/calculators/plumbing-hvac/heating-circuit-flow-rate-calculator/}},\n}"
    }
  },
  "inputs": [
    {
      "id": "heatOutput",
      "label": "Heat Output to Carry",
      "type": "number",
      "dimension": "thermal",
      "defaultValue": 10000,
      "min": 100,
      "max": 10000000,
      "step": 100,
      "help": "The emitter's output at the design water temperature, or the whole circuit's load."
    },
    {
      "id": "deltaT",
      "label": "Design Temperature Drop (Flow to Return)",
      "type": "number",
      "dimension": "tempdelta",
      "defaultValue": 20,
      "min": 1,
      "max": 60,
      "step": 0.5,
      "help": "The difference between flow and return water temperatures the system is designed for."
    },
    {
      "id": "bore",
      "label": "Internal Bore of the Pipe",
      "type": "number",
      "dimension": "length",
      "defaultValue": 0.0136,
      "min": 0.005,
      "max": 0.5,
      "step": 0.0001,
      "help": "The inside diameter of the pipe carrying this flow, not its nominal size."
    }
  ],
  "sources": [
    {
      "label": "Heat carried by water: Q = ṁ × c × ΔT, so the flow is the heat output ÷ (4.186 kJ/kg·K × the design temperature drop), with a litre of water taken as a kilogram"
    },
    {
      "label": "CIBSE Guide C, Reference data — the properties of water; BS EN 12828, Heating systems in buildings — Design for water-based heating systems"
    },
    {
      "label": "Velocity in the pipe = the volume flow ÷ the bore's cross-sectional area, π × d² ÷ 4"
    }
  ],
  "testCases": [
    {
      "name": "10 kW at a boiler's 20 K drop",
      "inputs": {
        "heatOutput": 10000,
        "deltaT": 20,
        "bore": 0.0136
      },
      "expected": 7.16675,
      "toleranceDecimalPlaces": 3,
      "unit": "L/min",
      "confidence": "high",
      "steps": [
        {
          "label": "The same flow in litres per second",
          "value": 0.11944577161968467,
          "unit": "L/s"
        },
        {
          "label": "Water velocity in the pipe",
          "value": 0.8222484854973375,
          "unit": "m/s"
        },
        {
          "label": "Mass of water per second",
          "value": 0.11944577161968467,
          "unit": "kg/s"
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "The same 10 kW at a heat pump's 5 K drop — four times the water",
      "inputs": {
        "heatOutput": 10000,
        "deltaT": 5,
        "bore": 0.0136
      },
      "expected": 28.66699,
      "toleranceDecimalPlaces": 3,
      "unit": "L/min",
      "confidence": "high",
      "steps": [
        {
          "label": "The same flow in litres per second",
          "value": 0.4777830864787387,
          "unit": "L/s"
        },
        {
          "label": "Water velocity in the pipe",
          "value": 3.28899394198935,
          "unit": "m/s"
        },
        {
          "label": "Mass of water per second",
          "value": 0.4777830864787387,
          "unit": "kg/s"
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "A 1.5 kW radiator at 20 K",
      "inputs": {
        "heatOutput": 1500,
        "deltaT": 20,
        "bore": 0.0136
      },
      "expected": 1.07501,
      "toleranceDecimalPlaces": 3,
      "unit": "L/min",
      "confidence": "high",
      "steps": [
        {
          "label": "The same flow in litres per second",
          "value": 0.0179168657429527,
          "unit": "L/s"
        },
        {
          "label": "Water velocity in the pipe",
          "value": 0.12333727282460061,
          "unit": "m/s"
        },
        {
          "label": "Mass of water per second",
          "value": 0.0179168657429527,
          "unit": "kg/s"
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    }
  ]
}