  "category": "materials-quantities",
  "title": "Feeder Conductor Ampacity Derating Calculator",
  "description": "Calculate a conductor's derated ampacity after applying ambient temperature and conductor-count correction factors.",
  "url": "https://craftquantities.com/calculators/materials-quantities/conductor-ampacity-derating-calculator/",
  "json": "https://craftquantities.com/api/v1/calculators/conductor-ampacity-derating-calculator.json",
  "inputCount": 3,
  "testCaseCount": 2,
  "sourceCount": 1,
  "lastVerified": "2026-09-06",
  "translations": {
    "es-US": "https://craftquantities.com/es/calculators/materials-quantities/conductor-ampacity-derating-calculator/"
  },
  "citation": {
    "author": "Craft Quantities",
    "title": "Feeder Conductor Ampacity Derating Calculator",
    "version": "1.0.1",
    "sourcesChecked": "2026-09-06",
    "url": "https://craftquantities.com/calculators/materials-quantities/conductor-ampacity-derating-calculator/",
    "accessDate": null,
    "accessDateNote": "Add the date you retrieved this. It is deliberately absent: a static file cannot know when you read it, and the build date would be wrong.",
    "permanentVersionedUrl": null,
    "permanentVersionedUrlNote": "Not offered. This site keeps no archive of previous builds, so any such URL would resolve to the current page or to nothing. The version and sourcesChecked fields identify the calculation instead.",
    "formats": {
      "plain": "Craft Quantities. Feeder Conductor Ampacity Derating Calculator. Version 1.0.1. Sources checked 2026-09-06. https://craftquantities.com/calculators/materials-quantities/conductor-ampacity-derating-calculator/",
      "apa": "Craft Quantities. (2026). Feeder Conductor Ampacity Derating Calculator (Version 1.0.1) [Web calculator]. Retrieved from https://craftquantities.com/calculators/materials-quantities/conductor-ampacity-derating-calculator/",
      "harvard": "Craft Quantities (2026) Feeder Conductor Ampacity Derating Calculator (Version 1.0.1). Available at: https://craftquantities.com/calculators/materials-quantities/conductor-ampacity-derating-calculator/",
      "bibtex": "@misc{craftquantities-calculators-materials-quantities-conductor-ampacity-derating-calculator,\n  author       = {{Craft Quantities}},\n  title        = {Feeder Conductor Ampacity Derating Calculator},\n  version      = {1.0.1},\n  year         = {2026},\n  howpublished = {\\url{https://craftquantities.com/calculators/materials-quantities/conductor-ampacity-derating-calculator/}},\n}"
    }
  },
  "inputs": [
    {
      "id": "baseAmpacity",
      "label": "Base Conductor Ampacity (A, from NEC Table 310.16)",
      "type": "number",
      "defaultValue": 130,
      "min": 10,
      "max": 500,
      "step": 5,
      "help": "The conductor's tabulated ampacity before any correction or adjustment factors are applied."
    },
    {
      "id": "tempCorrectionFactor",
      "label": "Ambient Temperature Correction Factor (Per NEC 310.15(B))",
      "type": "number",
      "defaultValue": 0.88,
      "min": 0.5,
      "max": 1.3,
      "step": 0.01,
      "help": "The multiplier for the ambient temperature the conductor will actually operate in, from the applicable NEC temperature correction table."
    },
    {
      "id": "conductorCountFactor",
      "label": "Conductor Count Adjustment Factor (Per NEC Table 310.15(C)(1))",
      "type": "number",
      "defaultValue": 0.8,
      "min": 0.35,
      "max": 1,
      "step": 0.01,
      "help": "The multiplier for the number of current-carrying conductors bundled together in the same raceway or cable."
    }
  ],
  "sources": [
    {
      "label": "Derated ampacity = base conductor ampacity × ambient temperature correction factor × conductor bundling/count adjustment factor, per NEC 310.15(B) temperature correction tables and NEC Table 310.15(C)(1) adjustment factors for more than 3 current-carrying conductors in a raceway"
    }
  ],
  "testCases": [
    {
      "name": "130A base, 0.88 temp factor, 0.8 count factor",
      "inputs": {
        "baseAmpacity": 130,
        "tempCorrectionFactor": 0.88,
        "conductorCountFactor": 0.8
      },
      "expected": 91.52,
      "toleranceDecimalPlaces": 1,
      "unit": "A",
      "confidence": "medium",
      "steps": [],
      "basis": "sole-source",
      "sourceIndex": 0
    },
    {
      "name": "175A base, 0.91 temp factor, 0.7 count factor",
      "inputs": {
        "baseAmpacity": 175,
        "tempCorrectionFactor": 0.91,
        "conductorCountFactor": 0.7
      },
      "expected": 111.48,
      "toleranceDecimalPlaces": 1,
      "unit": "A",
      "confidence": "medium",
      "steps": [],
      "basis": "sole-source",
      "sourceIndex": 0
    }
  ]
}