  "version": "v1",
  "source": "https://craftquantities.com",
  "licence": "CC BY 4.0",
  "licenceUrl": "https://creativecommons.org/licenses/by/4.0/",
  "attribution": "Craft Quantities — craftquantities.com",
  "documentation": "https://craftquantities.com/api/",
  "versioning": "Fields are added, never removed or repurposed, within a version. A breaking change becomes /api/v2/ and v1 keeps being built.",
  "slug": "box-fill-calculator",
  "category": "electrical",
  "title": "Electrical Box Fill Calculator (NEC 314.16, US)",
  "description": "Add up a US outlet or junction box's conductors, devices, clamps and grounds in NEC 314.16 volume allowances and compare them with the box's volume.",
  "url": "https://craftquantities.com/calculators/electrical/box-fill-calculator/",
  "json": "https://craftquantities.com/api/v1/calculators/box-fill-calculator.json",
  "inputCount": 17,
  "testCaseCount": 45,
  "sourceCount": 5,
  "lastVerified": "2026-10-05",
  "translations": {
    "es-US": "https://craftquantities.com/es/calculators/electrical/box-fill-calculator/"
  },
  "citation": {
    "author": "Craft Quantities",
    "title": "Electrical Box Fill Calculator (NEC 314.16, US)",
    "version": "1.0.0",
    "sourcesChecked": "2026-10-05",
    "url": "https://craftquantities.com/calculators/electrical/box-fill-calculator/",
    "accessDate": null,
    "accessDateNote": "Add the date you retrieved this. It is deliberately absent: a static file cannot know when you read it, and the build date would be wrong.",
    "permanentVersionedUrl": null,
    "permanentVersionedUrlNote": "Not offered. This site keeps no archive of previous builds, so any such URL would resolve to the current page or to nothing. The version and sourcesChecked fields identify the calculation instead.",
    "formats": {
      "plain": "Craft Quantities. Electrical Box Fill Calculator (NEC 314.16, US). Version 1.0.0. Sources checked 2026-10-05. https://craftquantities.com/calculators/electrical/box-fill-calculator/",
      "apa": "Craft Quantities. (2026). Electrical Box Fill Calculator (NEC 314.16, US) (Version 1.0.0) [Web calculator]. Retrieved from https://craftquantities.com/calculators/electrical/box-fill-calculator/",
      "harvard": "Craft Quantities (2026) Electrical Box Fill Calculator (NEC 314.16, US) (Version 1.0.0). Available at: https://craftquantities.com/calculators/electrical/box-fill-calculator/",
      "bibtex": "@misc{craftquantities-calculators-electrical-box-fill-calculator,\n  author       = {{Craft Quantities}},\n  title        = {Electrical Box Fill Calculator (NEC 314.16, US)},\n  version      = {1.0.0},\n  year         = {2026},\n  howpublished = {\\url{https://craftquantities.com/calculators/electrical/box-fill-calculator/}},\n}"
    }
  },
  "inputs": [
    {
      "id": "box",
      "label": "Box",
      "type": "select",
      "defaultValue": "square-4x2.125",
      "options": [
        {
          "value": "round-4x1.25",
          "label": "4 × 1¼ in round or octagonal — 12.5 in³"
        },
        {
          "value": "round-4x1.5",
          "label": "4 × 1½ in round or octagonal — 15.5 in³"
        },
        {
          "value": "round-4x2.125",
          "label": "4 × 2⅛ in round or octagonal — 21.5 in³"
        },
        {
          "value": "square-4x1.25",
          "label": "4 × 1¼ in square — 18.0 in³"
        },
        {
          "value": "square-4x1.5",
          "label": "4 × 1½ in square — 21.0 in³"
        },
        {
          "value": "square-4x2.125",
          "label": "4 × 2⅛ in square — 30.3 in³"
        },
        {
          "value": "square-4.6875x1.25",
          "label": "4 11/16 × 1¼ in square — 25.5 in³"
        },
        {
          "value": "square-4.6875x1.5",
          "label": "4 11/16 × 1½ in square — 29.5 in³"
        },
        {
          "value": "square-4.6875x2.125",
          "label": "4 11/16 × 2⅛ in square — 42.0 in³"
        },
        {
          "value": "device-3x2x1.5",
          "label": "3 × 2 × 1½ in device — 7.5 in³"
        },
        {
          "value": "device-3x2x2",
          "label": "3 × 2 × 2 in device — 10.0 in³"
        },
        {
          "value": "device-3x2x2.25",
          "label": "3 × 2 × 2¼ in device — 10.5 in³"
        },
        {
          "value": "device-3x2x2.5",
          "label": "3 × 2 × 2½ in device — 12.5 in³"
        },
        {
          "value": "device-3x2x2.75",
          "label": "3 × 2 × 2¾ in device — 14.0 in³"
        },
        {
          "value": "device-3x2x3.5",
          "label": "3 × 2 × 3½ in device — 18.0 in³"
        },
        {
          "value": "device-4x2.125x1.5",
          "label": "4 × 2⅛ × 1½ in device — 10.3 in³"
        },
        {
          "value": "device-4x2.125x1.875",
          "label": "4 × 2⅛ × 1⅞ in device — 13.0 in³"
        },
        {
          "value": "device-4x2.125x2.125",
          "label": "4 × 2⅛ × 2⅛ in device — 14.5 in³"
        },
        {
          "value": "masonry-3.75x2x2.5",
          "label": "3¾ × 2 × 2½ in masonry box or gang — 14.0 in³"
        },
        {
          "value": "masonry-3.75x2x3.5",
          "label": "3¾ × 2 × 3½ in masonry box or gang — 21.0 in³"
        },
        {
          "value": "marked",
          "label": "Another box — enter the volume marked on it"
        }
      ],
      "help": "A standard metal box from NEC Table 314.16(A), or another box with its volume marked on it."
    },
    {
      "id": "markedVolume",
      "label": "Volume marked on the box (in³)",
      "type": "number",
      "defaultValue": 22.5,
      "min": 1,
      "max": 500,
      "step": 0.1,
      "help": "The cubic inches stamped or moulded into the box."
    },
    {
      "id": "addedVolume",
      "label": "Volume of rings or raised covers (in³)",
      "type": "number",
      "defaultValue": 0,
      "min": 0,
      "max": 200,
      "step": 0.1,
      "help": "Extra cubic inches from a plaster ring, extension ring or raised cover: the volume marked on it, or a listed box's."
    },
    {
      "id": "conductors14",
      "label": "14 AWG conductors",
      "type": "number",
      "defaultValue": 8,
      "min": 0,
      "max": 60,
      "step": 1,
      "help": "Insulated 14 AWG conductors entering the box, each counted once."
    },
    {
      "id": "conductors12",
      "label": "12 AWG conductors",
      "type": "number",
      "defaultValue": 0,
      "min": 0,
      "max": 60,
      "step": 1,
      "help": "Insulated 12 AWG conductors entering the box, each counted once."
    },
    {
      "id": "conductors10",
      "label": "10 AWG conductors",
      "type": "number",
      "defaultValue": 0,
      "min": 0,
      "max": 60,
      "step": 1,
      "help": "Insulated 10 AWG conductors entering the box, each counted once."
    },
    {
      "id": "conductors8",
      "label": "8 AWG conductors",
      "type": "number",
      "defaultValue": 0,
      "min": 0,
      "max": 60,
      "step": 1,
      "help": "Insulated 8 AWG conductors entering the box, each counted once."
    },
    {
      "id": "conductors6",
      "label": "6 AWG conductors",
      "type": "number",
      "defaultValue": 0,
      "min": 0,
      "max": 60,
      "step": 1,
      "help": "Insulated 6 AWG conductors entering the box, each counted once."
    },
    {
      "id": "grounds",
      "label": "Equipment grounding conductors entering",
      "type": "number",
      "defaultValue": 4,
      "min": 0,
      "max": 30,
      "step": 1,
      "help": "The bare or green grounds that come into the box — one per cable, usually."
    },
    {
      "id": "groundSize",
      "label": "Largest grounding conductor",
      "type": "select",
      "defaultValue": "14",
      "options": [
        {
          "value": "14",
          "label": "14 AWG"
        },
        {
          "value": "12",
          "label": "12 AWG"
        },
        {
          "value": "10",
          "label": "10 AWG"
        },
        {
          "value": "8",
          "label": "8 AWG"
        },
        {
          "value": "6",
          "label": "6 AWG"
        }
      ],
      "help": "The size of the largest equipment grounding conductor in the box."
    },
    {
      "id": "edition",
      "label": "NEC edition adopted where the box is",
      "type": "select",
      "defaultValue": "2020",
      "options": [
        {
          "value": "2020",
          "label": "2020 NEC or later — grounds beyond four add a quarter each"
        },
        {
          "value": "2017",
          "label": "2017 NEC or earlier — the grounds count once together"
        }
      ],
      "help": "The edition your state or city enforces; it changes only how the grounds are counted."
    },
    {
      "id": "clamps",
      "label": "Internal cable clamps",
      "type": "select",
      "defaultValue": "yes",
      "options": [
        {
          "value": "yes",
          "label": "Yes — one or more clamps inside the box"
        },
        {
          "value": "no",
          "label": "No — connectors clamp outside the box, or none"
        }
      ],
      "help": "Whether the box has clamps inside it that grip the cables."
