  "version": "v1",
  "source": "https://craftquantities.com",
  "licence": "CC BY 4.0",
  "licenceUrl": "https://creativecommons.org/licenses/by/4.0/",
  "attribution": "Craft Quantities — craftquantities.com",
  "documentation": "https://craftquantities.com/api/",
  "versioning": "Fields are added, never removed or repurposed, within a version. A breaking change becomes /api/v2/ and v1 keeps being built.",
  "slug": "duct-leakage-class-calculator",
  "category": "materials-quantities",
  "title": "SMACNA Duct Leakage Class Allowable Leakage Calculator",
  "description": "Calculate the maximum allowable duct system leakage rate for a given SMACNA Leakage Class, test pressure, and duct surface area.",
  "url": "https://craftquantities.com/calculators/materials-quantities/duct-leakage-class-calculator/",
  "json": "https://craftquantities.com/api/v1/calculators/duct-leakage-class-calculator.json",
  "inputCount": 3,
  "testCaseCount": 2,
  "sourceCount": 1,
  "lastVerified": "2026-09-06",
  "citation": {
    "author": "Craft Quantities",
    "title": "SMACNA Duct Leakage Class Allowable Leakage Calculator",
    "version": "1.0.1",
    "sourcesChecked": "2026-09-06",
    "url": "https://craftquantities.com/calculators/materials-quantities/duct-leakage-class-calculator/",
    "accessDate": null,
    "accessDateNote": "Add the date you retrieved this. It is deliberately absent: a static file cannot know when you read it, and the build date would be wrong.",
    "permanentVersionedUrl": null,
    "permanentVersionedUrlNote": "Not offered. This site keeps no archive of previous builds, so any such URL would resolve to the current page or to nothing. The version and sourcesChecked fields identify the calculation instead.",
    "formats": {
      "plain": "Craft Quantities. SMACNA Duct Leakage Class Allowable Leakage Calculator. Version 1.0.1. Sources checked 2026-09-06. https://craftquantities.com/calculators/materials-quantities/duct-leakage-class-calculator/",
      "apa": "Craft Quantities. (2026). SMACNA Duct Leakage Class Allowable Leakage Calculator (Version 1.0.1) [Web calculator]. Retrieved from https://craftquantities.com/calculators/materials-quantities/duct-leakage-class-calculator/",
      "harvard": "Craft Quantities (2026) SMACNA Duct Leakage Class Allowable Leakage Calculator (Version 1.0.1). Available at: https://craftquantities.com/calculators/materials-quantities/duct-leakage-class-calculator/",
      "bibtex": "@misc{craftquantities-calculators-materials-quantities-duct-leakage-class-calculator,\n  author       = {{Craft Quantities}},\n  title        = {SMACNA Duct Leakage Class Allowable Leakage Calculator},\n  version      = {1.0.1},\n  year         = {2026},\n  howpublished = {\\url{https://craftquantities.com/calculators/materials-quantities/duct-leakage-class-calculator/}},\n}"
    }
  },
  "inputs": [
    {
      "id": "leakageClass",
      "label": "SMACNA Leakage Class (CL)",
      "type": "number",
      "defaultValue": 6,
      "min": 3,
      "max": 48,
      "step": 1,
      "help": "The specified SMACNA duct leakage classification."
    },
    {
      "id": "testPressure",
      "label": "Test Pressure (in. w.g.)",
      "type": "number",
      "defaultValue": 2,
      "min": 0.5,
      "max": 10,
      "step": 0.25,
      "help": "The static pressure the duct system is tested at."
    },
    {
      "id": "ductSurfaceArea",
      "label": "Total Duct Surface Area",
      "type": "number",
      "dimension": "area",
      "defaultValue": 46.5,
      "min": 0.01,
      "max": 5000,
      "step": 5,
      "help": "The total external surface area of the ductwork being tested."
    }
  ],
  "sources": [
    {
      "label": "Allowable leakage (CFM per 100 ft² of duct surface) = Leakage Class (CL) × (Test Pressure, in. w.g.)^0.65, per the SMACNA HVAC Air Duct Leakage Test Manual. Total allowable leakage = that rate × (total duct surface area ÷ 100). Common Leakage Class ratings range from CL 3 (very tight, e.g. hospital/cleanroom systems) to CL 24 (typical unsealed low-pressure ductwork), with CL 6 and CL 12 commonly specified for sealed low/medium pressure systems."
    }
  ],
  "testCases": [
    {
      "name": "CL 6, 2 in. w.g., 500 ft² of duct",
      "inputs": {
        "leakageClass": 6,
        "testPressure": 2,
        "ductSurfaceArea": 46.45
      },
      "expected": 47.08,
      "toleranceDecimalPlaces": 1,
      "unit": "CFM",
      "confidence": "high",
      "steps": [
        {
          "label": "Allowable leakage rate per 100 ft² of duct surface",
          "value": 9.415009174761009,
          "unit": "CFM/100 ft²"
        }
      ],
      "basis": "sole-source",
      "sourceIndex": 0
    },
    {
      "name": "CL 12, 4 in. w.g., 800 ft² of duct",
      "inputs": {
        "leakageClass": 12,
        "testPressure": 4,
        "ductSurfaceArea": 74.32
      },
      "expected": 236.38,
      "toleranceDecimalPlaces": 1,
      "unit": "CFM",
      "confidence": "high",
      "steps": [
        {
          "label": "Allowable leakage rate per 100 ft² of duct surface",
          "value": 29.547465920277993,
          "unit": "CFM/100 ft²"
        }
      ],
      "basis": "sole-source",
      "sourceIndex": 0
    }
  ]
}