  "category": "materials-quantities",
  "title": "Cable Tray Loaded Weight Per Unit Length Calculator",
  "description": "The load per unit length a cable tray puts on its supports: the cables, the tray, attached conduits, ice, and a worker's weight as a distributed load.",
  "url": "https://craftquantities.com/calculators/materials-quantities/cable-tray-loaded-weight-calculator/",
  "json": "https://craftquantities.com/api/v1/calculators/cable-tray-loaded-weight-calculator.json",
  "inputCount": 6,
  "testCaseCount": 3,
  "sourceCount": 4,
  "lastVerified": "2026-09-06",
  "citation": {
    "author": "Craft Quantities",
    "title": "Cable Tray Loaded Weight Per Unit Length Calculator",
    "version": "1.0.1",
    "sourcesChecked": "2026-09-06",
    "url": "https://craftquantities.com/calculators/materials-quantities/cable-tray-loaded-weight-calculator/",
    "accessDate": null,
    "accessDateNote": "Add the date you retrieved this. It is deliberately absent: a static file cannot know when you read it, and the build date would be wrong.",
    "permanentVersionedUrl": null,
    "permanentVersionedUrlNote": "Not offered. This site keeps no archive of previous builds, so any such URL would resolve to the current page or to nothing. The version and sourcesChecked fields identify the calculation instead.",
    "formats": {
      "plain": "Craft Quantities. Cable Tray Loaded Weight Per Unit Length Calculator. Version 1.0.1. Sources checked 2026-09-06. https://craftquantities.com/calculators/materials-quantities/cable-tray-loaded-weight-calculator/",
      "apa": "Craft Quantities. (2026). Cable Tray Loaded Weight Per Unit Length Calculator (Version 1.0.1) [Web calculator]. Retrieved from https://craftquantities.com/calculators/materials-quantities/cable-tray-loaded-weight-calculator/",
      "harvard": "Craft Quantities (2026) Cable Tray Loaded Weight Per Unit Length Calculator (Version 1.0.1). Available at: https://craftquantities.com/calculators/materials-quantities/cable-tray-loaded-weight-calculator/",
      "bibtex": "@misc{craftquantities-calculators-materials-quantities-cable-tray-loaded-weight-calculator,\n  author       = {{Craft Quantities}},\n  title        = {Cable Tray Loaded Weight Per Unit Length Calculator},\n  version      = {1.0.1},\n  year         = {2026},\n  howpublished = {\\url{https://craftquantities.com/calculators/materials-quantities/cable-tray-loaded-weight-calculator/}},\n}"
    }
  },
  "inputs": [
    {
      "id": "cableWeightPerLength",
      "label": "Cable Schedule Weight per Unit Length",
      "type": "number",
      "dimension": "lineardensity",
      "defaultValue": 14,
      "min": 0,
      "max": 200,
      "step": 0.5,
      "help": "Every cable in this segment, summed from the schedule."
    },
    {
      "id": "trayWeightPerLength",
      "label": "Tray Self-Weight per Unit Length",
      "type": "number",
      "dimension": "lineardensity",
      "defaultValue": 4.5,
      "min": 0,
      "max": 50,
      "step": 0.5,
      "help": "The empty weight of the tray section itself, from the manufacturer's catalogue."
    },
    {
      "id": "conduitWeightPerLength",
      "label": "Attached Conduits, Cleats and Accessories",
      "type": "number",
      "dimension": "lineardensity",
      "defaultValue": 2,
      "min": 0,
      "max": 100,
      "step": 0.5,
      "help": "Anything strapped to or hung off the tray that is not a cable in it."
    },
    {
      "id": "iceSnowPerLength",
      "label": "Ice or Snow Allowance per Unit Length",
      "type": "number",
      "dimension": "lineardensity",
      "defaultValue": 0,
      "min": 0,
      "max": 60,
      "step": 0.5,
      "help": "Radial ice or lying snow on an outdoor tray, per unit of run. Zero indoors."
    },
    {
      "id": "concentratedAllowance",
      "label": "Concentrated Worker Allowance",
      "type": "number",
      "dimension": "weight",
      "defaultValue": 90.718474,
      "min": 0,
      "max": 400,
      "step": 5,
      "help": "The point load of a person working in the tray during a pull, applied at mid-span."
    },
    {
      "id": "supportSpan",
      "label": "Support Span",
      "type": "number",
      "dimension": "length",
      "defaultValue": 3,
      "min": 0.5,
      "max": 9,
      "step": 0.1,
      "help": "Centre-to-centre distance between the two supports either side of this segment."