    },
    {
      "id": "supportFittings",
      "label": "Luminaire studs or hickeys",
      "type": "select",
      "defaultValue": "none",
      "options": [
        {
          "value": "none",
          "label": "None"
        },
        {
          "value": "studs",
          "label": "Luminaire studs only — one or more"
        },
        {
          "value": "hickeys",
          "label": "Hickeys only — one or more"
        },
        {
          "value": "both",
          "label": "Both studs and hickeys"
        }
      ],
      "help": "Fixture studs and hickeys count once for each type present, not once for each fitting."
    },
    {
      "id": "devicesA",
      "label": "Switches or receptacles",
      "type": "number",
      "defaultValue": 2,
      "min": 0,
      "max": 10,
      "step": 1,
      "help": "Device yokes in the box — each switch, receptacle or combination device on one strap."
    },
    {
      "id": "devicesASize",
      "label": "Largest conductor on those devices",
      "type": "select",
      "defaultValue": "14",
      "options": [
        {
          "value": "14",
          "label": "14 AWG"
        },
        {
          "value": "12",
          "label": "12 AWG"
        },
        {
          "value": "10",
          "label": "10 AWG"
        },
        {
          "value": "8",
          "label": "8 AWG"
        },
        {
          "value": "6",
          "label": "6 AWG"
        }
      ],
      "help": "The size of the largest conductor connected to the devices above."
    },
    {
      "id": "devicesB",
      "label": "Devices on a second conductor size",
      "type": "number",
      "defaultValue": 0,
      "min": 0,
      "max": 10,
      "step": 1,
      "help": "Any devices whose largest conductor is a different size from the first group."
    },
    {
      "id": "devicesBSize",
      "label": "Largest conductor on the second group",
      "type": "select",
      "defaultValue": "12",
      "options": [
        {
          "value": "14",
          "label": "14 AWG"
        },
        {
          "value": "12",
          "label": "12 AWG"
        },
        {
          "value": "10",
          "label": "10 AWG"
        },
        {
          "value": "8",
          "label": "8 AWG"
        },
        {
          "value": "6",
          "label": "6 AWG"
        }
      ],
      "help": "The size of the largest conductor connected to the second group of devices."
    }
  ],
  "sources": [
    {
      "label": "City of Republic, Missouri, Community Development Department, Electrical Box Fill Calculations (revised December 2016): 2012 IRC Table E3905.12.2.1, the volume allowance per conductor — 18 AWG 1.50, 16 AWG 1.75, 14 AWG 2.00, 12 AWG 2.25, 10 AWG 2.50, 8 AWG 3.00, 6 AWG 5.00 in³ — and Table E3905.12.1, the volumes of standard metal boxes, the residential code's copies of NEC Tables 314.16(B) and 314.16(A); and the counting rules of NEC 314.16(B)(1) to (5) with worked examples (eleven 14 AWG allowances, 22 in³; five 14 AWG and six 12 AWG, 23.5 in³ in a 4 × 2⅛ in square box). Its support-fitting rule, an allowance for each stud or hickey, is not the code's, which gives one for each type of fitting (Emerson's reprint, below); the page follows the code",
      "url": "https://republicmo.gov/DocumentCenter/View/351/Electric-Box-Fill"
    },
    {
      "label": "Minnesota Department of Labor and Industry, Electrical Inspection Checklist for One-Family Dwellings based on the 2023 NEC (revised 2023-05-06), item 046, NEC 314.16: each insulated wire one allowance, all grounding wires combined one, each switch or receptacle two, all internal cable clamps one; more than four equipment grounding conductors add a quarter allowance each; four 14/2 cables with a switch, a receptacle and clamps need 28 in³",
      "url": "https://www.dli.mn.gov/sites/default/files/pdf/eli_inspection_checklist2023NEC.pdf"
    },
    {
      "label": "City of San Antonio Development Services, 2020 National Electrical Code training (November 2022): 314.16(B)(5), new in 2020 — an additional ¼ volume allowance for equipment grounding conductors exceeding four",
      "url": "https://docsonline.sanantonio.gov/FileUploads/DSD/20221109DSD_GSABA_ElectricalCode.pdf"
    },
    {
      "label": "Emerson (Appleton and O-Z/Gedney), Capacity of Steel Boxes and Covers, commercial and industrial fittings catalogue page 444 (February 2017), which reprints NEC 314.16 from the 2008 edition with NFPA's permission: 314.16(A), a box's volume including plaster rings, domed covers and extension rings that are marked with their volume or made from a box size listed in Table 314.16(A); 314.16(B)(3), a single allowance for each type of support fitting, luminaire studs or hickeys, at the largest conductor in the box; 314.16(B)(5), one allowance for the equipment grounding conductors and, for an additional set of isolated ones under 250.146(D), one more; and Tables 314.16(A) and 314.16(B) in cm³ with in³ in brackets, a 4 × 2⅛ in square box at 497 cm³ (30.3 in³) and a 14 AWG conductor at 32.8 cm³ (2.00 in³)"
    },
    {
      "label": "Leviton, Captain Code 2020 NEC change summary, 314.16(B)(5): from 2020 a quarter allowance for each equipment grounding conductor or bonding jumper beyond four, a change that \"eliminates the need to specifically address\" the isolated-ground conductors of 250.146(D)",
      "url": "https://captaincode2020.leviton.com/node/246"
    }
  ],
  "testCases": [
    {
      "name": "Minnesota's example: four 14/2 cables, a switch, a receptacle and clamps need 28 in³",
      "inputs": {
        "box": "square-4x2.125",
        "addedVolume": 0,
        "conductors14": 8,
        "conductors12": 0,
        "conductors10": 0,
        "conductors8": 0,
        "conductors6": 0,
        "grounds": 4,
        "groundSize": "14",
        "edition": "2020",
        "clamps": "yes",
        "supportFittings": "none",
        "devicesA": 2,
        "devicesASize": "14",
        "devicesB": 0,
        "devicesBSize": "12"
      },
      "expected": 28,
      "toleranceDecimalPlaces": 6,
      "unit": "in³",
      "confidence": "medium",
      "steps": [
        {
          "label": "Box volume, with rings or covers (in³)",
          "value": 30.3
        },
        {
          "label": "Box volume less the contents' allowances (in³)",
          "value": 2.3000000000000007
        },
        {
          "label": "Insulated conductors (in³)",
          "value": 16
        },
        {
          "label": "Equipment grounding conductors (in³)",
          "value": 2
        },
        {
          "label": "Devices, two allowances per yoke (in³)",
          "value": 8
        },
        {
          "label": "Internal cable clamps (in³)",
          "value": 2
        },
        {
          "label": "Luminaire studs and hickeys, one allowance per type (in³)",
          "value": 0
        },
        {
          "label": "Smallest volume in Table 314.16(A) that holds this (in³)",
          "value": 29.5
        }
      ],
      "basis": "cited",
      "sourceIndex": 1
    },
    {
      "name": "Republic's figure 3: eleven 14 AWG allowances are 22 in³",
      "inputs": {
        "box": "square-4x2.125",
        "addedVolume": 0,
        "conductors14": 5,
        "grounds": 2,
        "groundSize": "14",
        "edition": "2017",
        "clamps": "yes",
        "supportFittings": "none",
        "devicesA": 2,
        "devicesASize": "14",
        "devicesB": 0,
        "devicesBSize": "12"
      },
      "expected": 22,
      "toleranceDecimalPlaces": 6,
      "unit": "in³",
      "confidence": "medium",
      "steps": [
        {
          "label": "Box volume, with rings or covers (in³)",
          "value": 30.3
        },
        {
          "label": "Box volume less the contents' allowances (in³)",
          "value": 8.3
        },
        {
          "label": "Insulated conductors (in³)",
          "value": 10
        },
        {
          "label": "Equipment grounding conductors (in³)",
          "value": 2
        },
        {
          "label": "Devices, two allowances per yoke (in³)",
          "value": 8
        },
        {
          "label": "Internal cable clamps (in³)",
          "value": 2
        },
        {
          "label": "Luminaire studs and hickeys, one allowance per type (in³)",
          "value": 0
        },
        {
          "label": "Smallest volume in Table 314.16(A) that holds this (in³)",
          "value": 25.5
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "Republic's mixed example: 14/3 to a switch and 12/2 to a receptacle, 23.5 in³",
      "inputs": {
        "box": "square-4x2.125",
        "addedVolume": 0,
        "conductors14": 3,
        "conductors12": 2,
        "grounds": 2,
        "groundSize": "12",
        "edition": "2017",
        "clamps": "yes",
        "supportFittings": "none",
        "devicesA": 1,
        "devicesASize": "14",
        "devicesB": 1,
        "devicesBSize": "12"
      },
      "expected": 23.5,
      "toleranceDecimalPlaces": 6,
      "unit": "in³",
      "confidence": "medium",
      "steps": [
        {
          "label": "Box volume, with rings or covers (in³)",
          "value": 30.3
        },
        {
          "label": "Box volume less the contents' allowances (in³)",
          "value": 6.800000000000001
        },
        {
          "label": "Insulated conductors (in³)",
          "value": 10.5
        },
        {
          "label": "Equipment grounding conductors (in³)",
          "value": 2.25
        },
        {
          "label": "Devices, two allowances per yoke (in³)",
          "value": 8.5
        },
        {
          "label": "Internal cable clamps (in³)",
          "value": 2.25
        },
        {
          "label": "Luminaire studs and hickeys, one allowance per type (in³)",
          "value": 0
        },
        {
          "label": "Smallest volume in Table 314.16(A) that holds this (in³)",
          "value": 25.5
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "six grounds under the 2020 NEC: one allowance plus two quarters, 3.375 in³ of 12 AWG",
