  "version": "v1",
  "source": "https://craftquantities.com",
  "licence": "CC BY 4.0",
  "licenceUrl": "https://creativecommons.org/licenses/by/4.0/",
  "attribution": "Craft Quantities — craftquantities.com",
  "documentation": "https://craftquantities.com/api/",
  "versioning": "Fields are added, never removed or repurposed, within a version. A breaking change becomes /api/v2/ and v1 keeps being built.",
  "slug": "copper-aluminum-wire-equivalent-calculator",
  "category": "electrical",
  "title": "Copper to Aluminum Wire Size Calculator (Aluminium Equivalent, AWG and mm²)",
  "description": "What aluminum wire size equals a copper one? The smallest aluminum conductor with no more resistance, in AWG, kcmil or mm², and how near the size below is.",
  "url": "https://craftquantities.com/calculators/electrical/copper-aluminum-wire-equivalent-calculator/",
  "json": "https://craftquantities.com/api/v1/calculators/copper-aluminum-wire-equivalent-calculator.json",
  "inputCount": 1,
  "testCaseCount": 37,
  "sourceCount": 4,
  "lastVerified": "2026-10-05",
  "citation": {
    "author": "Craft Quantities",
    "title": "Copper to Aluminum Wire Size Calculator (Aluminium Equivalent, AWG and mm²)",
    "version": "1.0.0",
    "sourcesChecked": "2026-10-05",
    "url": "https://craftquantities.com/calculators/electrical/copper-aluminum-wire-equivalent-calculator/",
    "accessDate": null,
    "accessDateNote": "Add the date you retrieved this. It is deliberately absent: a static file cannot know when you read it, and the build date would be wrong.",
    "permanentVersionedUrl": null,
    "permanentVersionedUrlNote": "Not offered. This site keeps no archive of previous builds, so any such URL would resolve to the current page or to nothing. The version and sourcesChecked fields identify the calculation instead.",
    "formats": {
      "plain": "Craft Quantities. Copper to Aluminum Wire Size Calculator (Aluminium Equivalent, AWG and mm²). Version 1.0.0. Sources checked 2026-10-05. https://craftquantities.com/calculators/electrical/copper-aluminum-wire-equivalent-calculator/",
      "apa": "Craft Quantities. (2026). Copper to Aluminum Wire Size Calculator (Aluminium Equivalent, AWG and mm²) (Version 1.0.0) [Web calculator]. Retrieved from https://craftquantities.com/calculators/electrical/copper-aluminum-wire-equivalent-calculator/",
      "harvard": "Craft Quantities (2026) Copper to Aluminum Wire Size Calculator (Aluminium Equivalent, AWG and mm²) (Version 1.0.0). Available at: https://craftquantities.com/calculators/electrical/copper-aluminum-wire-equivalent-calculator/",
      "bibtex": "@misc{craftquantities-calculators-electrical-copper-aluminum-wire-equivalent-calculator,\n  author       = {{Craft Quantities}},\n  title        = {Copper to Aluminum Wire Size Calculator (Aluminium Equivalent, AWG and mm²)},\n  version      = {1.0.0},\n  year         = {2026},\n  howpublished = {\\url{https://craftquantities.com/calculators/electrical/copper-aluminum-wire-equivalent-calculator/}},\n}"
    }
  },
  "inputs": [
    {
      "id": "copperSize",
      "label": "Copper conductor",
      "type": "select",
      "defaultValue": "2/0",
      "optionsBySystem": {
        "imperial": [
          {
            "value": "14",
            "label": "14 AWG copper"
          },
          {
            "value": "12",
            "label": "12 AWG copper"
          },
          {
            "value": "10",
            "label": "10 AWG copper"
          },
          {
            "value": "8",
            "label": "8 AWG copper"
          },
          {
            "value": "6",
            "label": "6 AWG copper"
          },
          {
            "value": "4",
            "label": "4 AWG copper"
          },
          {
            "value": "3",
            "label": "3 AWG copper"
          },
          {
            "value": "2",
            "label": "2 AWG copper"
          },
          {
            "value": "1",
            "label": "1 AWG copper"
          },
          {
            "value": "1/0",
            "label": "1/0 AWG copper"
          },
          {
            "value": "2/0",
            "label": "2/0 AWG copper"
          },
          {
            "value": "3/0",
            "label": "3/0 AWG copper"
          },
          {
            "value": "4/0",
            "label": "4/0 AWG copper"
          },
          {
            "value": "250",
            "label": "250 kcmil copper"
          },
          {
            "value": "300",
            "label": "300 kcmil copper"
          },
          {
            "value": "350",
            "label": "350 kcmil copper"
          },
          {
            "value": "400",
            "label": "400 kcmil copper"
          },
          {
            "value": "500",
            "label": "500 kcmil copper"
          },
          {
            "value": "600",
            "label": "600 kcmil copper"
          },
          {
            "value": "750",
            "label": "750 kcmil copper"
          },
          {
            "value": "1000",
            "label": "1,000 kcmil copper"
          },
          {
            "value": "1.5mm2",
            "label": "1.5 mm² copper"
          },
          {
            "value": "2.5mm2",
            "label": "2.5 mm² copper"
          },
          {
            "value": "4mm2",
            "label": "4 mm² copper"
          },
          {
            "value": "6mm2",
            "label": "6 mm² copper"
          },
          {
            "value": "10mm2",
            "label": "10 mm² copper"
          },
          {
            "value": "16mm2",
            "label": "16 mm² copper"
          },
          {
            "value": "25mm2",
            "label": "25 mm² copper"
          },
          {
            "value": "35mm2",
            "label": "35 mm² copper"
          },
          {
            "value": "50mm2",
            "label": "50 mm² copper"
          },
          {
            "value": "70mm2",
            "label": "70 mm² copper"
          },
          {
            "value": "95mm2",
            "label": "95 mm² copper"
          },
          {
            "value": "120mm2",
            "label": "120 mm² copper"
          },
          {
            "value": "150mm2",
            "label": "150 mm² copper"
