  "version": "v1",
  "source": "https://craftquantities.com",
  "licence": "CC BY 4.0",
  "licenceUrl": "https://creativecommons.org/licenses/by/4.0/",
  "attribution": "Craft Quantities — craftquantities.com",
  "documentation": "https://craftquantities.com/api/",
  "versioning": "Fields are added, never removed or repurposed, within a version. A breaking change becomes /api/v2/ and v1 keeps being built.",
  "slug": "fire-extinguisher-count-calculator",
  "category": "materials-quantities",
  "title": "Fire Extinguisher Count and Travel Distance Calculator",
  "description": "How many extinguishers a floor takes by the area rule and by the travel rule — and which of the two governs, because it is usually the one people skip.",
  "url": "https://craftquantities.com/calculators/materials-quantities/fire-extinguisher-count-calculator/",
  "json": "https://craftquantities.com/api/v1/calculators/fire-extinguisher-count-calculator.json",
  "inputCount": 5,
  "testCaseCount": 4,
  "sourceCount": 3,
  "lastVerified": "2026-09-23",
  "citation": {
    "author": "Craft Quantities",
    "title": "Fire Extinguisher Count and Travel Distance Calculator",
    "version": "1.0.0",
    "sourcesChecked": "2026-09-23",
    "url": "https://craftquantities.com/calculators/materials-quantities/fire-extinguisher-count-calculator/",
    "accessDate": null,
    "accessDateNote": "Add the date you retrieved this. It is deliberately absent: a static file cannot know when you read it, and the build date would be wrong.",
    "permanentVersionedUrl": null,
    "permanentVersionedUrlNote": "Not offered. This site keeps no archive of previous builds, so any such URL would resolve to the current page or to nothing. The version and sourcesChecked fields identify the calculation instead.",
    "formats": {
      "plain": "Craft Quantities. Fire Extinguisher Count and Travel Distance Calculator. Version 1.0.0. Sources checked 2026-09-23. https://craftquantities.com/calculators/materials-quantities/fire-extinguisher-count-calculator/",
      "apa": "Craft Quantities. (2026). Fire Extinguisher Count and Travel Distance Calculator (Version 1.0.0) [Web calculator]. Retrieved from https://craftquantities.com/calculators/materials-quantities/fire-extinguisher-count-calculator/",
      "harvard": "Craft Quantities (2026) Fire Extinguisher Count and Travel Distance Calculator (Version 1.0.0). Available at: https://craftquantities.com/calculators/materials-quantities/fire-extinguisher-count-calculator/",
      "bibtex": "@misc{craftquantities-calculators-materials-quantities-fire-extinguisher-count-calculator,\n  author       = {{Craft Quantities}},\n  title        = {Fire Extinguisher Count and Travel Distance Calculator},\n  version      = {1.0.0},\n  year         = {2026},\n  howpublished = {\\url{https://craftquantities.com/calculators/materials-quantities/fire-extinguisher-count-calculator/}},\n}"
    }
  },
  "inputs": [
    {
      "id": "floorArea",
      "label": "Floor area per storey",
      "type": "number",
      "dimension": "area",
      "defaultValue": 1000,
      "min": 10,
      "max": 100000,
      "step": 10,
      "help": "The area one storey covers."
    },
    {
      "id": "hazard",
      "label": "Hazard class",
      "type": "select",
      "defaultValue": "ordinary",
      "options": [
        {
          "value": "light",
          "label": "Light — offices, classrooms, assembly"
        },
        {
          "value": "ordinary",
          "label": "Ordinary — retail, workshops, parking"
        },
        {
          "value": "extra",
          "label": "Extra — woodworking, painting, storage of combustibles"
        }
      ],
      "help": "What is in the space, not what the building is called."
    },
    {
      "id": "ratingA",
      "label": "Extinguisher A rating",
      "type": "number",
      "defaultValue": 2,
      "min": 1,
      "max": 40,
      "step": 1,
      "help": "The number before the A on the label — 2-A, 4-A, 10-A."
    },
    {
      "id": "travelDistance",
      "label": "Maximum travel distance",
      "type": "number",
      "dimension": "length",
      "defaultValue": 22.86,
      "min": 5,
      "max": 60,
      "step": 0.5,
      "help": "How far anybody may have to walk to reach one."
    },
    {
      "id": "minimumPerFloor",
      "label": "Minimum per storey",
      "type": "number",
      "defaultValue": 2,
      "min": 1,
      "max": 10,
      "step": 1,
      "help": "A floor gets at least this many however small it is."