      "inputs": {
        "box": "square-4.6875x2.125",
        "addedVolume": 0,
        "conductors12": 12,
        "grounds": 6,
        "groundSize": "12",
        "edition": "2020",
        "clamps": "no",
        "supportFittings": "none",
        "devicesA": 0,
        "devicesASize": "14",
        "devicesB": 0,
        "devicesBSize": "12"
      },
      "expected": 30.375,
      "toleranceDecimalPlaces": 6,
      "unit": "in³",
      "confidence": "medium",
      "steps": [
        {
          "label": "Box volume, with rings or covers (in³)",
          "value": 42
        },
        {
          "label": "Box volume less the contents' allowances (in³)",
          "value": 11.625
        },
        {
          "label": "Insulated conductors (in³)",
          "value": 27
        },
        {
          "label": "Equipment grounding conductors (in³)",
          "value": 3.375
        },
        {
          "label": "Devices, two allowances per yoke (in³)",
          "value": 0
        },
        {
          "label": "Internal cable clamps (in³)",
          "value": 0
        },
        {
          "label": "Luminaire studs and hickeys, one allowance per type (in³)",
          "value": 0
        },
        {
          "label": "Smallest volume in Table 314.16(A) that holds this (in³)",
          "value": 42
        }
      ],
      "basis": "cited",
      "sourceIndex": 2
    },
    {
      "name": "the same box under the 2017 NEC counts the six grounds once: 29.25 in³",
      "inputs": {
        "box": "square-4.6875x2.125",
        "addedVolume": 0,
        "conductors12": 12,
        "grounds": 6,
        "groundSize": "12",
        "edition": "2017",
        "clamps": "no",
        "supportFittings": "none",
        "devicesA": 0,
        "devicesASize": "14",
        "devicesB": 0,
        "devicesBSize": "12"
      },
      "expected": 29.25,
      "toleranceDecimalPlaces": 6,
      "unit": "in³",
      "confidence": "medium",
      "steps": [
        {
          "label": "Box volume, with rings or covers (in³)",
          "value": 42
        },
        {
          "label": "Box volume less the contents' allowances (in³)",
          "value": 12.75
        },
        {
          "label": "Insulated conductors (in³)",
          "value": 27
        },
        {
          "label": "Equipment grounding conductors (in³)",
          "value": 2.25
        },
        {
          "label": "Devices, two allowances per yoke (in³)",
          "value": 0
        },
        {
          "label": "Internal cable clamps (in³)",
          "value": 0
        },
        {
          "label": "Luminaire studs and hickeys, one allowance per type (in³)",
          "value": 0
        },
        {
          "label": "Smallest volume in Table 314.16(A) that holds this (in³)",
          "value": 29.5
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "a 6 AWG junction: four conductors at 5.00 in³, an 8 AWG grounds allowance at 3.00 and the clamps at 6 AWG make 28 in³",
      "inputs": {
        "box": "square-4.6875x2.125",
        "addedVolume": 0,
        "conductors6": 4,
        "grounds": 2,
        "groundSize": "8",
        "edition": "2020",
        "clamps": "yes",
        "supportFittings": "none",
        "devicesA": 0,
        "devicesASize": "14",
        "devicesB": 0,
        "devicesBSize": "12"
      },
      "expected": 28,
      "toleranceDecimalPlaces": 6,
      "unit": "in³",
      "confidence": "medium",
      "steps": [
        {
          "label": "Box volume, with rings or covers (in³)",
          "value": 42
        },
        {
          "label": "Box volume less the contents' allowances (in³)",
          "value": 14
        },
        {
          "label": "Insulated conductors (in³)",
          "value": 20
        },
        {
          "label": "Equipment grounding conductors (in³)",
          "value": 3
        },
        {
          "label": "Devices, two allowances per yoke (in³)",
          "value": 0
        },
        {
          "label": "Internal cable clamps (in³)",
          "value": 5
        },
        {
          "label": "Luminaire studs and hickeys, one allowance per type (in³)",
          "value": 0
        },
        {
          "label": "Smallest volume in Table 314.16(A) that holds this (in³)",
          "value": 29.5
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "luminaire studs, however many, are one allowance at the largest conductor: 13 + 2.50 = 15.5 in³",
      "inputs": {
        "box": "square-4x2.125",
        "addedVolume": 0,
        "conductors14": 4,
        "conductors10": 2,
        "grounds": 0,
        "groundSize": "14",
        "edition": "2020",
        "clamps": "no",
        "supportFittings": "studs",
        "devicesA": 0,
        "devicesASize": "14",
        "devicesB": 0,
        "devicesBSize": "12"
      },
      "expected": 15.5,
      "toleranceDecimalPlaces": 6,
      "unit": "in³",
      "confidence": "medium",
      "steps": [
        {
          "label": "Box volume, with rings or covers (in³)",
          "value": 30.3
        },
        {
          "label": "Box volume less the contents' allowances (in³)",
          "value": 14.8
        },
        {
          "label": "Insulated conductors (in³)",
          "value": 13
        },
        {
          "label": "Equipment grounding conductors (in³)",
          "value": 0
        },
        {
          "label": "Devices, two allowances per yoke (in³)",
          "value": 0
        },
        {
          "label": "Internal cable clamps (in³)",
          "value": 0
        },
        {
          "label": "Luminaire studs and hickeys, one allowance per type (in³)",
          "value": 2.5
        },
        {
          "label": "Smallest volume in Table 314.16(A) that holds this (in³)",
          "value": 15.5
        }
      ],
      "basis": "cited",
      "sourceIndex": 3
    },
    {
      "name": "hickeys alone are one allowance too: 15.5 in³",
      "inputs": {
        "box": "square-4x2.125",
        "addedVolume": 0,
        "conductors14": 4,
        "conductors10": 2,
        "grounds": 0,
        "groundSize": "14",
        "edition": "2020",
        "clamps": "no",
        "supportFittings": "hickeys",
        "devicesA": 0,
        "devicesASize": "14",
        "devicesB": 0,
        "devicesBSize": "12"
      },
      "expected": 15.5,
      "toleranceDecimalPlaces": 6,
      "unit": "in³",
      "confidence": "medium",
      "steps": [
        {
          "label": "Box volume, with rings or covers (in³)",
          "value": 30.3
        },
        {
          "label": "Box volume less the contents' allowances (in³)",
          "value": 14.8
        },
        {
          "label": "Insulated conductors (in³)",
          "value": 13
        },
        {
          "label": "Equipment grounding conductors (in³)",
          "value": 0
        },
        {
          "label": "Devices, two allowances per yoke (in³)",
          "value": 0
        },
        {
          "label": "Internal cable clamps (in³)",
          "value": 0
        },
        {
          "label": "Luminaire studs and hickeys, one allowance per type (in³)",
          "value": 2.5
        },
        {
          "label": "Smallest volume in Table 314.16(A) that holds this (in³)",
          "value": 15.5
        }
      ],
      "basis": "cited",
      "sourceIndex": 3
    },
    {
      "name": "a stud and a hickey are two types, two allowances: 13 + 2 x 2.50 = 18 in³",
      "inputs": {
        "box": "square-4x2.125",
        "addedVolume": 0,
        "conductors14": 4,
        "conductors10": 2,
        "grounds": 0,
        "groundSize": "14",
        "edition": "2020",
        "clamps": "no",
        "supportFittings": "both",
        "devicesA": 0,
        "devicesASize": "14",
        "devicesB": 0,
        "devicesBSize": "12"
      },
      "expected": 18,
      "toleranceDecimalPlaces": 6,
      "unit": "in³",
      "confidence": "medium",
      "steps": [
        {
          "label": "Box volume, with rings or covers (in³)",
          "value": 30.3
        },
        {
          "label": "Box volume less the contents' allowances (in³)",
          "value": 12.3
        },
        {
          "label": "Insulated conductors (in³)",
          "value": 13
        },
        {
          "label": "Equipment grounding conductors (in³)",
          "value": 0
        },
        {
          "label": "Devices, two allowances per yoke (in³)",
          "value": 0
        },
        {
          "label": "Internal cable clamps (in³)",
          "value": 0
        },
        {
          "label": "Luminaire studs and hickeys, one allowance per type (in³)",
          "value": 5
        },
        {
          "label": "Smallest volume in Table 314.16(A) that holds this (in³)",
          "value": 18
        }
      ],
      "basis": "cited",
      "sourceIndex": 3
    },
    {
      "name": "one 14 AWG ground is one allowance: 2 in³",
      "inputs": {
        "box": "square-4x2.125",
        "grounds": 1,
        "groundSize": "14",
        "edition": "2020",
        "clamps": "no",
        "devicesA": 0,
        "devicesASize": "14",
        "devicesB": 0,
        "devicesBSize": "12"
      },
      "expected": 2,
      "toleranceDecimalPlaces": 6,
      "unit": "in³",
      "confidence": "medium",
      "steps": [
        {
          "label": "Box volume, with rings or covers (in³)",
          "value": 30.3
        },
        {
          "label": "Box volume less the contents' allowances (in³)",
          "value": 28.3
        },
        {
          "label": "Insulated conductors (in³)",
          "value": 0
        },
        {
          "label": "Equipment grounding conductors (in³)",
          "value": 2
        },
        {
          "label": "Devices, two allowances per yoke (in³)",
          "value": 0
        },
        {
          "label": "Internal cable clamps (in³)",
          "value": 0
        },
        {
          "label": "Luminaire studs and hickeys, one allowance per type (in³)",