          },
          {
            "value": "185mm2",
            "label": "185 mm² copper"
          },
          {
            "value": "240mm2",
            "label": "240 mm² copper"
          },
          {
            "value": "300mm2",
            "label": "300 mm² copper"
          }
        ],
        "metric": [
          {
            "value": "1.5mm2",
            "label": "1.5 mm² copper"
          },
          {
            "value": "2.5mm2",
            "label": "2.5 mm² copper"
          },
          {
            "value": "4mm2",
            "label": "4 mm² copper"
          },
          {
            "value": "6mm2",
            "label": "6 mm² copper"
          },
          {
            "value": "10mm2",
            "label": "10 mm² copper"
          },
          {
            "value": "16mm2",
            "label": "16 mm² copper"
          },
          {
            "value": "25mm2",
            "label": "25 mm² copper"
          },
          {
            "value": "35mm2",
            "label": "35 mm² copper"
          },
          {
            "value": "50mm2",
            "label": "50 mm² copper"
          },
          {
            "value": "70mm2",
            "label": "70 mm² copper"
          },
          {
            "value": "95mm2",
            "label": "95 mm² copper"
          },
          {
            "value": "120mm2",
            "label": "120 mm² copper"
          },
          {
            "value": "150mm2",
            "label": "150 mm² copper"
          },
          {
            "value": "185mm2",
            "label": "185 mm² copper"
          },
          {
            "value": "240mm2",
            "label": "240 mm² copper"
          },
          {
            "value": "300mm2",
            "label": "300 mm² copper"
          },
          {
            "value": "14",
            "label": "14 AWG copper"
          },
          {
            "value": "12",
            "label": "12 AWG copper"
          },
          {
            "value": "10",
            "label": "10 AWG copper"
          },
          {
            "value": "8",
            "label": "8 AWG copper"
          },
          {
            "value": "6",
            "label": "6 AWG copper"
          },
          {
            "value": "4",
            "label": "4 AWG copper"
          },
          {
            "value": "3",
            "label": "3 AWG copper"
          },
          {
            "value": "2",
            "label": "2 AWG copper"
          },
          {
            "value": "1",
            "label": "1 AWG copper"
          },
          {
            "value": "1/0",
            "label": "1/0 AWG copper"
          },
          {
            "value": "2/0",
            "label": "2/0 AWG copper"
          },
          {
            "value": "3/0",
            "label": "3/0 AWG copper"
          },
          {
            "value": "4/0",
            "label": "4/0 AWG copper"
          },
          {
            "value": "250",
            "label": "250 kcmil copper"
          },
          {
            "value": "300",
            "label": "300 kcmil copper"
          },
          {
            "value": "350",
            "label": "350 kcmil copper"
          },
          {
            "value": "400",
            "label": "400 kcmil copper"
          },
          {
            "value": "500",
            "label": "500 kcmil copper"
          },
          {
            "value": "600",
            "label": "600 kcmil copper"
          },
          {
            "value": "750",
            "label": "750 kcmil copper"
          },
          {
            "value": "1000",
            "label": "1,000 kcmil copper"
          }
        ]
      },
      "help": "The copper size you want an aluminum equal for: AWG and kcmil, or mm²."
    }
  ],
  "sources": [
    {
      "label": "IAEI Magazine, \"Voltage Drop Formulas\" (March/April 2017): K constants at 75 °C (167 °F) read off NEC Chapter 9 Table 8 — 12.9 for uncoated copper (1,000 kcmil at 0.0129 Ω per 1,000 ft, 0.0423 Ω/km) and 21.2 for aluminum (0.0212 Ω per 1,000 ft, 0.0696 Ω/km) — with every size in the table close to them",
      "url": "https://iaeimagazine.org/electrical-fundamentals/voltage-drop-formulas/"
    },
    {
      "label": "Bayerische Kabelwerke AG (Bayka), Conductor resistance at 20 °C (68 °F) acc. to EN 60228: plain copper and aluminium, class 1 and 2 — 16 mm² copper 1.15 Ω/km (0.351 Ω per 1,000 ft) against 25 mm² aluminium 1.20 (0.366) and 35 mm² aluminium 0.868 (0.265)",
      "url": "https://www.bayka.de/en/service/technical-information/conductor-resistance"
    },
    {
      "label": "NBS Handbook 109, Aluminum Wire Tables: EC-H19 aluminum at 61.0% IACS, 17.002 Ω·cmil/ft (0.028264 Ω·mm²/m) at 20 °C (68 °F), against the International Annealed Copper Standard's 10.371 (0.017241) — a ratio of 1.639",
      "url": "https://nvlpubs.nist.gov/nistpubs/Legacy/hb/nbshandbook109.pdf"
    },
    {
      "label": "Minnesota Department of Labor and Industry, Electrical Inspection Checklist for One-Family Dwellings based on the 2023 NEC (revised 2023-05-06): dwelling service conductors under NEC 310.12 — 4 AWG copper or 2 AWG aluminum at 100 A, 1 AWG or 2/0 at 150 A, 2/0 or 4/0 at 200 A, 400 or 600 kcmil at 400 A; and dissimilar metals not intermixed unless the device is listed for it (NEC 110.14)",
      "url": "https://www.dli.mn.gov/sites/default/files/pdf/eli_inspection_checklist2023NEC.pdf"
    }
  ],
  "testCases": [
    {
      "name": "the opening: 2/0 copper needs 250 kcmil aluminum for equal resistance",
      "inputs": {
        "copperSize": "2/0"
      },
      "expected": 250,
      "toleranceDecimalPlaces": 6,
      "unit": "kcmil",
      "confidence": "high",
      "steps": [
        {
          "label": "Copper conductor area (kcmil)",
          "value": 133.1
        },
        {
          "label": "Aluminum area for equal resistance (kcmil)",
          "value": 218.737984496124
        },
        {
          "label": "The same area in mm²",
          "value": 110.83617270689852,
          "unit": "mm²"
        },
        {
          "label": "This aluminum size's resistance against the copper's (%)",
          "value": 87.4951937984496
        },
        {
          "label": "The size below it, 4/0 AWG: area (kcmil)",
