  "version": "v1",
  "source": "https://craftquantities.com",
  "licence": "CC BY 4.0",
  "licenceUrl": "https://creativecommons.org/licenses/by/4.0/",
  "attribution": "Craft Quantities — craftquantities.com",
  "documentation": "https://craftquantities.com/api/",
  "versioning": "Fields are added, never removed or repurposed, within a version. A breaking change becomes /api/v2/ and v1 keeps being built.",
  "slug": "ground-rod-resistance-calculator",
  "category": "materials-quantities",
  "title": "Isolated Ground Rod Earth Resistance Calculator (Dwight's Formula)",
  "description": "Calculate a single driven ground rod's earth resistance using Dwight's formula.",
  "url": "https://craftquantities.com/calculators/materials-quantities/ground-rod-resistance-calculator/",
  "json": "https://craftquantities.com/api/v1/calculators/ground-rod-resistance-calculator.json",
  "inputCount": 3,
  "testCaseCount": 2,
  "sourceCount": 1,
  "lastVerified": "2026-09-06",
  "translations": {
    "es-US": "https://craftquantities.com/es/calculators/materials-quantities/ground-rod-resistance-calculator/"
  },
  "citation": {
    "author": "Craft Quantities",
    "title": "Isolated Ground Rod Earth Resistance Calculator (Dwight's Formula)",
    "version": "1.0.1",
    "sourcesChecked": "2026-09-06",
    "url": "https://craftquantities.com/calculators/materials-quantities/ground-rod-resistance-calculator/",
    "accessDate": null,
    "accessDateNote": "Add the date you retrieved this. It is deliberately absent: a static file cannot know when you read it, and the build date would be wrong.",
    "permanentVersionedUrl": null,
    "permanentVersionedUrlNote": "Not offered. This site keeps no archive of previous builds, so any such URL would resolve to the current page or to nothing. The version and sourcesChecked fields identify the calculation instead.",
    "formats": {
      "plain": "Craft Quantities. Isolated Ground Rod Earth Resistance Calculator (Dwight's Formula). Version 1.0.1. Sources checked 2026-09-06. https://craftquantities.com/calculators/materials-quantities/ground-rod-resistance-calculator/",
      "apa": "Craft Quantities. (2026). Isolated Ground Rod Earth Resistance Calculator (Dwight's Formula) (Version 1.0.1) [Web calculator]. Retrieved from https://craftquantities.com/calculators/materials-quantities/ground-rod-resistance-calculator/",
      "harvard": "Craft Quantities (2026) Isolated Ground Rod Earth Resistance Calculator (Dwight's Formula) (Version 1.0.1). Available at: https://craftquantities.com/calculators/materials-quantities/ground-rod-resistance-calculator/",
      "bibtex": "@misc{craftquantities-calculators-materials-quantities-ground-rod-resistance-calculator,\n  author       = {{Craft Quantities}},\n  title        = {Isolated Ground Rod Earth Resistance Calculator (Dwight's Formula)},\n  version      = {1.0.1},\n  year         = {2026},\n  howpublished = {\\url{https://craftquantities.com/calculators/materials-quantities/ground-rod-resistance-calculator/}},\n}"
    }
  },
  "inputs": [
    {
      "id": "soilResistivity",
      "label": "Soil Resistivity ρ (Ω·m)",
      "type": "number",
      "defaultValue": 100,
      "min": 10,
      "max": 1000,
      "step": 10,
      "help": "How strongly the surrounding soil resists electrical current flow."
    },
    {
      "id": "rodLength",
      "label": "Rod driven length",
      "type": "number",
      "dimension": "length",
      "defaultValue": 2.4,
      "min": 0.01,
      "max": 6,
      "step": 0.1,
      "help": "The length of the ground rod actually driven into the earth."
    },
    {
      "id": "rodDiameter",
      "label": "Rod Diameter d (m, e.g. 0.0159 for 5/8 in)",
      "type": "number",
      "defaultValue": 0.0159,
      "min": 0.0127,
      "max": 0.025,
      "step": 0.0001,
      "help": "The rod's outer diameter."
    }
  ],
  "sources": [
    {
      "label": "Dwight's formula for a single driven ground rod: R = (ρ ÷ (2×π×L)) × (ln(8L÷d) − 1), where ρ is soil resistivity, L is the rod's driven length, and d is the rod diameter — a well-established, widely-cited formula for estimating single ground rod resistance (IEEE Std 142)"
    }
  ],
  "testCases": [
    {
      "name": "100 Ω·m soil, 2.4m rod, 5/8in diameter",
      "inputs": {
        "soilResistivity": 100,
        "rodLength": 2.4,
        "rodDiameter": 0.0159
      },
      "expected": 40.43,
      "toleranceDecimalPlaces": 1,
      "unit": "Ω",
      "confidence": "medium",
      "steps": [],
      "basis": "sole-source",
      "sourceIndex": 0
    },
    {
      "name": "150 Ω·m soil, 3.0m rod, 3/4in diameter",
      "inputs": {
        "soilResistivity": 150,
        "rodLength": 3,
        "rodDiameter": 0.0191
      },
      "expected": 48.83,
      "toleranceDecimalPlaces": 2,
      "unit": "Ω",
      "confidence": "medium",
      "steps": [],
      "basis": "sole-source",
      "sourceIndex": 0
    }
  ]
}