          "value": 0
        },
        {
          "label": "Smallest volume in Table 314.16(A) that holds this (in³)",
          "value": 7.5
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "a device on 14 AWG is two allowances: 4 in³",
      "inputs": {
        "box": "square-4x2.125",
        "grounds": 0,
        "groundSize": "14",
        "edition": "2020",
        "clamps": "no",
        "devicesA": 1,
        "devicesASize": "14",
        "devicesB": 0,
        "devicesBSize": "12"
      },
      "expected": 4,
      "toleranceDecimalPlaces": 6,
      "unit": "in³",
      "confidence": "medium",
      "steps": [
        {
          "label": "Box volume, with rings or covers (in³)",
          "value": 30.3
        },
        {
          "label": "Box volume less the contents' allowances (in³)",
          "value": 26.3
        },
        {
          "label": "Insulated conductors (in³)",
          "value": 0
        },
        {
          "label": "Equipment grounding conductors (in³)",
          "value": 0
        },
        {
          "label": "Devices, two allowances per yoke (in³)",
          "value": 4
        },
        {
          "label": "Internal cable clamps (in³)",
          "value": 0
        },
        {
          "label": "Luminaire studs and hickeys, one allowance per type (in³)",
          "value": 0
        },
        {
          "label": "Smallest volume in Table 314.16(A) that holds this (in³)",
          "value": 7.5
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "a second-group device on 14 AWG is two allowances too",
      "inputs": {
        "box": "square-4x2.125",
        "grounds": 0,
        "groundSize": "14",
        "edition": "2020",
        "clamps": "no",
        "devicesA": 0,
        "devicesASize": "14",
        "devicesB": 1,
        "devicesBSize": "14"
      },
      "expected": 4,
      "toleranceDecimalPlaces": 6,
      "unit": "in³",
      "confidence": "medium",
      "steps": [
        {
          "label": "Box volume, with rings or covers (in³)",
          "value": 30.3
        },
        {
          "label": "Box volume less the contents' allowances (in³)",
          "value": 26.3
        },
        {
          "label": "Insulated conductors (in³)",
          "value": 0
        },
        {
          "label": "Equipment grounding conductors (in³)",
          "value": 0
        },
        {
          "label": "Devices, two allowances per yoke (in³)",
          "value": 4
        },
        {
          "label": "Internal cable clamps (in³)",
          "value": 0
        },
        {
          "label": "Luminaire studs and hickeys, one allowance per type (in³)",
          "value": 0
        },
        {
          "label": "Smallest volume in Table 314.16(A) that holds this (in³)",
          "value": 7.5
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "one 12 AWG ground is one allowance: 2.25 in³",
      "inputs": {
        "box": "square-4x2.125",
        "grounds": 1,
        "groundSize": "12",
        "edition": "2020",
        "clamps": "no",
        "devicesA": 0,
        "devicesASize": "14",
        "devicesB": 0,
        "devicesBSize": "12"
      },
      "expected": 2.25,
      "toleranceDecimalPlaces": 6,
      "unit": "in³",
      "confidence": "medium",
      "steps": [
        {
          "label": "Box volume, with rings or covers (in³)",
          "value": 30.3
        },
        {
          "label": "Box volume less the contents' allowances (in³)",
          "value": 28.05
        },
        {
          "label": "Insulated conductors (in³)",
          "value": 0
        },
        {
          "label": "Equipment grounding conductors (in³)",
          "value": 2.25
        },
        {
          "label": "Devices, two allowances per yoke (in³)",
          "value": 0
        },
        {
          "label": "Internal cable clamps (in³)",
          "value": 0
        },
        {
          "label": "Luminaire studs and hickeys, one allowance per type (in³)",
          "value": 0
        },
        {
          "label": "Smallest volume in Table 314.16(A) that holds this (in³)",
          "value": 7.5
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "a device on 12 AWG is two allowances: 4.5 in³",
      "inputs": {
        "box": "square-4x2.125",
        "grounds": 0,
        "groundSize": "14",
        "edition": "2020",
        "clamps": "no",
        "devicesA": 1,
        "devicesASize": "12",
        "devicesB": 0,
        "devicesBSize": "12"
      },
      "expected": 4.5,
      "toleranceDecimalPlaces": 6,
      "unit": "in³",
      "confidence": "medium",
      "steps": [
        {
          "label": "Box volume, with rings or covers (in³)",
          "value": 30.3
        },
        {
          "label": "Box volume less the contents' allowances (in³)",
          "value": 25.8
        },
        {
          "label": "Insulated conductors (in³)",
          "value": 0
        },
        {
          "label": "Equipment grounding conductors (in³)",
          "value": 0
        },
        {
          "label": "Devices, two allowances per yoke (in³)",
          "value": 4.5
        },
        {
          "label": "Internal cable clamps (in³)",
          "value": 0
        },
        {
          "label": "Luminaire studs and hickeys, one allowance per type (in³)",
          "value": 0
        },
        {
          "label": "Smallest volume in Table 314.16(A) that holds this (in³)",
          "value": 7.5
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "a second-group device on 12 AWG is two allowances too",
      "inputs": {
        "box": "square-4x2.125",
        "grounds": 0,
        "groundSize": "14",
        "edition": "2020",
        "clamps": "no",
        "devicesA": 0,
        "devicesASize": "14",
        "devicesB": 1,
        "devicesBSize": "12"
      },
      "expected": 4.5,
      "toleranceDecimalPlaces": 6,
      "unit": "in³",
      "confidence": "medium",
      "steps": [
        {
          "label": "Box volume, with rings or covers (in³)",
          "value": 30.3
        },
        {
          "label": "Box volume less the contents' allowances (in³)",
          "value": 25.8
        },
        {
          "label": "Insulated conductors (in³)",
          "value": 0
        },
        {
          "label": "Equipment grounding conductors (in³)",
          "value": 0
        },
        {
          "label": "Devices, two allowances per yoke (in³)",
          "value": 4.5
        },
        {
          "label": "Internal cable clamps (in³)",
          "value": 0
        },
        {
          "label": "Luminaire studs and hickeys, one allowance per type (in³)",
          "value": 0
        },
        {
          "label": "Smallest volume in Table 314.16(A) that holds this (in³)",
          "value": 7.5
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "one 10 AWG ground is one allowance: 2.5 in³",
      "inputs": {
        "box": "square-4x2.125",
        "grounds": 1,
        "groundSize": "10",
        "edition": "2020",
        "clamps": "no",
        "devicesA": 0,
        "devicesASize": "14",
        "devicesB": 0,
        "devicesBSize": "12"
      },
      "expected": 2.5,
      "toleranceDecimalPlaces": 6,
      "unit": "in³",
      "confidence": "medium",
      "steps": [
        {
          "label": "Box volume, with rings or covers (in³)",
          "value": 30.3
        },
        {
          "label": "Box volume less the contents' allowances (in³)",
          "value": 27.8
        },
        {
          "label": "Insulated conductors (in³)",
          "value": 0
        },
        {
          "label": "Equipment grounding conductors (in³)",
          "value": 2.5
        },
        {
          "label": "Devices, two allowances per yoke (in³)",
          "value": 0
        },
        {
          "label": "Internal cable clamps (in³)",
          "value": 0
        },
        {
          "label": "Luminaire studs and hickeys, one allowance per type (in³)",
          "value": 0
        },
        {
          "label": "Smallest volume in Table 314.16(A) that holds this (in³)",
          "value": 7.5
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "a device on 10 AWG is two allowances: 5 in³",
      "inputs": {
        "box": "square-4x2.125",
        "grounds": 0,
        "groundSize": "14",
        "edition": "2020",
        "clamps": "no",
        "devicesA": 1,
        "devicesASize": "10",
        "devicesB": 0,
        "devicesBSize": "12"
      },
      "expected": 5,
      "toleranceDecimalPlaces": 6,
      "unit": "in³",
      "confidence": "medium",
      "steps": [
        {
          "label": "Box volume, with rings or covers (in³)",
          "value": 30.3
        },
        {
          "label": "Box volume less the contents' allowances (in³)",
          "value": 25.3
        },
        {
          "label": "Insulated conductors (in³)",
          "value": 0
        },
        {
          "label": "Equipment grounding conductors (in³)",
          "value": 0
        },
        {
          "label": "Devices, two allowances per yoke (in³)",
          "value": 5
        },
        {
          "label": "Internal cable clamps (in³)",
          "value": 0
        },
        {
          "label": "Luminaire studs and hickeys, one allowance per type (in³)",
          "value": 0
        },
        {
          "label": "Smallest volume in Table 314.16(A) that holds this (in³)",
          "value": 7.5
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "a second-group device on 10 AWG is two allowances too",
      "inputs": {
        "box": "square-4x2.125",
        "grounds": 0,
        "groundSize": "14",
        "edition": "2020",
        "clamps": "no",
        "devicesA": 0,
        "devicesASize": "14",
        "devicesB": 1,
        "devicesBSize": "10"
      },
      "expected": 5,
      "toleranceDecimalPlaces": 6,
      "unit": "in³",
      "confidence": "medium",
      "steps": [
        {
          "label": "Box volume, with rings or covers (in³)",
          "value": 30.3
        },