          "value": 211.6
        },
        {
          "label": "The size below it: resistance against the copper's (%)",
          "value": 103.37333860875427
        },
        {
          "label": "Aluminum's resistance per circular mil against copper's, 21.2 ÷ 12.9",
          "value": 1.643410852713178
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "12 AWG copper needs 8 AWG aluminum: 10 AWG is 3% over",
      "inputs": {
        "copperSize": "12"
      },
      "expected": 16.51,
      "toleranceDecimalPlaces": 6,
      "unit": "kcmil (8 AWG)",
      "confidence": "high",
      "steps": [
        {
          "label": "Copper conductor area (kcmil)",
          "value": 6.53
        },
        {
          "label": "Aluminum area for equal resistance (kcmil)",
          "value": 10.731472868217054
        },
        {
          "label": "The same area in mm²",
          "value": 5.437717564057456,
          "unit": "mm²"
        },
        {
          "label": "This aluminum size's resistance against the copper's (%)",
          "value": 64.99983566454908
        },
        {
          "label": "The size below it, 10 AWG: area (kcmil)",
          "value": 10.38
        },
        {
          "label": "The size below it: resistance against the copper's (%)",
          "value": 103.38605846066527
        },
        {
          "label": "Aluminum's resistance per circular mil against copper's, 21.2 ÷ 12.9",
          "value": 1.643410852713178
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "6 AWG copper needs 3 AWG aluminum",
      "inputs": {
        "copperSize": "6"
      },
      "expected": 52.62,
      "toleranceDecimalPlaces": 6,
      "unit": "kcmil (3 AWG)",
      "confidence": "high",
      "steps": [
        {
          "label": "Copper conductor area (kcmil)",
          "value": 26.24
        },
        {
          "label": "Aluminum area for equal resistance (kcmil)",
          "value": 43.12310077519379
        },
        {
          "label": "The same area in mm²",
          "value": 21.850797684665796,
          "unit": "mm²"
        },
        {
          "label": "This aluminum size's resistance against the copper's (%)",
          "value": 81.95192089546521
        },
        {
          "label": "The size below it, 4 AWG: area (kcmil)",
          "value": 41.74
        },
        {
          "label": "The size below it: resistance against the copper's (%)",
          "value": 103.31360990702873
        },
        {
          "label": "Aluminum's resistance per circular mil against copper's, 21.2 ÷ 12.9",
          "value": 1.643410852713178
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "400 kcmil copper needs 750 kcmil aluminum on resistance",
      "inputs": {
        "copperSize": "400"
      },
      "expected": 750,
      "toleranceDecimalPlaces": 6,
      "unit": "kcmil",
      "confidence": "high",
      "steps": [
        {
          "label": "Copper conductor area (kcmil)",
          "value": 400
        },
        {
          "label": "Aluminum area for equal resistance (kcmil)",
          "value": 657.3643410852712
        },
        {
          "label": "The same area in mm²",
          "value": 333.0914281199054,
          "unit": "mm²"
        },
        {
          "label": "This aluminum size's resistance against the copper's (%)",
          "value": 87.64857881136949
        },
        {
          "label": "The size below it, 600 kcmil: area (kcmil)",
          "value": 600
        },
        {
          "label": "The size below it: resistance against the copper's (%)",
          "value": 109.56072351421187
        },
        {
          "label": "Aluminum's resistance per circular mil against copper's, 21.2 ÷ 12.9",
          "value": 1.643410852713178
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "1,000 kcmil copper has no single aluminum equal in the list",
      "inputs": {
        "copperSize": "1000"
      },
      "expected": 0,
      "toleranceDecimalPlaces": 6,
      "unit": "kcmil",
      "confidence": "low",
      "steps": [
        {
          "label": "Copper conductor area (kcmil)",
          "value": 1000
        },
        {
          "label": "Aluminum area for equal resistance (kcmil)",
          "value": 1643.4108527131782
        },
        {
          "label": "The same area in mm²",
          "value": 832.7285702997635,
          "unit": "mm²"
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "a UK reader's opening: 16 mm² copper needs 35 mm² aluminium",
      "inputs": {
        "copperSize": "16mm2"
      },
      "expected": 35,
      "toleranceDecimalPlaces": 6,
      "unit": "mm²",
      "confidence": "high",
      "steps": [
        {
          "label": "Copper conductor resistance at 20 °C (68 °F), Ω/km",
          "value": 1.15
        },
        {
          "label": "This aluminium size's resistance at 20 °C (68 °F), Ω/km",
          "value": 0.868
        },
        {
          "label": "This aluminium size's resistance against the copper's (%)",
          "value": 75.47826086956523
        },
        {
          "label": "The size below it (mm²)",
          "value": 25,
          "unit": "mm²"
        },
        {
          "label": "The size below it: resistance against the copper's (%)",
          "value": 104.34782608695652
        },
        {
          "label": "Aluminium area against copper area",
          "value": 2.1875
        }
      ],
      "basis": "cited",
      "sourceIndex": 1
    },
    {
      "name": "6 mm² copper and 10 mm² aluminium are equal at 3.08 Ω/km (0.939 Ω per 1,000 ft)",
      "inputs": {
        "copperSize": "6mm2"
      },
      "expected": 10,
      "toleranceDecimalPlaces": 6,
      "unit": "mm²",
      "confidence": "high",
      "steps": [
        {
          "label": "Copper conductor resistance at 20 °C (68 °F), Ω/km",
          "value": 3.08
        },
        {
          "label": "This aluminium size's resistance at 20 °C (68 °F), Ω/km",
          "value": 3.08
        },
        {
          "label": "This aluminium size's resistance against the copper's (%)",
          "value": 100
        },
        {
          "label": "Aluminium area against copper area",
          "value": 1.6666666666666667
        }
      ],
      "basis": "cited",
