  "title": "Hydronic Circulator Pump Head Loss Calculator",
  "description": "Calculate the total dynamic head a hydronic circulator pump must overcome, from friction loss rate and total equivalent pipe length.",
  "url": "https://craftquantities.com/calculators/materials-quantities/circulator-pump-head-loss-calculator/",
  "json": "https://craftquantities.com/api/v1/calculators/circulator-pump-head-loss-calculator.json",
  "inputCount": 2,
  "testCaseCount": 2,
  "sourceCount": 1,
  "lastVerified": "2026-09-06",
  "translations": {
    "es-US": "https://craftquantities.com/es/calculators/materials-quantities/circulator-pump-head-loss-calculator/"
  },
  "citation": {
    "author": "Craft Quantities",
    "title": "Hydronic Circulator Pump Head Loss Calculator",
    "version": "1.0.1",
    "sourcesChecked": "2026-09-06",
    "url": "https://craftquantities.com/calculators/materials-quantities/circulator-pump-head-loss-calculator/",
    "accessDate": null,
    "accessDateNote": "Add the date you retrieved this. It is deliberately absent: a static file cannot know when you read it, and the build date would be wrong.",
    "permanentVersionedUrl": null,
    "permanentVersionedUrlNote": "Not offered. This site keeps no archive of previous builds, so any such URL would resolve to the current page or to nothing. The version and sourcesChecked fields identify the calculation instead.",
    "formats": {
      "plain": "Craft Quantities. Hydronic Circulator Pump Head Loss Calculator. Version 1.0.1. Sources checked 2026-09-06. https://craftquantities.com/calculators/materials-quantities/circulator-pump-head-loss-calculator/",
      "apa": "Craft Quantities. (2026). Hydronic Circulator Pump Head Loss Calculator (Version 1.0.1) [Web calculator]. Retrieved from https://craftquantities.com/calculators/materials-quantities/circulator-pump-head-loss-calculator/",
      "harvard": "Craft Quantities (2026) Hydronic Circulator Pump Head Loss Calculator (Version 1.0.1). Available at: https://craftquantities.com/calculators/materials-quantities/circulator-pump-head-loss-calculator/",
      "bibtex": "@misc{craftquantities-calculators-materials-quantities-circulator-pump-head-loss-calculator,\n  author       = {{Craft Quantities}},\n  title        = {Hydronic Circulator Pump Head Loss Calculator},\n  version      = {1.0.1},\n  year         = {2026},\n  howpublished = {\\url{https://craftquantities.com/calculators/materials-quantities/circulator-pump-head-loss-calculator/}},\n}"
    }
  },
  "inputs": [
    {
      "id": "frictionLossRate",
      "label": "Friction Loss Rate (Head Units per 100 ft/m of Pipe)",
      "type": "number",
      "defaultValue": 4,
      "min": 0.5,
      "max": 15,
      "step": 0.5,
      "help": "The friction head loss per 100 ft (or 100 m) of pipe run, from a pipe sizing chart or a Hazen-Williams friction loss calculation at the design flow rate."
    },
    {
      "id": "totalEquivalentLength",
      "label": "Total Equivalent Pipe Length (Straight Pipe + Fittings)",
      "type": "number",
      "defaultValue": 250,
      "min": 0.01,
      "max": 2000,
      "step": 10,
      "help": "The straight pipe length plus the equivalent length of all fittings, valves, and equipment in the circuit's index (longest/most-resistant) run."
    }
  ],
  "sources": [
    {
      "label": "Total head loss = friction loss rate per 100 ft/m of pipe × (total equivalent pipe length ÷ 100), the standard method for sizing a circulator pump's required head once the system's friction loss rate is known (from a pipe sizing chart or Hazen-Williams calculation) and combined with the total equivalent length including fittings"
    }
  ],
  "testCases": [
    {
      "name": "4 head units/100, 250 equivalent length",
      "inputs": {
        "frictionLossRate": 4,
        "totalEquivalentLength": 250
      },
      "expected": 10,
      "toleranceDecimalPlaces": 0,
      "unit": "head units",
      "confidence": "medium",
      "steps": [],
      "basis": "sole-source",
      "sourceIndex": 0
    },
    {
      "name": "5 head units/100, 320 equivalent length",
      "inputs": {
        "frictionLossRate": 5,
        "totalEquivalentLength": 320
      },
      "expected": 16,
      "toleranceDecimalPlaces": 0,
      "unit": "head units",
      "confidence": "medium",
      "steps": [],
      "basis": "sole-source",
      "sourceIndex": 0
    }
  ]
}