        {
          "label": "Box volume less the contents' allowances (in³)",
          "value": 25.3
        },
        {
          "label": "Insulated conductors (in³)",
          "value": 0
        },
        {
          "label": "Equipment grounding conductors (in³)",
          "value": 0
        },
        {
          "label": "Devices, two allowances per yoke (in³)",
          "value": 5
        },
        {
          "label": "Internal cable clamps (in³)",
          "value": 0
        },
        {
          "label": "Luminaire studs and hickeys, one allowance per type (in³)",
          "value": 0
        },
        {
          "label": "Smallest volume in Table 314.16(A) that holds this (in³)",
          "value": 7.5
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "one 8 AWG ground is one allowance: 3 in³",
      "inputs": {
        "box": "square-4x2.125",
        "grounds": 1,
        "groundSize": "8",
        "edition": "2020",
        "clamps": "no",
        "devicesA": 0,
        "devicesASize": "14",
        "devicesB": 0,
        "devicesBSize": "12"
      },
      "expected": 3,
      "toleranceDecimalPlaces": 6,
      "unit": "in³",
      "confidence": "medium",
      "steps": [
        {
          "label": "Box volume, with rings or covers (in³)",
          "value": 30.3
        },
        {
          "label": "Box volume less the contents' allowances (in³)",
          "value": 27.3
        },
        {
          "label": "Insulated conductors (in³)",
          "value": 0
        },
        {
          "label": "Equipment grounding conductors (in³)",
          "value": 3
        },
        {
          "label": "Devices, two allowances per yoke (in³)",
          "value": 0
        },
        {
          "label": "Internal cable clamps (in³)",
          "value": 0
        },
        {
          "label": "Luminaire studs and hickeys, one allowance per type (in³)",
          "value": 0
        },
        {
          "label": "Smallest volume in Table 314.16(A) that holds this (in³)",
          "value": 7.5
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "a device on 8 AWG is two allowances: 6 in³",
      "inputs": {
        "box": "square-4x2.125",
        "grounds": 0,
        "groundSize": "14",
        "edition": "2020",
        "clamps": "no",
        "devicesA": 1,
        "devicesASize": "8",
        "devicesB": 0,
        "devicesBSize": "12"
      },
      "expected": 6,
      "toleranceDecimalPlaces": 6,
      "unit": "in³",
      "confidence": "medium",
      "steps": [
        {
          "label": "Box volume, with rings or covers (in³)",
          "value": 30.3
        },
        {
          "label": "Box volume less the contents' allowances (in³)",
          "value": 24.3
        },
        {
          "label": "Insulated conductors (in³)",
          "value": 0
        },
        {
          "label": "Equipment grounding conductors (in³)",
          "value": 0
        },
        {
          "label": "Devices, two allowances per yoke (in³)",
          "value": 6
        },
        {
          "label": "Internal cable clamps (in³)",
          "value": 0
        },
        {
          "label": "Luminaire studs and hickeys, one allowance per type (in³)",
          "value": 0
        },
        {
          "label": "Smallest volume in Table 314.16(A) that holds this (in³)",
          "value": 7.5
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "a second-group device on 8 AWG is two allowances too",
      "inputs": {
        "box": "square-4x2.125",
        "grounds": 0,
        "groundSize": "14",
        "edition": "2020",
        "clamps": "no",
        "devicesA": 0,
        "devicesASize": "14",
        "devicesB": 1,
        "devicesBSize": "8"
      },
      "expected": 6,
      "toleranceDecimalPlaces": 6,
      "unit": "in³",
      "confidence": "medium",
      "steps": [
        {
          "label": "Box volume, with rings or covers (in³)",
          "value": 30.3
        },
        {
          "label": "Box volume less the contents' allowances (in³)",
          "value": 24.3
        },
        {
          "label": "Insulated conductors (in³)",
          "value": 0
        },
        {
          "label": "Equipment grounding conductors (in³)",
          "value": 0
        },
        {
          "label": "Devices, two allowances per yoke (in³)",
          "value": 6
        },
        {
          "label": "Internal cable clamps (in³)",
          "value": 0
        },
        {
          "label": "Luminaire studs and hickeys, one allowance per type (in³)",
          "value": 0
        },
        {
          "label": "Smallest volume in Table 314.16(A) that holds this (in³)",
          "value": 7.5
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "one 6 AWG ground is one allowance: 5 in³",
      "inputs": {
        "box": "square-4x2.125",
        "grounds": 1,
        "groundSize": "6",
        "edition": "2020",
        "clamps": "no",
        "devicesA": 0,
        "devicesASize": "14",
        "devicesB": 0,
        "devicesBSize": "12"
      },
      "expected": 5,
      "toleranceDecimalPlaces": 6,
      "unit": "in³",
      "confidence": "medium",
      "steps": [
        {
          "label": "Box volume, with rings or covers (in³)",
          "value": 30.3
        },
        {
          "label": "Box volume less the contents' allowances (in³)",
          "value": 25.3
        },
        {
          "label": "Insulated conductors (in³)",
          "value": 0
        },
        {
          "label": "Equipment grounding conductors (in³)",
          "value": 5
        },
        {
          "label": "Devices, two allowances per yoke (in³)",
          "value": 0
        },
        {
          "label": "Internal cable clamps (in³)",
          "value": 0
        },
        {
          "label": "Luminaire studs and hickeys, one allowance per type (in³)",
          "value": 0
        },
        {
          "label": "Smallest volume in Table 314.16(A) that holds this (in³)",
          "value": 7.5
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "a device on 6 AWG is two allowances: 10 in³",
      "inputs": {
        "box": "square-4x2.125",
        "grounds": 0,
        "groundSize": "14",
        "edition": "2020",
        "clamps": "no",
        "devicesA": 1,
        "devicesASize": "6",
        "devicesB": 0,
        "devicesBSize": "12"
      },
      "expected": 10,
      "toleranceDecimalPlaces": 6,
      "unit": "in³",
      "confidence": "medium",
      "steps": [
        {
          "label": "Box volume, with rings or covers (in³)",
          "value": 30.3
        },
        {
          "label": "Box volume less the contents' allowances (in³)",
          "value": 20.3
        },
        {
          "label": "Insulated conductors (in³)",
          "value": 0
        },
        {
          "label": "Equipment grounding conductors (in³)",
          "value": 0
        },
        {
          "label": "Devices, two allowances per yoke (in³)",
          "value": 10
        },
        {
          "label": "Internal cable clamps (in³)",
          "value": 0
        },
        {
          "label": "Luminaire studs and hickeys, one allowance per type (in³)",
          "value": 0
        },
        {
          "label": "Smallest volume in Table 314.16(A) that holds this (in³)",
          "value": 10
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "a second-group device on 6 AWG is two allowances too",
      "inputs": {
        "box": "square-4x2.125",
        "grounds": 0,
        "groundSize": "14",
        "edition": "2020",
        "clamps": "no",
        "devicesA": 0,
        "devicesASize": "14",
        "devicesB": 1,
        "devicesBSize": "6"
      },
      "expected": 10,
      "toleranceDecimalPlaces": 6,
      "unit": "in³",
      "confidence": "medium",
      "steps": [
        {
          "label": "Box volume, with rings or covers (in³)",
          "value": 30.3
        },
        {
          "label": "Box volume less the contents' allowances (in³)",
          "value": 20.3
        },
        {
          "label": "Insulated conductors (in³)",
          "value": 0
        },
        {
          "label": "Equipment grounding conductors (in³)",
          "value": 0
        },
        {
          "label": "Devices, two allowances per yoke (in³)",
          "value": 10
        },
        {
          "label": "Internal cable clamps (in³)",
          "value": 0
        },
        {
          "label": "Luminaire studs and hickeys, one allowance per type (in³)",
          "value": 0
        },
        {
          "label": "Smallest volume in Table 314.16(A) that holds this (in³)",
          "value": 10
        }
      ],
      "basis": "cited",
      "sourceIndex": 0
    },
    {
      "name": "Minnesota's contents in a 4 × 1¼ in round or octagonal box need 28 in³",
      "inputs": {
        "box": "round-4x1.25",
        "markedVolume": 22.5,
        "addedVolume": 0,
        "conductors14": 8,
        "grounds": 4,
        "groundSize": "14",
        "edition": "2020",
        "clamps": "yes",
        "supportFittings": "none",
        "devicesA": 2,
        "devicesASize": "14",
        "devicesB": 0,
        "devicesBSize": "12"
      },
      "expected": 28,
      "toleranceDecimalPlaces": 6,
      "unit": "in³",
      "confidence": "medium",
      "steps": [
        {
          "label": "Box volume, with rings or covers (in³)",
          "value": 12.5
        },
        {
          "label": "Box volume less the contents' allowances (in³)",
          "value": -15.5
        },
        {
          "label": "Insulated conductors (in³)",
          "value": 16
        },
        {
          "label": "Equipment grounding conductors (in³)",
          "value": 2
        },
        {
          "label": "Devices, two allowances per yoke (in³)",
          "value": 8
        },
        {
          "label": "Internal cable clamps (in³)",
          "value": 2
        },
        {
          "label": "Luminaire studs and hickeys, one allowance per type (in³)",
          "value": 0