      "sourceIndex": 1
    },
    {
      "name": "150 mm² copper needs 300 mm² aluminium: 240 mm² is 0.8% over",
      "inputs": {
        "copperSize": "150mm2"
      },
      "expected": 300,
      "toleranceDecimalPlaces": 6,
      "unit": "mm²",
      "confidence": "high",
      "steps": [
        {
          "label": "Copper conductor resistance at 20 °C (68 °F), Ω/km",
          "value": 0.124
        },
        {
          "label": "This aluminium size's resistance at 20 °C (68 °F), Ω/km",
          "value": 0.1
        },
        {
          "label": "This aluminium size's resistance against the copper's (%)",
          "value": 80.64516129032259
        },
        {
          "label": "The size below it (mm²)",
          "value": 240,
          "unit": "mm²"
        },
        {
          "label": "The size below it: resistance against the copper's (%)",
          "value": 100.80645161290323
        },
        {
          "label": "Aluminium area against copper area",
          "value": 2
        }
      ],
      "basis": "cited",
      "sourceIndex": 1
    },
    {
      "name": "14 copper: 10.38 kcmil of aluminum",
      "inputs": {
        "copperSize": "14"
      },
      "expected": 10.38,
      "toleranceDecimalPlaces": 6,
      "unit": "kcmil (10 AWG)",
      "confidence": "high",
      "steps": [
        {
          "label": "Copper conductor area (kcmil)",
          "value": 4.11
        },
        {
          "label": "Aluminum area for equal resistance (kcmil)",
          "value": 6.754418604651162
        },
        {
          "label": "The same area in mm²",
          "value": 3.422514423932028,
          "unit": "mm²"
        },
        {
          "label": "This aluminum size's resistance against the copper's (%)",
          "value": 65.07147017968364
        },
        {
          "label": "The size below it, 12 AWG: area (kcmil)",
          "value": 6.53
        },
        {
          "label": "The size below it: resistance against the copper's (%)",
          "value": 103.43673207735318
        },
        {
          "label": "Aluminum's resistance per circular mil against copper's, 21.2 ÷ 12.9",
          "value": 1.643410852713178
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "10 copper: 26.24 kcmil of aluminum",
      "inputs": {
        "copperSize": "10"
      },
      "expected": 26.24,
      "toleranceDecimalPlaces": 6,
      "unit": "kcmil (6 AWG)",
      "confidence": "high",
      "steps": [
        {
          "label": "Copper conductor area (kcmil)",
          "value": 10.38
        },
        {
          "label": "Aluminum area for equal resistance (kcmil)",
          "value": 17.05860465116279
        },
        {
          "label": "The same area in mm²",
          "value": 8.643722559711547,
          "unit": "mm²"
        },
        {
          "label": "This aluminum size's resistance against the copper's (%)",
          "value": 65.00992626205331
        },
        {
          "label": "The size below it, 8 AWG: area (kcmil)",
          "value": 16.51
        },
        {
          "label": "The size below it: resistance against the copper's (%)",
          "value": 103.32286281746089
        },
        {
          "label": "Aluminum's resistance per circular mil against copper's, 21.2 ÷ 12.9",
          "value": 1.643410852713178
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "8 copper: 41.74 kcmil of aluminum",
      "inputs": {
        "copperSize": "8"
      },
      "expected": 41.74,
      "toleranceDecimalPlaces": 6,
      "unit": "kcmil (4 AWG)",
      "confidence": "high",
      "steps": [
        {
          "label": "Copper conductor area (kcmil)",
          "value": 16.51
        },
        {
          "label": "Aluminum area for equal resistance (kcmil)",
          "value": 27.13271317829457
        },
        {
          "label": "The same area in mm²",
          "value": 13.748348695649096,
          "unit": "mm²"
        },
        {
          "label": "This aluminum size's resistance against the copper's (%)",
          "value": 65.00410440415565
        },
        {
          "label": "The size below it, 6 AWG: area (kcmil)",
          "value": 26.24
        },
        {
          "label": "The size below it: resistance against the copper's (%)",
          "value": 103.40210814898845
        },
        {
          "label": "Aluminum's resistance per circular mil against copper's, 21.2 ÷ 12.9",
          "value": 1.643410852713178
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "4 copper: 83.69 kcmil of aluminum",
      "inputs": {
        "copperSize": "4"
      },
      "expected": 83.69,
      "toleranceDecimalPlaces": 6,
      "unit": "kcmil (1 AWG)",
      "confidence": "high",
      "steps": [
        {
          "label": "Copper conductor area (kcmil)",
          "value": 41.74
        },
        {
          "label": "Aluminum area for equal resistance (kcmil)",
          "value": 68.59596899224806
        },
        {
          "label": "The same area in mm²",
          "value": 34.75809052431213,
          "unit": "mm²"
        },
        {
          "label": "This aluminum size's resistance against the copper's (%)",
          "value": 81.96435534980053
        },
        {
          "label": "The size below it, 2 AWG: area (kcmil)",
          "value": 66.36
        },
        {
          "label": "The size below it: resistance against the copper's (%)",
          "value": 103.36945297204349
        },
        {
          "label": "Aluminum's resistance per circular mil against copper's, 21.2 ÷ 12.9",
          "value": 1.643410852713178
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "3 copper: 105.6 kcmil of aluminum",
      "inputs": {
        "copperSize": "3"
      },
      "expected": 105.6,
      "toleranceDecimalPlaces": 6,
      "unit": "kcmil (1/0 AWG)",
      "confidence": "high",
      "steps": [
        {
          "label": "Copper conductor area (kcmil)",
          "value": 52.62
        },
        {
          "label": "Aluminum area for equal resistance (kcmil)",
          "value": 86.47627906976743
        },
        {
          "label": "The same area in mm²",
          "value": 43.81817736917356,
          "unit": "mm²"
        },
        {
          "label": "This aluminum size's resistance against the copper's (%)",
