  "version": "v1",
  "source": "https://craftquantities.com",
  "licence": "CC BY 4.0",
  "licenceUrl": "https://creativecommons.org/licenses/by/4.0/",
  "attribution": "Craft Quantities — craftquantities.com",
  "documentation": "https://craftquantities.com/api/",
  "versioning": "Fields are added, never removed or repurposed, within a version. A breaking change becomes /api/v2/ and v1 keeps being built.",
  "slug": "conduit-fill-calculator",
  "category": "electrical",
  "title": "Conduit Fill Calculator",
  "description": "Find the maximum number of THHN conductors that fit in a conduit, per the NEC's 40% fill rule.",
  "url": "https://craftquantities.com/calculators/electrical/conduit-fill-calculator/",
  "json": "https://craftquantities.com/api/v1/calculators/conduit-fill-calculator.json",
  "inputCount": 2,
  "testCaseCount": 5,
  "sourceCount": 3,
  "lastVerified": "2026-09-02",
  "translations": {
    "es-US": "https://craftquantities.com/es/calculators/electrical/conduit-fill-calculator/"
  },
  "citation": {
    "author": "Craft Quantities",
    "title": "Conduit Fill Calculator",
    "version": "1.0.1",
    "sourcesChecked": "2026-09-02",
    "url": "https://craftquantities.com/calculators/electrical/conduit-fill-calculator/",
    "accessDate": null,
    "accessDateNote": "Add the date you retrieved this. It is deliberately absent: a static file cannot know when you read it, and the build date would be wrong.",
    "permanentVersionedUrl": null,
    "permanentVersionedUrlNote": "Not offered. This site keeps no archive of previous builds, so any such URL would resolve to the current page or to nothing. The version and sourcesChecked fields identify the calculation instead.",
    "formats": {
      "plain": "Craft Quantities. Conduit Fill Calculator. Version 1.0.1. Sources checked 2026-09-02. https://craftquantities.com/calculators/electrical/conduit-fill-calculator/",
      "apa": "Craft Quantities. (2026). Conduit Fill Calculator (Version 1.0.1) [Web calculator]. Retrieved from https://craftquantities.com/calculators/electrical/conduit-fill-calculator/",
      "harvard": "Craft Quantities (2026) Conduit Fill Calculator (Version 1.0.1). Available at: https://craftquantities.com/calculators/electrical/conduit-fill-calculator/",
      "bibtex": "@misc{craftquantities-calculators-electrical-conduit-fill-calculator,\n  author       = {{Craft Quantities}},\n  title        = {Conduit Fill Calculator},\n  version      = {1.0.1},\n  year         = {2026},\n  howpublished = {\\url{https://craftquantities.com/calculators/electrical/conduit-fill-calculator/}},\n}"
    }
  },
  "inputs": [
    {
      "id": "wireGauge",
      "label": "Conductor Size (THHN)",
      "type": "select",
      "defaultValue": "12",
      "options": [
        {
          "value": "14",
          "label": "14 AWG"
        },
        {
          "value": "12",
          "label": "12 AWG"
        },
        {
          "value": "10",
          "label": "10 AWG"
        },
        {
          "value": "8",
          "label": "8 AWG"
        }
      ],
      "help": "The gauge of the conductors being pulled through the conduit."
    },
    {
      "id": "conduitSize",
      "label": "Conduit (EMT) Size",
      "type": "select",
      "defaultValue": "0.75",
      "options": [
        {
          "value": "0.5",
          "label": "1/2 in"
        },
        {
          "value": "0.75",
          "label": "3/4 in"
        },
        {
          "value": "1",
          "label": "1 in"
        },
        {
          "value": "1.25",
          "label": "1-1/4 in"
        },
        {
          "value": "1.5",
          "label": "1-1/2 in"
        },
        {
          "value": "2",
          "label": "2 in"
        }
      ],
      "help": "The trade size of the EMT conduit."
    }
  ],
  "sources": [
    {
      "label": "NEC Chapter 9, Table 1: conduit fill is limited to 40% of internal area for 3 or more conductors"
    },
    {
      "label": "Approximate THHN conductor areas and EMT conduit internal areas, per NEC Chapter 9 tables"
    },
    {
      "label": "NEC Chapter 9, Notes to Tables, Note 7: where all conductors are the same size, a result ending in a decimal of 0.8 or larger is taken to the next whole number"
    }
  ],
  "testCases": [
    {
      "name": "12 AWG in 3/4 in EMT",
      "inputs": {
        "wireGauge": "12",
        "conduitSize": "0.75"
      },
      "expected": 16,
      "toleranceDecimalPlaces": 0,
      "unit": "conductors (maximum)",
      "confidence": "medium",
      "steps": [
        {
          "label": "Available fill area (40% of conduit)",
          "value": 0.21320000000000003,
          "unit": "in²"
        }
      ],
      "basis": "ambiguous"
    },
    {
      "name": "8 AWG in 1 in EMT",
      "inputs": {
        "wireGauge": "8",
        "conduitSize": "1"
      },
      "expected": 9,
      "toleranceDecimalPlaces": 0,
      "unit": "conductors (maximum)",
      "confidence": "medium",
      "steps": [
        {
          "label": "Available fill area (40% of conduit)",
          "value": 0.3456,
          "unit": "in²"
        }
      ],
      "basis": "ambiguous"
    },
    {
      "name": "14 AWG in 3/4 in EMT — Note 7 rounds this one up",
      "inputs": {
        "wireGauge": "14",
        "conduitSize": "0.75"
      },
      "expected": 22,
      "toleranceDecimalPlaces": 0,
      "unit": "conductors (maximum)",
      "confidence": "medium",
      "steps": [
        {
          "label": "Available fill area (40% of conduit)",
          "value": 0.21320000000000003,
          "unit": "in²"
        }
      ],
      "basis": "ambiguous"
    },
    {
      "name": "8 AWG in 3/4 in EMT — the smallest case Note 7 changes",
      "inputs": {
        "wireGauge": "8",
        "conduitSize": "0.75"
      },
      "expected": 6,
      "toleranceDecimalPlaces": 0,
      "unit": "conductors (maximum)",
      "confidence": "medium",
      "steps": [
        {
          "label": "Available fill area (40% of conduit)",
          "value": 0.21320000000000003,
          "unit": "in²"
        }
      ],
      "basis": "ambiguous"
    },
    {
      "name": "12 AWG in 3/4 in EMT — Note 7 must NOT fire here",
      "inputs": {
        "wireGauge": "12",
        "conduitSize": "0.75"
      },
      "expected": 16,
      "toleranceDecimalPlaces": 0,
      "unit": "conductors (maximum)",
      "confidence": "medium",
      "steps": [
        {
          "label": "Available fill area (40% of conduit)",
          "value": 0.21320000000000003,
          "unit": "in²"
        }
      ],
      "basis": "ambiguous"
    }
  ]
}