        },
        {
          "label": "Smallest volume in Table 314.16(A) that holds this (in³)",
          "value": 29.5
        }
      ],
      "basis": "cited",
      "sourceIndex": 1
    },
    {
      "name": "Minnesota's contents in a 4 × 1½ in round or octagonal box need 28 in³",
      "inputs": {
        "box": "round-4x1.5",
        "markedVolume": 22.5,
        "addedVolume": 0,
        "conductors14": 8,
        "grounds": 4,
        "groundSize": "14",
        "edition": "2020",
        "clamps": "yes",
        "supportFittings": "none",
        "devicesA": 2,
        "devicesASize": "14",
        "devicesB": 0,
        "devicesBSize": "12"
      },
      "expected": 28,
      "toleranceDecimalPlaces": 6,
      "unit": "in³",
      "confidence": "medium",
      "steps": [
        {
          "label": "Box volume, with rings or covers (in³)",
          "value": 15.5
        },
        {
          "label": "Box volume less the contents' allowances (in³)",
          "value": -12.5
        },
        {
          "label": "Insulated conductors (in³)",
          "value": 16
        },
        {
          "label": "Equipment grounding conductors (in³)",
          "value": 2
        },
        {
          "label": "Devices, two allowances per yoke (in³)",
          "value": 8
        },
        {
          "label": "Internal cable clamps (in³)",
          "value": 2
        },
        {
          "label": "Luminaire studs and hickeys, one allowance per type (in³)",
          "value": 0
        },
        {
          "label": "Smallest volume in Table 314.16(A) that holds this (in³)",
          "value": 29.5
        }
      ],
      "basis": "cited",
      "sourceIndex": 1
    },
    {
      "name": "Minnesota's contents in a 4 × 2⅛ in round or octagonal box need 28 in³",
      "inputs": {
        "box": "round-4x2.125",
        "markedVolume": 22.5,
        "addedVolume": 0,
        "conductors14": 8,
        "grounds": 4,
        "groundSize": "14",
        "edition": "2020",
        "clamps": "yes",
        "supportFittings": "none",
        "devicesA": 2,
        "devicesASize": "14",
        "devicesB": 0,
        "devicesBSize": "12"
      },
      "expected": 28,
      "toleranceDecimalPlaces": 6,
      "unit": "in³",
      "confidence": "medium",
      "steps": [
        {
          "label": "Box volume, with rings or covers (in³)",
          "value": 21.5
        },
        {
          "label": "Box volume less the contents' allowances (in³)",
          "value": -6.5
        },
        {
          "label": "Insulated conductors (in³)",
          "value": 16
        },
        {
          "label": "Equipment grounding conductors (in³)",
          "value": 2
        },
        {
          "label": "Devices, two allowances per yoke (in³)",
          "value": 8
        },
        {
          "label": "Internal cable clamps (in³)",
          "value": 2
        },
        {
          "label": "Luminaire studs and hickeys, one allowance per type (in³)",
          "value": 0
        },
        {
          "label": "Smallest volume in Table 314.16(A) that holds this (in³)",
          "value": 29.5
        }
      ],
      "basis": "cited",
      "sourceIndex": 1
    },
    {
      "name": "Minnesota's contents in a 4 × 1¼ in square box need 28 in³",
      "inputs": {
        "box": "square-4x1.25",
        "markedVolume": 22.5,
        "addedVolume": 0,
        "conductors14": 8,
        "grounds": 4,
        "groundSize": "14",
        "edition": "2020",
        "clamps": "yes",
        "supportFittings": "none",
        "devicesA": 2,
        "devicesASize": "14",
        "devicesB": 0,
        "devicesBSize": "12"
      },
      "expected": 28,
      "toleranceDecimalPlaces": 6,
      "unit": "in³",
      "confidence": "medium",
      "steps": [
        {
          "label": "Box volume, with rings or covers (in³)",
          "value": 18
        },
        {
          "label": "Box volume less the contents' allowances (in³)",
          "value": -10
        },
        {
          "label": "Insulated conductors (in³)",
          "value": 16
        },
        {
          "label": "Equipment grounding conductors (in³)",
          "value": 2
        },
        {
          "label": "Devices, two allowances per yoke (in³)",
          "value": 8
        },
        {
          "label": "Internal cable clamps (in³)",
          "value": 2
        },
        {
          "label": "Luminaire studs and hickeys, one allowance per type (in³)",
          "value": 0
        },
        {
          "label": "Smallest volume in Table 314.16(A) that holds this (in³)",
          "value": 29.5
        }
      ],
      "basis": "cited",
      "sourceIndex": 1
    },
    {
      "name": "Minnesota's contents in a 4 × 1½ in square box need 28 in³",
      "inputs": {
        "box": "square-4x1.5",
        "markedVolume": 22.5,
        "addedVolume": 0,
        "conductors14": 8,
        "grounds": 4,
        "groundSize": "14",
        "edition": "2020",
        "clamps": "yes",
        "supportFittings": "none",
        "devicesA": 2,
        "devicesASize": "14",
        "devicesB": 0,
        "devicesBSize": "12"
      },
      "expected": 28,
      "toleranceDecimalPlaces": 6,
      "unit": "in³",
      "confidence": "medium",
      "steps": [
        {
          "label": "Box volume, with rings or covers (in³)",
          "value": 21
        },
        {
          "label": "Box volume less the contents' allowances (in³)",
          "value": -7
        },
        {
          "label": "Insulated conductors (in³)",
          "value": 16
        },
        {
          "label": "Equipment grounding conductors (in³)",
          "value": 2
        },
        {
          "label": "Devices, two allowances per yoke (in³)",
          "value": 8
        },
        {
          "label": "Internal cable clamps (in³)",
          "value": 2
        },
        {
          "label": "Luminaire studs and hickeys, one allowance per type (in³)",
          "value": 0
        },
        {
          "label": "Smallest volume in Table 314.16(A) that holds this (in³)",
          "value": 29.5
        }
      ],
      "basis": "cited",
      "sourceIndex": 1
    },
    {
      "name": "Minnesota's contents in a 4 × 2⅛ in square box need 28 in³",
      "inputs": {
        "box": "square-4x2.125",
        "markedVolume": 22.5,
        "addedVolume": 0,
        "conductors14": 8,
        "grounds": 4,
        "groundSize": "14",
        "edition": "2020",
        "clamps": "yes",
        "supportFittings": "none",
        "devicesA": 2,
        "devicesASize": "14",
        "devicesB": 0,
        "devicesBSize": "12"
      },
      "expected": 28,
      "toleranceDecimalPlaces": 6,
      "unit": "in³",
      "confidence": "medium",
      "steps": [
        {
          "label": "Box volume, with rings or covers (in³)",
          "value": 30.3
        },
        {
          "label": "Box volume less the contents' allowances (in³)",
          "value": 2.3000000000000007
        },
        {
          "label": "Insulated conductors (in³)",
          "value": 16
        },
        {
          "label": "Equipment grounding conductors (in³)",
          "value": 2
        },
        {
          "label": "Devices, two allowances per yoke (in³)",
          "value": 8
        },
        {
          "label": "Internal cable clamps (in³)",
          "value": 2
        },
        {
          "label": "Luminaire studs and hickeys, one allowance per type (in³)",
          "value": 0
        },
        {
          "label": "Smallest volume in Table 314.16(A) that holds this (in³)",
          "value": 29.5
        }
      ],
      "basis": "cited",
      "sourceIndex": 1
    },
    {
      "name": "Minnesota's contents in a 4 11/16 × 1¼ in square box need 28 in³",
      "inputs": {
        "box": "square-4.6875x1.25",
        "markedVolume": 22.5,
        "addedVolume": 0,
        "conductors14": 8,
        "grounds": 4,
        "groundSize": "14",
        "edition": "2020",
        "clamps": "yes",
        "supportFittings": "none",
        "devicesA": 2,
        "devicesASize": "14",
        "devicesB": 0,
        "devicesBSize": "12"
      },
      "expected": 28,
      "toleranceDecimalPlaces": 6,
      "unit": "in³",
      "confidence": "medium",
      "steps": [
        {
          "label": "Box volume, with rings or covers (in³)",
          "value": 25.5
        },
        {
          "label": "Box volume less the contents' allowances (in³)",
          "value": -2.5
        },
        {
          "label": "Insulated conductors (in³)",
          "value": 16
        },
        {
          "label": "Equipment grounding conductors (in³)",
          "value": 2
        },
        {
          "label": "Devices, two allowances per yoke (in³)",
          "value": 8
        },
        {
          "label": "Internal cable clamps (in³)",
          "value": 2
        },
        {
          "label": "Luminaire studs and hickeys, one allowance per type (in³)",
          "value": 0
        },
        {
          "label": "Smallest volume in Table 314.16(A) that holds this (in³)",
          "value": 29.5
        }
      ],
      "basis": "cited",
      "sourceIndex": 1
    },
    {
      "name": "Minnesota's contents in a 4 11/16 × 1½ in square box need 28 in³",
      "inputs": {
        "box": "square-4.6875x1.5",
        "markedVolume": 22.5,
        "addedVolume": 0,
        "conductors14": 8,
        "grounds": 4,
        "groundSize": "14",
        "edition": "2020",
        "clamps": "yes",
        "supportFittings": "none",
        "devicesA": 2,
        "devicesASize": "14",
        "devicesB": 0,
        "devicesBSize": "12"
      },
      "expected": 28,
      "toleranceDecimalPlaces": 6,
      "unit": "in³",
      "confidence": "medium",
      "steps": [
        {
          "label": "Box volume, with rings or covers (in³)",
          "value": 29.5
        },
        {
          "label": "Box volume less the contents' allowances (in³)",
          "value": 1.5
        },
        {