          "value": 81.89041578576462
        },
        {
          "label": "The size below it, 1 AWG: area (kcmil)",
          "value": 83.69
        },
        {
          "label": "The size below it: resistance against the copper's (%)",
          "value": 103.32928554160286
        },
        {
          "label": "Aluminum's resistance per circular mil against copper's, 21.2 ÷ 12.9",
          "value": 1.643410852713178
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "2 copper: 133.1 kcmil of aluminum",
      "inputs": {
        "copperSize": "2"
      },
      "expected": 133.1,
      "toleranceDecimalPlaces": 6,
      "unit": "kcmil (2/0 AWG)",
      "confidence": "high",
      "steps": [
        {
          "label": "Copper conductor area (kcmil)",
          "value": 66.36
        },
        {
          "label": "Aluminum area for equal resistance (kcmil)",
          "value": 109.0567441860465
        },
        {
          "label": "The same area in mm²",
          "value": 55.25986792509231,
          "unit": "mm²"
        },
        {
          "label": "This aluminum size's resistance against the copper's (%)",
          "value": 81.93594604511382
        },
        {
          "label": "The size below it, 1/0 AWG: area (kcmil)",
          "value": 105.6
        },
        {
          "label": "The size below it: resistance against the copper's (%)",
          "value": 103.27343199436223
        },
        {
          "label": "Aluminum's resistance per circular mil against copper's, 21.2 ÷ 12.9",
          "value": 1.643410852713178
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "1 copper: 167.8 kcmil of aluminum",
      "inputs": {
        "copperSize": "1"
      },
      "expected": 167.8,
      "toleranceDecimalPlaces": 6,
      "unit": "kcmil (3/0 AWG)",
      "confidence": "high",
      "steps": [
        {
          "label": "Copper conductor area (kcmil)",
          "value": 83.69
        },
        {
          "label": "Aluminum area for equal resistance (kcmil)",
          "value": 137.53705426356586
        },
        {
          "label": "The same area in mm²",
          "value": 69.6910540483872,
          "unit": "mm²"
        },
        {
          "label": "This aluminum size's resistance against the copper's (%)",
          "value": 81.9648714323992
        },
        {
          "label": "The size below it, 2/0 AWG: area (kcmil)",
          "value": 133.1
        },
        {
          "label": "The size below it: resistance against the copper's (%)",
          "value": 103.33362454062049
        },
        {
          "label": "Aluminum's resistance per circular mil against copper's, 21.2 ÷ 12.9",
          "value": 1.643410852713178
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "1/0 copper: 211.6 kcmil of aluminum",
      "inputs": {
        "copperSize": "1/0"
      },
      "expected": 211.6,
      "toleranceDecimalPlaces": 6,
      "unit": "kcmil (4/0 AWG)",
      "confidence": "high",
      "steps": [
        {
          "label": "Copper conductor area (kcmil)",
          "value": 105.6
        },
        {
          "label": "Aluminum area for equal resistance (kcmil)",
          "value": 173.5441860465116
        },
        {
          "label": "The same area in mm²",
          "value": 87.93613702365504,
          "unit": "mm²"
        },
        {
          "label": "This aluminum size's resistance against the copper's (%)",
          "value": 82.01521079702817
        },
        {
          "label": "The size below it, 3/0 AWG: area (kcmil)",
          "value": 167.8
        },
        {
          "label": "The size below it: resistance against the copper's (%)",
          "value": 103.42323363916066
        },
        {
          "label": "Aluminum's resistance per circular mil against copper's, 21.2 ÷ 12.9",
          "value": 1.643410852713178
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "3/0 copper: 300 kcmil of aluminum",
      "inputs": {
        "copperSize": "3/0"
      },
      "expected": 300,
      "toleranceDecimalPlaces": 6,
      "unit": "kcmil",
      "confidence": "high",
      "steps": [
        {
          "label": "Copper conductor area (kcmil)",
          "value": 167.8
        },
        {
          "label": "Aluminum area for equal resistance (kcmil)",
          "value": 275.76434108527127
        },
        {
          "label": "The same area in mm²",
          "value": 139.7318540963003,
          "unit": "mm²"
        },
        {
          "label": "This aluminum size's resistance against the copper's (%)",
          "value": 91.92144702842376
        },
        {
          "label": "The size below it, 250 kcmil: area (kcmil)",
          "value": 250
        },
        {
          "label": "The size below it: resistance against the copper's (%)",
          "value": 110.3057364341085
        },
        {
          "label": "Aluminum's resistance per circular mil against copper's, 21.2 ÷ 12.9",
          "value": 1.643410852713178
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "4/0 copper: 350 kcmil of aluminum",
      "inputs": {
        "copperSize": "4/0"
      },
      "expected": 350,
      "toleranceDecimalPlaces": 6,
      "unit": "kcmil",
      "confidence": "high",
      "steps": [
        {
          "label": "Copper conductor area (kcmil)",
          "value": 211.6
        },
        {
          "label": "Aluminum area for equal resistance (kcmil)",
          "value": 347.74573643410844
        },
        {
          "label": "The same area in mm²",
          "value": 176.20536547542994,
          "unit": "mm²"
        },
        {
          "label": "This aluminum size's resistance against the copper's (%)",
          "value": 99.35592469545956
        },
        {
          "label": "The size below it, 300 kcmil: area (kcmil)",
          "value": 300
        },
        {
          "label": "The size below it: resistance against the copper's (%)",
          "value": 115.91524547803616
        },
        {
          "label": "Aluminum's resistance per circular mil against copper's, 21.2 ÷ 12.9",
          "value": 1.643410852713178
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "250 copper: 500 kcmil of aluminum",
      "inputs": {
        "copperSize": "250"