    }
  ],
  "sources": [
    {
      "label": "NEMA VE 1, Metal Cable Tray Systems — tray is rated for a uniformly distributed working load applied together with a concentrated load at mid-span, which is why a worker allowance has to be carried alongside the distributed cable weight rather than folded into it"
    },
    {
      "label": "NEMA VE 2, Cable Tray Installation Guidelines — the concentrated allowance represents an installer standing or kneeling in the tray during a pull, and it is applied where it does most harm, at mid-span"
    },
    {
      "label": "Restating a mid-span point load as an equivalent uniform load is exact beam statics, and the factor depends on what is being checked: 2P/L matches the bending moment (PL/4 = wL²/8) and 1.6P/L matches the deflection (PL³/48EI = 5wL⁴/384EI). Both are reported because using one where the other belongs overstates or understates by 25%"
    },
    {
      "label": "Distinct from this site's Cable Tray Center-Span Deflection Calculator, which takes a load per unit length as an input. This one builds that number from the segment's own schedule and hands it over — but hand over one of the two N/m rows in the breakdown, NOT the kg/m headline: that field is a force per unit length and the headline is a mass per unit length, a factor of 9.81 apart"
    }
  ],
  "testCases": [
    {
      "name": "14 + 4.5 + 2 kg/m loaded, 200 lb worker allowance on a 3 m span",
      "inputs": {
        "cableWeightPerLength": 14,
        "trayWeightPerLength": 4.5,
        "conduitWeightPerLength": 2,
        "iceSnowPerLength": 0,
        "concentratedAllowance": 90.718474,
        "supportSpan": 3
      },
      "expected": 80.978983,
      "toleranceDecimalPlaces": 3,
      "unit": "kg/m",
      "confidence": "high",
      "steps": [
        {
          "label": "Uniformly distributed load from the schedule",
          "value": 20.5,
          "unit": "kg/m"
        },
        {
          "label": "Cables in the segment",
          "value": 14,
          "unit": "kg/m"
        },
        {
          "label": "Tray self-weight",
          "value": 4.5,
          "unit": "kg/m"
        },
        {
          "label": "Attached conduits and cleats",
          "value": 2,
          "unit": "kg/m"
        },
        {
          "label": "Ice or snow allowance",
          "value": 0,
          "unit": "kg/m"
        },
        {
          "label": "Concentrated allowance restated for a moment check",
          "value": 60.47898266666667,
          "unit": "kg/m"
        },
        {
          "label": "Concentrated allowance restated for a deflection check",
          "value": 48.38318613333334,
          "unit": "kg/m"
        },
        {
          "label": "Total load for a moment check, in N/m for the deflection page",
          "value": 794.1325403680667,
          "unit": "N/m"
        },
        {
          "label": "Total load for a deflection check, in N/m for the deflection page",
          "value": 675.5132972944533,
          "unit": "N/m"
        },
        {
          "label": "Mid-span bending moment from the total",
          "value": 893.399107914075,
          "unit": "N·m"
        }
      ],
      "basis": "ambiguous"
    },
    {
      "name": "Heavy schedule with ice and no worker in the tray",
      "inputs": {
        "cableWeightPerLength": 30,
        "trayWeightPerLength": 6,
        "conduitWeightPerLength": 0,
        "iceSnowPerLength": 4,
        "concentratedAllowance": 0,
        "supportSpan": 3
      },
      "expected": 40,
      "toleranceDecimalPlaces": 3,
      "unit": "kg/m",
      "confidence": "high",
      "steps": [
        {
          "label": "Uniformly distributed load from the schedule",
          "value": 40,
          "unit": "kg/m"
        },
        {
          "label": "Cables in the segment",
          "value": 30,
          "unit": "kg/m"
        },
        {
          "label": "Tray self-weight",
          "value": 6,
          "unit": "kg/m"
        },
        {
          "label": "Attached conduits and cleats",
          "value": 0,
          "unit": "kg/m"
        },
        {
          "label": "Ice or snow allowance",
          "value": 4,
          "unit": "kg/m"
        },
        {
          "label": "Concentrated allowance restated for a moment check",
          "value": 0,
          "unit": "kg/m"
        },
        {
          "label": "Concentrated allowance restated for a deflection check",
          "value": 0,
          "unit": "kg/m"
        },
        {
          "label": "Total load for a moment check, in N/m for the deflection page",
          "value": 392.26599999999996,
          "unit": "N/m"
        },
        {
          "label": "Total load for a deflection check, in N/m for the deflection page",
          "value": 392.26599999999996,
          "unit": "N/m"
        },
        {
          "label": "Mid-span bending moment from the total",
          "value": 441.2992499999999,
          "unit": "N·m"
        }
      ],
      "basis": "ambiguous"
    },
    {
      "name": "Empty tray carrying only the worker allowance over a 6 m span",
      "inputs": {
        "cableWeightPerLength": 0,
        "trayWeightPerLength": 0,
        "conduitWeightPerLength": 0,
        "iceSnowPerLength": 0,
        "concentratedAllowance": 90.718474,
        "supportSpan": 6
      },
      "expected": 30.239491,
      "toleranceDecimalPlaces": 3,
      "unit": "kg/m",
      "confidence": "high",
      "steps": [
        {
          "label": "Uniformly distributed load from the schedule",
          "value": 0,
          "unit": "kg/m"
        },
        {
          "label": "Cables in the segment",
          "value": 0,
          "unit": "kg/m"
        },
        {
          "label": "Tray self-weight",
          "value": 0,
          "unit": "kg/m"
        },
        {
          "label": "Attached conduits and cleats",
          "value": 0,
          "unit": "kg/m"
        },
        {
          "label": "Ice or snow allowance",
          "value": 0,
          "unit": "kg/m"
        },
        {
          "label": "Concentrated allowance restated for a moment check",
          "value": 30.239491333333334,
          "unit": "kg/m"
        },
        {
          "label": "Concentrated allowance restated for a deflection check",
          "value": 24.19159306666667,
          "unit": "kg/m"
        },
        {
          "label": "Total load for a moment check, in N/m for the deflection page",
          "value": 296.5481076840333,
          "unit": "N/m"
        },
        {
          "label": "Total load for a deflection check, in N/m for the deflection page",
          "value": 237.2384861472267,
          "unit": "N/m"
        },
        {
          "label": "Mid-span bending moment from the total",
          "value": 1334.46648457815,
          "unit": "N·m"
        }
      ],
      "basis": "ambiguous"
    }
  ]
}