          "label": "Insulated conductors (in³)",
          "value": 16
        },
        {
          "label": "Equipment grounding conductors (in³)",
          "value": 2
        },
        {
          "label": "Devices, two allowances per yoke (in³)",
          "value": 8
        },
        {
          "label": "Internal cable clamps (in³)",
          "value": 2
        },
        {
          "label": "Luminaire studs and hickeys, one allowance per type (in³)",
          "value": 0
        },
        {
          "label": "Smallest volume in Table 314.16(A) that holds this (in³)",
          "value": 29.5
        }
      ],
      "basis": "cited",
      "sourceIndex": 1
    },
    {
      "name": "Minnesota's contents in a 4 11/16 × 2⅛ in square box need 28 in³",
      "inputs": {
        "box": "square-4.6875x2.125",
        "markedVolume": 22.5,
        "addedVolume": 0,
        "conductors14": 8,
        "grounds": 4,
        "groundSize": "14",
        "edition": "2020",
        "clamps": "yes",
        "supportFittings": "none",
        "devicesA": 2,
        "devicesASize": "14",
        "devicesB": 0,
        "devicesBSize": "12"
      },
      "expected": 28,
      "toleranceDecimalPlaces": 6,
      "unit": "in³",
      "confidence": "medium",
      "steps": [
        {
          "label": "Box volume, with rings or covers (in³)",
          "value": 42
        },
        {
          "label": "Box volume less the contents' allowances (in³)",
          "value": 14
        },
        {
          "label": "Insulated conductors (in³)",
          "value": 16
        },
        {
          "label": "Equipment grounding conductors (in³)",
          "value": 2
        },
        {
          "label": "Devices, two allowances per yoke (in³)",
          "value": 8
        },
        {
          "label": "Internal cable clamps (in³)",
          "value": 2
        },
        {
          "label": "Luminaire studs and hickeys, one allowance per type (in³)",
          "value": 0
        },
        {
          "label": "Smallest volume in Table 314.16(A) that holds this (in³)",
          "value": 29.5
        }
      ],
      "basis": "cited",
      "sourceIndex": 1
    },
    {
      "name": "Minnesota's contents in a 3 × 2 × 1½ in device box need 28 in³",
      "inputs": {
        "box": "device-3x2x1.5",
        "markedVolume": 22.5,
        "addedVolume": 0,
        "conductors14": 8,
        "grounds": 4,
        "groundSize": "14",
        "edition": "2020",
        "clamps": "yes",
        "supportFittings": "none",
        "devicesA": 2,
        "devicesASize": "14",
        "devicesB": 0,
        "devicesBSize": "12"
      },
      "expected": 28,
      "toleranceDecimalPlaces": 6,
      "unit": "in³",
      "confidence": "medium",
      "steps": [
        {
          "label": "Box volume, with rings or covers (in³)",
          "value": 7.5
        },
        {
          "label": "Box volume less the contents' allowances (in³)",
          "value": -20.5
        },
        {
          "label": "Insulated conductors (in³)",
          "value": 16
        },
        {
          "label": "Equipment grounding conductors (in³)",
          "value": 2
        },
        {
          "label": "Devices, two allowances per yoke (in³)",
          "value": 8
        },
        {
          "label": "Internal cable clamps (in³)",
          "value": 2
        },
        {
          "label": "Luminaire studs and hickeys, one allowance per type (in³)",
          "value": 0
        },
        {
          "label": "Smallest volume in Table 314.16(A) that holds this (in³)",
          "value": 29.5
        }
      ],
      "basis": "cited",
      "sourceIndex": 1
    },
    {
      "name": "Minnesota's contents in a 3 × 2 × 2 in device box need 28 in³",
      "inputs": {
        "box": "device-3x2x2",
        "markedVolume": 22.5,
        "addedVolume": 0,
        "conductors14": 8,
        "grounds": 4,
        "groundSize": "14",
        "edition": "2020",
        "clamps": "yes",
        "supportFittings": "none",
        "devicesA": 2,
        "devicesASize": "14",
        "devicesB": 0,
        "devicesBSize": "12"
      },
      "expected": 28,
      "toleranceDecimalPlaces": 6,
      "unit": "in³",
      "confidence": "medium",
      "steps": [
        {
          "label": "Box volume, with rings or covers (in³)",
          "value": 10
        },
        {
          "label": "Box volume less the contents' allowances (in³)",
          "value": -18
        },
        {
          "label": "Insulated conductors (in³)",
          "value": 16
        },
        {
          "label": "Equipment grounding conductors (in³)",
          "value": 2
        },
        {
          "label": "Devices, two allowances per yoke (in³)",
          "value": 8
        },
        {
          "label": "Internal cable clamps (in³)",
          "value": 2
        },
        {
          "label": "Luminaire studs and hickeys, one allowance per type (in³)",
          "value": 0
        },
        {
          "label": "Smallest volume in Table 314.16(A) that holds this (in³)",
          "value": 29.5
        }
      ],
      "basis": "cited",
      "sourceIndex": 1
    },
    {
      "name": "Minnesota's contents in a 3 × 2 × 2¼ in device box need 28 in³",
      "inputs": {
        "box": "device-3x2x2.25",
        "markedVolume": 22.5,
        "addedVolume": 0,
        "conductors14": 8,
        "grounds": 4,
        "groundSize": "14",
        "edition": "2020",
        "clamps": "yes",
        "supportFittings": "none",
        "devicesA": 2,
        "devicesASize": "14",
        "devicesB": 0,
        "devicesBSize": "12"
      },
      "expected": 28,
      "toleranceDecimalPlaces": 6,
      "unit": "in³",
      "confidence": "medium",
      "steps": [
        {
          "label": "Box volume, with rings or covers (in³)",
          "value": 10.5
        },
        {
          "label": "Box volume less the contents' allowances (in³)",
          "value": -17.5
        },
        {
          "label": "Insulated conductors (in³)",
          "value": 16
        },
        {
          "label": "Equipment grounding conductors (in³)",
          "value": 2
        },
        {
          "label": "Devices, two allowances per yoke (in³)",
          "value": 8
        },
        {
          "label": "Internal cable clamps (in³)",
          "value": 2
        },
        {
          "label": "Luminaire studs and hickeys, one allowance per type (in³)",
          "value": 0
        },
        {
          "label": "Smallest volume in Table 314.16(A) that holds this (in³)",
          "value": 29.5
        }
      ],
      "basis": "cited",
      "sourceIndex": 1
    },
    {
      "name": "Minnesota's contents in a 3 × 2 × 2½ in device box need 28 in³",
      "inputs": {
        "box": "device-3x2x2.5",
        "markedVolume": 22.5,
        "addedVolume": 0,
        "conductors14": 8,
        "grounds": 4,
        "groundSize": "14",
        "edition": "2020",
        "clamps": "yes",
        "supportFittings": "none",
        "devicesA": 2,
        "devicesASize": "14",
        "devicesB": 0,
        "devicesBSize": "12"
      },
      "expected": 28,
      "toleranceDecimalPlaces": 6,
      "unit": "in³",
      "confidence": "medium",
      "steps": [
        {
          "label": "Box volume, with rings or covers (in³)",
          "value": 12.5
        },
        {
          "label": "Box volume less the contents' allowances (in³)",
          "value": -15.5
        },
        {
          "label": "Insulated conductors (in³)",
          "value": 16
        },
        {
          "label": "Equipment grounding conductors (in³)",
          "value": 2
        },
        {
          "label": "Devices, two allowances per yoke (in³)",
          "value": 8
        },
        {
          "label": "Internal cable clamps (in³)",
          "value": 2
        },
        {
          "label": "Luminaire studs and hickeys, one allowance per type (in³)",
          "value": 0
        },
        {
          "label": "Smallest volume in Table 314.16(A) that holds this (in³)",
          "value": 29.5
        }
      ],
      "basis": "cited",
      "sourceIndex": 1
    },
    {
      "name": "Minnesota's contents in a 3 × 2 × 2¾ in device box need 28 in³",
      "inputs": {
        "box": "device-3x2x2.75",
        "markedVolume": 22.5,
        "addedVolume": 0,
        "conductors14": 8,
        "grounds": 4,
        "groundSize": "14",
        "edition": "2020",
        "clamps": "yes",
        "supportFittings": "none",
        "devicesA": 2,
        "devicesASize": "14",
        "devicesB": 0,
        "devicesBSize": "12"
      },
      "expected": 28,
      "toleranceDecimalPlaces": 6,
      "unit": "in³",
      "confidence": "medium",
      "steps": [
        {
          "label": "Box volume, with rings or covers (in³)",
          "value": 14
        },
        {
          "label": "Box volume less the contents' allowances (in³)",
          "value": -14
        },
        {
          "label": "Insulated conductors (in³)",
          "value": 16
        },
        {
          "label": "Equipment grounding conductors (in³)",
          "value": 2
        },
        {
          "label": "Devices, two allowances per yoke (in³)",
          "value": 8
        },
        {
          "label": "Internal cable clamps (in³)",
          "value": 2
        },
        {
          "label": "Luminaire studs and hickeys, one allowance per type (in³)",
          "value": 0
        },
        {
          "label": "Smallest volume in Table 314.16(A) that holds this (in³)",
          "value": 29.5
        }
      ],
      "basis": "cited",
      "sourceIndex": 1
    },
    {
      "name": "Minnesota's contents in a 3 × 2 × 3½ in device box need 28 in³",
      "inputs": {
        "box": "device-3x2x3.5",
        "markedVolume": 22.5,
        "addedVolume": 0,
        "conductors14": 8,
        "grounds": 4,
        "groundSize": "14",
        "edition": "2020",
        "clamps": "yes",
        "supportFittings": "none",
