  "version": "v1",
  "source": "https://craftquantities.com",
  "licence": "CC BY 4.0",
  "licenceUrl": "https://creativecommons.org/licenses/by/4.0/",
  "attribution": "Craft Quantities — craftquantities.com",
  "documentation": "https://craftquantities.com/api/",
  "versioning": "Fields are added, never removed or repurposed, within a version. A breaking change becomes /api/v2/ and v1 keeps being built.",
  "slug": "gas-pipe-sizing-calculator",
  "category": "plumbing-hvac",
  "title": "Gas Pipe Sizing Calculator (Longest-Length Method)",
  "description": "Turn a connected appliance load into the gas flow and the table row the NFPA 54 longest-length method needs, for natural gas or propane.",
  "url": "https://craftquantities.com/calculators/plumbing-hvac/gas-pipe-sizing-calculator/",
  "json": "https://craftquantities.com/api/v1/calculators/gas-pipe-sizing-calculator.json",
  "inputCount": 6,
  "testCaseCount": 4,
  "sourceCount": 4,
  "lastVerified": "2026-09-11",
  "citation": {
    "author": "Craft Quantities",
    "title": "Gas Pipe Sizing Calculator (Longest-Length Method)",
    "version": "1.0.0",
    "sourcesChecked": "2026-09-11",
    "url": "https://craftquantities.com/calculators/plumbing-hvac/gas-pipe-sizing-calculator/",
    "accessDate": null,
    "accessDateNote": "Add the date you retrieved this. It is deliberately absent: a static file cannot know when you read it, and the build date would be wrong.",
    "permanentVersionedUrl": null,
    "permanentVersionedUrlNote": "Not offered. This site keeps no archive of previous builds, so any such URL would resolve to the current page or to nothing. The version and sourcesChecked fields identify the calculation instead.",
    "formats": {
      "plain": "Craft Quantities. Gas Pipe Sizing Calculator (Longest-Length Method). Version 1.0.0. Sources checked 2026-09-11. https://craftquantities.com/calculators/plumbing-hvac/gas-pipe-sizing-calculator/",
      "apa": "Craft Quantities. (2026). Gas Pipe Sizing Calculator (Longest-Length Method) (Version 1.0.0) [Web calculator]. Retrieved from https://craftquantities.com/calculators/plumbing-hvac/gas-pipe-sizing-calculator/",
      "harvard": "Craft Quantities (2026) Gas Pipe Sizing Calculator (Longest-Length Method) (Version 1.0.0). Available at: https://craftquantities.com/calculators/plumbing-hvac/gas-pipe-sizing-calculator/",
      "bibtex": "@misc{craftquantities-calculators-plumbing-hvac-gas-pipe-sizing-calculator,\n  author       = {{Craft Quantities}},\n  title        = {Gas Pipe Sizing Calculator (Longest-Length Method)},\n  version      = {1.0.0},\n  year         = {2026},\n  howpublished = {\\url{https://craftquantities.com/calculators/plumbing-hvac/gas-pipe-sizing-calculator/}},\n}"
    }
  },
  "inputs": [
    {
      "id": "fuelType",
      "label": "Fuel",
      "type": "select",
      "defaultValue": "natural",
      "options": [
        {
          "value": "natural",
          "label": "Natural gas (0.60 specific gravity)"
        },
        {
          "value": "propane",
          "label": "Propane / LPG (1.50 specific gravity)"
        }
      ],
      "help": "Which fuel the system carries — it changes the required flow by a factor of nearly two and a half."
    },
    {
      "id": "connectedLoadBtu",
      "label": "Total connected load (BTU/h)",
      "type": "number",
      "defaultValue": 250000,
      "min": 1000,
      "max": 5000000,
      "step": 1000,
      "help": "Add the input rating of every gas appliance the section of pipe serves."
    },
    {
      "id": "developedLength",
      "label": "Developed length to the most remote outlet",
      "type": "number",
      "dimension": "length",
      "defaultValue": 18.288,
      "min": 1,
      "max": 200,
      "step": 0.5,
      "help": "The measured run of pipe from the point of delivery to the furthest appliance."
    },
    {
      "id": "pipeMaterial",
      "label": "Pipe material",
      "type": "select",
      "defaultValue": "schedule-40",
      "options": [
        {
          "value": "schedule-40",
          "label": "Black iron, schedule 40"
        },
        {
          "value": "copper",
          "label": "Copper tube"
        },
        {
          "value": "csst",
          "label": "CSST (corrugated stainless steel tubing)"
        },
        {
          "value": "pe",
          "label": "Polyethylene (buried)"
        }
      ],
      "help": "Which capacity table the flow figure has to be read against."
    },
    {
      "id": "inletPressure",
      "label": "Supply pressure at the meter or regulator",
      "type": "select",
      "defaultValue": "low",
      "options": [
        {
          "value": "low",
          "label": "Low pressure — about 7 in w.c. (standard residential)"
        },
        {
          "value": "two-psi",
          "label": "2 psi, with regulators at the appliances"
        },
        {
          "value": "five-psi",
          "label": "5 psi or higher, with regulators at the appliances"
        }
      ],
      "help": "The pressure the system runs at — it selects an entirely different capacity table."
    },
    {
      "id": "allowableDrop",
      "label": "Allowable pressure drop",
      "type": "select",
      "defaultValue": "0.3",
      "options": [
        {
          "value": "0.3",
          "label": "0.3 in w.c. (the usual residential basis)"
        },
        {
          "value": "0.5",
          "label": "0.5 in w.c."