      },
      "expected": 500,
      "toleranceDecimalPlaces": 6,
      "unit": "kcmil",
      "confidence": "high",
      "steps": [
        {
          "label": "Copper conductor area (kcmil)",
          "value": 250
        },
        {
          "label": "Aluminum area for equal resistance (kcmil)",
          "value": 410.85271317829455
        },
        {
          "label": "The same area in mm²",
          "value": 208.18214257494088,
          "unit": "mm²"
        },
        {
          "label": "This aluminum size's resistance against the copper's (%)",
          "value": 82.1705426356589
        },
        {
          "label": "The size below it, 400 kcmil: area (kcmil)",
          "value": 400
        },
        {
          "label": "The size below it: resistance against the copper's (%)",
          "value": 102.71317829457362
        },
        {
          "label": "Aluminum's resistance per circular mil against copper's, 21.2 ÷ 12.9",
          "value": 1.643410852713178
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "300 copper: 500 kcmil of aluminum",
      "inputs": {
        "copperSize": "300"
      },
      "expected": 500,
      "toleranceDecimalPlaces": 6,
      "unit": "kcmil",
      "confidence": "high",
      "steps": [
        {
          "label": "Copper conductor area (kcmil)",
          "value": 300
        },
        {
          "label": "Aluminum area for equal resistance (kcmil)",
          "value": 493.0232558139534
        },
        {
          "label": "The same area in mm²",
          "value": 249.81857108992907,
          "unit": "mm²"
        },
        {
          "label": "This aluminum size's resistance against the copper's (%)",
          "value": 98.60465116279067
        },
        {
          "label": "The size below it, 400 kcmil: area (kcmil)",
          "value": 400
        },
        {
          "label": "The size below it: resistance against the copper's (%)",
          "value": 123.25581395348834
        },
        {
          "label": "Aluminum's resistance per circular mil against copper's, 21.2 ÷ 12.9",
          "value": 1.643410852713178
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "350 copper: 600 kcmil of aluminum",
      "inputs": {
        "copperSize": "350"
      },
      "expected": 600,
      "toleranceDecimalPlaces": 6,
      "unit": "kcmil",
      "confidence": "high",
      "steps": [
        {
          "label": "Copper conductor area (kcmil)",
          "value": 350
        },
        {
          "label": "Aluminum area for equal resistance (kcmil)",
          "value": 575.1937984496124
        },
        {
          "label": "The same area in mm²",
          "value": 291.45499960491725,
          "unit": "mm²"
        },
        {
          "label": "This aluminum size's resistance against the copper's (%)",
          "value": 95.86563307493539
        },
        {
          "label": "The size below it, 500 kcmil: area (kcmil)",
          "value": 500
        },
        {
          "label": "The size below it: resistance against the copper's (%)",
          "value": 115.03875968992247
        },
        {
          "label": "Aluminum's resistance per circular mil against copper's, 21.2 ÷ 12.9",
          "value": 1.643410852713178
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "500 copper: 1000 kcmil of aluminum",
      "inputs": {
        "copperSize": "500"
      },
      "expected": 1000,
      "toleranceDecimalPlaces": 6,
      "unit": "kcmil",
      "confidence": "high",
      "steps": [
        {
          "label": "Copper conductor area (kcmil)",
          "value": 500
        },
        {
          "label": "Aluminum area for equal resistance (kcmil)",
          "value": 821.7054263565891
        },
        {
          "label": "The same area in mm²",
          "value": 416.36428514988177,
          "unit": "mm²"
        },
        {
          "label": "This aluminum size's resistance against the copper's (%)",
          "value": 82.1705426356589
        },
        {
          "label": "The size below it, 750 kcmil: area (kcmil)",
          "value": 750
        },
        {
          "label": "The size below it: resistance against the copper's (%)",
          "value": 109.56072351421187
        },
        {
          "label": "Aluminum's resistance per circular mil against copper's, 21.2 ÷ 12.9",
          "value": 1.643410852713178
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "600 copper: 1000 kcmil of aluminum",
      "inputs": {
        "copperSize": "600"
      },
      "expected": 1000,
      "toleranceDecimalPlaces": 6,
      "unit": "kcmil",
      "confidence": "high",
      "steps": [
        {
          "label": "Copper conductor area (kcmil)",
          "value": 600
        },
        {
          "label": "Aluminum area for equal resistance (kcmil)",
          "value": 986.0465116279069
        },
        {
          "label": "The same area in mm²",
          "value": 499.63714217985813,
          "unit": "mm²"
        },
        {
          "label": "This aluminum size's resistance against the copper's (%)",
          "value": 98.60465116279067
        },
        {
          "label": "The size below it, 750 kcmil: area (kcmil)",
          "value": 750
        },
        {
          "label": "The size below it: resistance against the copper's (%)",
          "value": 131.47286821705424
        },
        {
          "label": "Aluminum's resistance per circular mil against copper's, 21.2 ÷ 12.9",
          "value": 1.643410852713178
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "750 copper: no single aluminum equal",
      "inputs": {
        "copperSize": "750"
      },
      "expected": 0,
      "toleranceDecimalPlaces": 6,
      "unit": "kcmil",
      "confidence": "low",
      "steps": [
        {
          "label": "Copper conductor area (kcmil)",
          "value": 750
        },
        {
          "label": "Aluminum area for equal resistance (kcmil)",
          "value": 1232.5581395348836
        },
        {
          "label": "The same area in mm²",
          "value": 624.5464277248227,
          "unit": "mm²"
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "1.5 mm² copper: 10 mm² of aluminium",
      "inputs": {
        "copperSize": "1.5mm2"
      },
      "expected": 10,