    }
  ],
  "sources": [
    {
      "label": "NFPA 10 gives a maximum floor area per unit of A by hazard class — 3,000 sq ft light, 1,500 sq ft ordinary, 1,000 sq ft extra — with 11,250 sq ft the most any single extinguisher may cover whatever its rating"
    },
    {
      "label": "Maximum travel distance to a Class A extinguisher is 75 ft (about 23 m). On a square grid walked along its axes the worst case is half the spacing in each direction, so one extinguisher covers at most the travel distance squared"
    },
    {
      "label": "BS 5306-8 works to a comparable figure — a 30 m travel distance and a minimum of two extinguishers per floor — which is why the minimum-per-floor field exists"
    }
  ],
  "testCases": [
    {
      "name": "1,000 m² of ordinary hazard, 2-A, 22.86 m travel",
      "inputs": {
        "floorArea": 1000,
        "hazard": "ordinary",
        "ratingA": 2,
        "travelDistance": 22.86,
        "minimumPerFloor": 2
      },
      "expected": 4,
      "toleranceDecimalPlaces": 0,
      "unit": "extinguishers",
      "confidence": "medium",
      "steps": [
        {
          "label": "By the area rule",
          "value": 4,
          "unit": "extinguishers"
        },
        {
          "label": "By the travel rule",
          "value": 2,
          "unit": "extinguishers"
        },
        {
          "label": "Area one extinguisher covers, area rule",
          "value": 3000.0000000000005,
          "unit": "sq ft"
        },
        {
          "label": "Area one extinguisher covers, travel rule",
          "value": 5625,
          "unit": "sq ft"
        },
        {
          "label": "Grid spacing the travel rule allows",
          "value": 75,
          "unit": "ft"
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "Light hazard, where travel governs instead",
      "inputs": {
        "floorArea": 1000,
        "hazard": "light",
        "ratingA": 2,
        "travelDistance": 22.86,
        "minimumPerFloor": 2
      },
      "expected": 2,
      "toleranceDecimalPlaces": 0,
      "unit": "extinguishers",
      "confidence": "medium",
      "steps": [
        {
          "label": "By the area rule",
          "value": 2,
          "unit": "extinguishers"
        },
        {
          "label": "By the travel rule",
          "value": 2,
          "unit": "extinguishers"
        },
        {
          "label": "Area one extinguisher covers, area rule",
          "value": 6000.000000000001,
          "unit": "sq ft"
        },
        {
          "label": "Area one extinguisher covers, travel rule",
          "value": 5625,
          "unit": "sq ft"
        },
        {
          "label": "Grid spacing the travel rule allows",
          "value": 75,
          "unit": "ft"
        }
      ],
      "basis": "cited",
      "sourceIndex": 1
    },
    {
      "name": "Extra hazard, where the area rule bites hardest",
      "inputs": {
        "floorArea": 1000,
        "hazard": "extra",
        "ratingA": 2,
        "travelDistance": 22.86,
        "minimumPerFloor": 2
      },
      "expected": 6,
      "toleranceDecimalPlaces": 0,
      "unit": "extinguishers",
      "confidence": "medium",
      "steps": [
        {
          "label": "By the area rule",
          "value": 6,
          "unit": "extinguishers"
        },
        {
          "label": "By the travel rule",
          "value": 2,
          "unit": "extinguishers"
        },
        {
          "label": "Area one extinguisher covers, area rule",
          "value": 2000,
          "unit": "sq ft"
        },
        {
          "label": "Area one extinguisher covers, travel rule",
          "value": 5625,
          "unit": "sq ft"
        },
        {
          "label": "Grid spacing the travel rule allows",
          "value": 75,
          "unit": "ft"
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "A small floor still takes the minimum",
      "inputs": {
        "floorArea": 100,
        "hazard": "ordinary",
        "ratingA": 2,
        "travelDistance": 22.86,
        "minimumPerFloor": 2
      },
      "expected": 2,
      "toleranceDecimalPlaces": 0,
      "unit": "extinguishers",
      "confidence": "medium",
      "steps": [
        {
          "label": "By the area rule",
          "value": 1,
          "unit": "extinguishers"
        },
        {
          "label": "By the travel rule",
          "value": 1,
          "unit": "extinguishers"
        },
        {
          "label": "Area one extinguisher covers, area rule",
          "value": 3000.0000000000005,
          "unit": "sq ft"
        },
        {
          "label": "Area one extinguisher covers, travel rule",
          "value": 5625,
          "unit": "sq ft"
        },
        {
          "label": "Grid spacing the travel rule allows",
          "value": 75,
          "unit": "ft"
        }
      ],
      "basis": "cited",
      "sourceIndex": 2
    }
  ]
}