        },
        {
          "value": "1.0",
          "label": "1.0 in w.c."
        }
      ],
      "help": "How much pressure the design allows the pipe to lose between the meter and the furthest appliance."
    }
  ],
  "sources": [
    {
      "label": "NFPA 54 / IFGC longest-length method: every section of the piping system is sized from the total developed length of the run to the most remote outlet, using the total connected load carried by that section"
    },
    {
      "label": "NFPA 54 6.2: where the measured length falls between two tabulated lengths, the next longer length is used"
    },
    {
      "label": "Capacity in cubic feet per hour = connected load in BTU/h ÷ the gas heating value per cubic foot. Planning values: natural gas commonly 1,000–1,050 BTU/ft³, commercial propane about 2,500 BTU/ft³ — the supplier's published figure governs"
    },
    {
      "label": "Standard table bases: natural gas at 0.60 specific gravity, propane at 1.50. A table computed for one gas does not apply to the other"
    }
  ],
  "testCases": [
    {
      "name": "250,000 BTU/h of natural gas is 243 CFH",
      "inputs": {
        "fuelType": "natural",
        "connectedLoadBtu": 250000,
        "developedLength": 18.288,
        "pipeMaterial": "schedule-40",
        "inletPressure": "low",
        "allowableDrop": "0.3"
      },
      "expected": 242.7,
      "toleranceDecimalPlaces": 1,
      "unit": "CFH",
      "confidence": "medium",
      "steps": [
        {
          "label": "Table row to read — next tabulated length at or above the measured run",
          "value": 60,
          "unit": "ft"
        },
        {
          "label": "Measured developed length",
          "value": 59.99999999999999,
          "unit": "ft"
        },
        {
          "label": "Heating value used (BTU per ft³)",
          "value": 1030,
          "unit": "BTU per ft³"
        },
        {
          "label": "Gas specific gravity the table must be computed at",
          "value": 0.6
        },
        {
          "label": "Same flow in cubic metres an hour",
          "value": 6.873021017475728,
          "unit": "m³/h"
        }
      ],
      "basis": "ambiguous"
    },
    {
      "name": "The same load on propane is 100 CFH",
      "inputs": {
        "fuelType": "propane",
        "connectedLoadBtu": 250000,
        "developedLength": 18.288,
        "pipeMaterial": "schedule-40",
        "inletPressure": "low",
        "allowableDrop": "0.3"
      },
      "expected": 100,
      "toleranceDecimalPlaces": 4,
      "unit": "CFH",
      "confidence": "medium",
      "steps": [
        {
          "label": "Table row to read — next tabulated length at or above the measured run",
          "value": 60,
          "unit": "ft"
        },
        {
          "label": "Measured developed length",
          "value": 59.99999999999999,
          "unit": "ft"
        },
        {
          "label": "Heating value used (BTU per ft³)",
          "value": 2500,
          "unit": "BTU per ft³"
        },
        {
          "label": "Gas specific gravity the table must be computed at",
          "value": 1.5
        },
        {
          "label": "Same flow in cubic metres an hour",
          "value": 2.8316846592,
          "unit": "m³/h"
        }
      ],
      "basis": "ambiguous"
    },
    {
      "name": "A single 100,000 BTU/h furnace is 97 CFH",
      "inputs": {
        "fuelType": "natural",
        "connectedLoadBtu": 100000,
        "developedLength": 9.144,
        "pipeMaterial": "schedule-40",
        "inletPressure": "low",
        "allowableDrop": "0.3"
      },
      "expected": 97.09,
      "toleranceDecimalPlaces": 2,
      "unit": "CFH",
      "confidence": "medium",
      "steps": [
        {
          "label": "Table row to read — next tabulated length at or above the measured run",
          "value": 30,
          "unit": "ft"
        },
        {
          "label": "Measured developed length",
          "value": 29.999999999999996,
          "unit": "ft"
        },
        {
          "label": "Heating value used (BTU per ft³)",
          "value": 1030,
          "unit": "BTU per ft³"
        },
        {
          "label": "Gas specific gravity the table must be computed at",
          "value": 0.6
        },
        {
          "label": "Same flow in cubic metres an hour",
          "value": 2.7492084069902916,
          "unit": "m³/h"
        }
      ],
      "basis": "ambiguous"
    },
    {
      "name": "A 600,000 BTU/h commercial load is 583 CFH",
      "inputs": {
        "fuelType": "natural",
        "connectedLoadBtu": 600000,
        "developedLength": 30.48,
        "pipeMaterial": "csst",
        "inletPressure": "two-psi",
        "allowableDrop": "1.0"
      },
      "expected": 582.5,
      "toleranceDecimalPlaces": 1,
      "unit": "CFH",
      "confidence": "medium",
      "steps": [
        {
          "label": "Table row to read — next tabulated length at or above the measured run",
          "value": 100,
          "unit": "ft"
        },
        {
          "label": "Measured developed length",
          "value": 99.99999999999999,
          "unit": "ft"
        },
        {
          "label": "Heating value used (BTU per ft³)",
          "value": 1030,
          "unit": "BTU per ft³"
        },
        {
          "label": "Gas specific gravity the table must be computed at",
          "value": 0.6
        },
        {
          "label": "Same flow in cubic metres an hour",
          "value": 16.49525044194175,
          "unit": "m³/h"
        }
      ],
      "basis": "ambiguous"
    }
  ]
}