      "toleranceDecimalPlaces": 6,
      "unit": "mm²",
      "confidence": "medium",
      "steps": [
        {
          "label": "Copper conductor resistance at 20 °C (68 °F), Ω/km",
          "value": 12.1
        },
        {
          "label": "This aluminium size's resistance at 20 °C (68 °F), Ω/km",
          "value": 3.08
        },
        {
          "label": "This aluminium size's resistance against the copper's (%)",
          "value": 25.454545454545457
        },
        {
          "label": "Aluminium area against copper area",
          "value": 6.666666666666667
        }
      ],
      "basis": "cited",
      "sourceIndex": 1
    },
    {
      "name": "2.5 mm² copper: 10 mm² of aluminium",
      "inputs": {
        "copperSize": "2.5mm2"
      },
      "expected": 10,
      "toleranceDecimalPlaces": 6,
      "unit": "mm²",
      "confidence": "medium",
      "steps": [
        {
          "label": "Copper conductor resistance at 20 °C (68 °F), Ω/km",
          "value": 7.41
        },
        {
          "label": "This aluminium size's resistance at 20 °C (68 °F), Ω/km",
          "value": 3.08
        },
        {
          "label": "This aluminium size's resistance against the copper's (%)",
          "value": 41.56545209176788
        },
        {
          "label": "Aluminium area against copper area",
          "value": 4
        }
      ],
      "basis": "cited",
      "sourceIndex": 1
    },
    {
      "name": "4 mm² copper: 10 mm² of aluminium",
      "inputs": {
        "copperSize": "4mm2"
      },
      "expected": 10,
      "toleranceDecimalPlaces": 6,
      "unit": "mm²",
      "confidence": "medium",
      "steps": [
        {
          "label": "Copper conductor resistance at 20 °C (68 °F), Ω/km",
          "value": 4.61
        },
        {
          "label": "This aluminium size's resistance at 20 °C (68 °F), Ω/km",
          "value": 3.08
        },
        {
          "label": "This aluminium size's resistance against the copper's (%)",
          "value": 66.81127982646422
        },
        {
          "label": "Aluminium area against copper area",
          "value": 2.5
        }
      ],
      "basis": "cited",
      "sourceIndex": 1
    },
    {
      "name": "10 mm² copper: 25 mm² of aluminium",
      "inputs": {
        "copperSize": "10mm2"
      },
      "expected": 25,
      "toleranceDecimalPlaces": 6,
      "unit": "mm²",
      "confidence": "high",
      "steps": [
        {
          "label": "Copper conductor resistance at 20 °C (68 °F), Ω/km",
          "value": 1.83
        },
        {
          "label": "This aluminium size's resistance at 20 °C (68 °F), Ω/km",
          "value": 1.2
        },
        {
          "label": "This aluminium size's resistance against the copper's (%)",
          "value": 65.57377049180327
        },
        {
          "label": "The size below it (mm²)",
          "value": 16,
          "unit": "mm²"
        },
        {
          "label": "The size below it: resistance against the copper's (%)",
          "value": 104.37158469945354
        },
        {
          "label": "Aluminium area against copper area",
          "value": 2.5
        }
      ],
      "basis": "cited",
      "sourceIndex": 1
    },
    {
      "name": "25 mm² copper: 50 mm² of aluminium",
      "inputs": {
        "copperSize": "25mm2"
      },
      "expected": 50,
      "toleranceDecimalPlaces": 6,
      "unit": "mm²",
      "confidence": "high",
      "steps": [
        {
          "label": "Copper conductor resistance at 20 °C (68 °F), Ω/km",
          "value": 0.727
        },
        {
          "label": "This aluminium size's resistance at 20 °C (68 °F), Ω/km",
          "value": 0.641
        },
        {
          "label": "This aluminium size's resistance against the copper's (%)",
          "value": 88.17056396148556
        },
        {
          "label": "The size below it (mm²)",
          "value": 35,
          "unit": "mm²"
        },
        {
          "label": "The size below it: resistance against the copper's (%)",
          "value": 119.39477303988997
        },
        {
          "label": "Aluminium area against copper area",
          "value": 2
        }
      ],
      "basis": "cited",
      "sourceIndex": 1
    },
    {
      "name": "35 mm² copper: 70 mm² of aluminium",
      "inputs": {
        "copperSize": "35mm2"
      },
      "expected": 70,
      "toleranceDecimalPlaces": 6,
      "unit": "mm²",
      "confidence": "high",
      "steps": [
        {
          "label": "Copper conductor resistance at 20 °C (68 °F), Ω/km",
          "value": 0.524
        },
        {
          "label": "This aluminium size's resistance at 20 °C (68 °F), Ω/km",
          "value": 0.443
        },
        {
          "label": "This aluminium size's resistance against the copper's (%)",
          "value": 84.54198473282443
        },
        {
          "label": "The size below it (mm²)",
          "value": 50,
          "unit": "mm²"
        },
        {
          "label": "The size below it: resistance against the copper's (%)",
          "value": 122.32824427480915
        },
        {
          "label": "Aluminium area against copper area",
          "value": 2
        }
      ],
      "basis": "cited",
      "sourceIndex": 1
    },
    {
      "name": "50 mm² copper: 95 mm² of aluminium",
      "inputs": {
        "copperSize": "50mm2"
      },
      "expected": 95,
      "toleranceDecimalPlaces": 6,
      "unit": "mm²",
      "confidence": "high",
      "steps": [
        {
          "label": "Copper conductor resistance at 20 °C (68 °F), Ω/km",
          "value": 0.387
        },
        {
          "label": "This aluminium size's resistance at 20 °C (68 °F), Ω/km",
          "value": 0.32
        },
        {
          "label": "This aluminium size's resistance against the copper's (%)",
          "value": 82.68733850129199
        },
        {
          "label": "The size below it (mm²)",
          "value": 70,
          "unit": "mm²"
        },
        {
          "label": "The size below it: resistance against the copper's (%)",
          "value": 114.47028423772609
        },
        {
          "label": "Aluminium area against copper area",
          "value": 1.9
        }
      ],
      "basis": "cited",
      "sourceIndex": 1
    },
    {
      "name": "70 mm² copper: 120 mm² of aluminium",
      "inputs": {
        "copperSize": "70mm2"
      },
      "expected": 120,
      "toleranceDecimalPlaces": 6,
      "unit": "mm²",
      "confidence": "high",
      "steps": [
        {
          "label": "Copper conductor resistance at 20 °C (68 °F), Ω/km",
          "value": 0.268
        },
        {
          "label": "This aluminium size's resistance at 20 °C (68 °F), Ω/km",
          "value": 0.253
        },
        {
          "label": "This aluminium size's resistance against the copper's (%)",
          "value": 94.40298507462687
        },
        {
          "label": "The size below it (mm²)",
          "value": 95,
          "unit": "mm²"
        },
        {
          "label": "The size below it: resistance against the copper's (%)",
          "value": 119.40298507462686
        },
        {
          "label": "Aluminium area against copper area",
          "value": 1.7142857142857142
        }
      ],
      "basis": "cited",
      "sourceIndex": 1
    },
    {
      "name": "95 mm² copper: 185 mm² of aluminium",
      "inputs": {
        "copperSize": "95mm2"
      },
      "expected": 185,
      "toleranceDecimalPlaces": 6,
      "unit": "mm²",
      "confidence": "high",
      "steps": [
        {
          "label": "Copper conductor resistance at 20 °C (68 °F), Ω/km",
          "value": 0.193
        },
        {
          "label": "This aluminium size's resistance at 20 °C (68 °F), Ω/km",
          "value": 0.164
        },
        {
          "label": "This aluminium size's resistance against the copper's (%)",
          "value": 84.97409326424871
        },
        {
          "label": "The size below it (mm²)",
          "value": 150,
          "unit": "mm²"
        },
        {
          "label": "The size below it: resistance against the copper's (%)",
          "value": 106.73575129533678
        },
        {
          "label": "Aluminium area against copper area",
          "value": 1.9473684210526316
        }
      ],
      "basis": "cited",
      "sourceIndex": 1
    },
    {
      "name": "120 mm² copper: 240 mm² of aluminium",
      "inputs": {
        "copperSize": "120mm2"
      },
      "expected": 240,
      "toleranceDecimalPlaces": 6,
      "unit": "mm²",
      "confidence": "high",
      "steps": [
        {
          "label": "Copper conductor resistance at 20 °C (68 °F), Ω/km",
          "value": 0.153
        },
        {
          "label": "This aluminium size's resistance at 20 °C (68 °F), Ω/km",
          "value": 0.125
        },
        {
          "label": "This aluminium size's resistance against the copper's (%)",
          "value": 81.69934640522875
        },
        {
          "label": "The size below it (mm²)",
          "value": 185,
          "unit": "mm²"
        },
        {
          "label": "The size below it: resistance against the copper's (%)",
          "value": 107.18954248366013
        },
        {
          "label": "Aluminium area against copper area",
          "value": 2
        }
      ],
      "basis": "cited",
      "sourceIndex": 1
    },
    {
      "name": "185 mm² copper: 400 mm² of aluminium",
      "inputs": {
        "copperSize": "185mm2"
      },
      "expected": 400,
      "toleranceDecimalPlaces": 6,
      "unit": "mm²",
      "confidence": "high",
      "steps": [
        {
          "label": "Copper conductor resistance at 20 °C (68 °F), Ω/km",
          "value": 0.0991
        },
        {
          "label": "This aluminium size's resistance at 20 °C (68 °F), Ω/km",
          "value": 0.0778
        },
        {
          "label": "This aluminium size's resistance against the copper's (%)",
          "value": 78.50655903128153
        },
        {
          "label": "The size below it (mm²)",
          "value": 300,
          "unit": "mm²"
        },
        {
          "label": "The size below it: resistance against the copper's (%)",
          "value": 100.90817356205855
        },
        {
          "label": "Aluminium area against copper area",
          "value": 2.1621621621621623
        }
      ],
      "basis": "cited",
      "sourceIndex": 1
    },
    {
      "name": "240 mm² copper: 500 mm² of aluminium",
      "inputs": {
        "copperSize": "240mm2"
      },
      "expected": 500,
      "toleranceDecimalPlaces": 6,
      "unit": "mm²",
      "confidence": "high",
      "steps": [
        {
          "label": "Copper conductor resistance at 20 °C (68 °F), Ω/km",
          "value": 0.0754
        },
        {
          "label": "This aluminium size's resistance at 20 °C (68 °F), Ω/km",
          "value": 0.0605
        },
        {
          "label": "This aluminium size's resistance against the copper's (%)",
          "value": 80.23872679045093
        },
        {
          "label": "The size below it (mm²)",
          "value": 400,
          "unit": "mm²"
        },
        {
          "label": "The size below it: resistance against the copper's (%)",
          "value": 103.18302387267903
        },
        {
          "label": "Aluminium area against copper area",
          "value": 2.0833333333333335
        }
      ],
      "basis": "cited",
      "sourceIndex": 1
    },
    {
      "name": "300 mm² copper: 630 mm² of aluminium",
      "inputs": {
        "copperSize": "300mm2"
      },
      "expected": 630,
      "toleranceDecimalPlaces": 6,
      "unit": "mm²",
      "confidence": "high",
      "steps": [
        {
          "label": "Copper conductor resistance at 20 °C (68 °F), Ω/km",
          "value": 0.0601
        },
        {
          "label": "This aluminium size's resistance at 20 °C (68 °F), Ω/km",
          "value": 0.0469
        },
        {
          "label": "This aluminium size's resistance against the copper's (%)",
          "value": 78.03660565723793
        },
        {
          "label": "The size below it (mm²)",
          "value": 500,
          "unit": "mm²"
        },
        {
          "label": "The size below it: resistance against the copper's (%)",
          "value": 100.66555740432612
        },
        {
          "label": "Aluminium area against copper area",
          "value": 2.1
        }
      ],
      "basis": "cited",
      "sourceIndex": 1
    }
  ]
}