        "devicesA": 2,
        "devicesASize": "14",
        "devicesB": 0,
        "devicesBSize": "12"
      },
      "expected": 28,
      "toleranceDecimalPlaces": 6,
      "unit": "in³",
      "confidence": "medium",
      "steps": [
        {
          "label": "Box volume, with rings or covers (in³)",
          "value": 18
        },
        {
          "label": "Box volume less the contents' allowances (in³)",
          "value": -10
        },
        {
          "label": "Insulated conductors (in³)",
          "value": 16
        },
        {
          "label": "Equipment grounding conductors (in³)",
          "value": 2
        },
        {
          "label": "Devices, two allowances per yoke (in³)",
          "value": 8
        },
        {
          "label": "Internal cable clamps (in³)",
          "value": 2
        },
        {
          "label": "Luminaire studs and hickeys, one allowance per type (in³)",
          "value": 0
        },
        {
          "label": "Smallest volume in Table 314.16(A) that holds this (in³)",
          "value": 29.5
        }
      ],
      "basis": "cited",
      "sourceIndex": 1
    },
    {
      "name": "Minnesota's contents in a 4 × 2⅛ × 1½ in device box need 28 in³",
      "inputs": {
        "box": "device-4x2.125x1.5",
        "markedVolume": 22.5,
        "addedVolume": 0,
        "conductors14": 8,
        "grounds": 4,
        "groundSize": "14",
        "edition": "2020",
        "clamps": "yes",
        "supportFittings": "none",
        "devicesA": 2,
        "devicesASize": "14",
        "devicesB": 0,
        "devicesBSize": "12"
      },
      "expected": 28,
      "toleranceDecimalPlaces": 6,
      "unit": "in³",
      "confidence": "medium",
      "steps": [
        {
          "label": "Box volume, with rings or covers (in³)",
          "value": 10.3
        },
        {
          "label": "Box volume less the contents' allowances (in³)",
          "value": -17.7
        },
        {
          "label": "Insulated conductors (in³)",
          "value": 16
        },
        {
          "label": "Equipment grounding conductors (in³)",
          "value": 2
        },
        {
          "label": "Devices, two allowances per yoke (in³)",
          "value": 8
        },
        {
          "label": "Internal cable clamps (in³)",
          "value": 2
        },
        {
          "label": "Luminaire studs and hickeys, one allowance per type (in³)",
          "value": 0
        },
        {
          "label": "Smallest volume in Table 314.16(A) that holds this (in³)",
          "value": 29.5
        }
      ],
      "basis": "cited",
      "sourceIndex": 1
    },
    {
      "name": "Minnesota's contents in a 4 × 2⅛ × 1⅞ in device box need 28 in³",
      "inputs": {
        "box": "device-4x2.125x1.875",
        "markedVolume": 22.5,
        "addedVolume": 0,
        "conductors14": 8,
        "grounds": 4,
        "groundSize": "14",
        "edition": "2020",
        "clamps": "yes",
        "supportFittings": "none",
        "devicesA": 2,
        "devicesASize": "14",
        "devicesB": 0,
        "devicesBSize": "12"
      },
      "expected": 28,
      "toleranceDecimalPlaces": 6,
      "unit": "in³",
      "confidence": "medium",
      "steps": [
        {
          "label": "Box volume, with rings or covers (in³)",
          "value": 13
        },
        {
          "label": "Box volume less the contents' allowances (in³)",
          "value": -15
        },
        {
          "label": "Insulated conductors (in³)",
          "value": 16
        },
        {
          "label": "Equipment grounding conductors (in³)",
          "value": 2
        },
        {
          "label": "Devices, two allowances per yoke (in³)",
          "value": 8
        },
        {
          "label": "Internal cable clamps (in³)",
          "value": 2
        },
        {
          "label": "Luminaire studs and hickeys, one allowance per type (in³)",
          "value": 0
        },
        {
          "label": "Smallest volume in Table 314.16(A) that holds this (in³)",
          "value": 29.5
        }
      ],
      "basis": "cited",
      "sourceIndex": 1
    },
    {
      "name": "Minnesota's contents in a 4 × 2⅛ × 2⅛ in device box need 28 in³",
      "inputs": {
        "box": "device-4x2.125x2.125",
        "markedVolume": 22.5,
        "addedVolume": 0,
        "conductors14": 8,
        "grounds": 4,
        "groundSize": "14",
        "edition": "2020",
        "clamps": "yes",
        "supportFittings": "none",
        "devicesA": 2,
        "devicesASize": "14",
        "devicesB": 0,
        "devicesBSize": "12"
      },
      "expected": 28,
      "toleranceDecimalPlaces": 6,
      "unit": "in³",
      "confidence": "medium",
      "steps": [
        {
          "label": "Box volume, with rings or covers (in³)",
          "value": 14.5
        },
        {
          "label": "Box volume less the contents' allowances (in³)",
          "value": -13.5
        },
        {
          "label": "Insulated conductors (in³)",
          "value": 16
        },
        {
          "label": "Equipment grounding conductors (in³)",
          "value": 2
        },
        {
          "label": "Devices, two allowances per yoke (in³)",
          "value": 8
        },
        {
          "label": "Internal cable clamps (in³)",
          "value": 2
        },
        {
          "label": "Luminaire studs and hickeys, one allowance per type (in³)",
          "value": 0
        },
        {
          "label": "Smallest volume in Table 314.16(A) that holds this (in³)",
          "value": 29.5
        }
      ],
      "basis": "cited",
      "sourceIndex": 1
    },
    {
      "name": "Minnesota's contents in a 3¾ × 2 × 2½ in masonry box or gang box need 28 in³",
      "inputs": {
        "box": "masonry-3.75x2x2.5",
        "markedVolume": 22.5,
        "addedVolume": 0,
        "conductors14": 8,
        "grounds": 4,
        "groundSize": "14",
        "edition": "2020",
        "clamps": "yes",
        "supportFittings": "none",
        "devicesA": 2,
        "devicesASize": "14",
        "devicesB": 0,
        "devicesBSize": "12"
      },
      "expected": 28,
      "toleranceDecimalPlaces": 6,
      "unit": "in³",
      "confidence": "medium",
      "steps": [
        {
          "label": "Box volume, with rings or covers (in³)",
          "value": 14
        },
        {
          "label": "Box volume less the contents' allowances (in³)",
          "value": -14
        },
        {
          "label": "Insulated conductors (in³)",
          "value": 16
        },
        {
          "label": "Equipment grounding conductors (in³)",
          "value": 2
        },
        {
          "label": "Devices, two allowances per yoke (in³)",
          "value": 8
        },
        {
          "label": "Internal cable clamps (in³)",
          "value": 2
        },
        {
          "label": "Luminaire studs and hickeys, one allowance per type (in³)",
          "value": 0
        },
        {
          "label": "Smallest volume in Table 314.16(A) that holds this (in³)",
          "value": 29.5
        }
      ],
      "basis": "cited",
      "sourceIndex": 1
    },
    {
      "name": "Minnesota's contents in a 3¾ × 2 × 3½ in masonry box or gang box need 28 in³",
      "inputs": {
        "box": "masonry-3.75x2x3.5",
        "markedVolume": 22.5,
        "addedVolume": 0,
        "conductors14": 8,
        "grounds": 4,
        "groundSize": "14",
        "edition": "2020",
        "clamps": "yes",
        "supportFittings": "none",
        "devicesA": 2,
        "devicesASize": "14",
        "devicesB": 0,
        "devicesBSize": "12"
      },
      "expected": 28,
      "toleranceDecimalPlaces": 6,
      "unit": "in³",
      "confidence": "medium",
      "steps": [
        {
          "label": "Box volume, with rings or covers (in³)",
          "value": 21
        },
        {
          "label": "Box volume less the contents' allowances (in³)",
          "value": -7
        },
        {
          "label": "Insulated conductors (in³)",
          "value": 16
        },
        {
          "label": "Equipment grounding conductors (in³)",
          "value": 2
        },
        {
          "label": "Devices, two allowances per yoke (in³)",
          "value": 8
        },
        {
          "label": "Internal cable clamps (in³)",
          "value": 2
        },
        {
          "label": "Luminaire studs and hickeys, one allowance per type (in³)",
          "value": 0
        },
        {
          "label": "Smallest volume in Table 314.16(A) that holds this (in³)",
          "value": 29.5
        }
      ],
      "basis": "cited",
      "sourceIndex": 1
    },
    {
      "name": "Minnesota's contents in a box marked with its volume box need 28 in³",
      "inputs": {
        "box": "marked",
        "markedVolume": 22.5,
        "addedVolume": 0,
        "conductors14": 8,
        "grounds": 4,
        "groundSize": "14",
        "edition": "2020",
        "clamps": "yes",
        "supportFittings": "none",
        "devicesA": 2,
        "devicesASize": "14",
        "devicesB": 0,
        "devicesBSize": "12"
      },
      "expected": 28,
      "toleranceDecimalPlaces": 6,
      "unit": "in³",
      "confidence": "medium",
      "steps": [
        {
          "label": "Box volume, with rings or covers (in³)",
          "value": 22.5
        },
        {
          "label": "Box volume less the contents' allowances (in³)",
          "value": -5.5
        },
        {
          "label": "Insulated conductors (in³)",
          "value": 16
        },
        {
          "label": "Equipment grounding conductors (in³)",
          "value": 2
        },
        {
          "label": "Devices, two allowances per yoke (in³)",
          "value": 8
        },
        {
          "label": "Internal cable clamps (in³)",
          "value": 2
        },
        {
          "label": "Luminaire studs and hickeys, one allowance per type (in³)",
          "value": 0
        },
        {
          "label": "Smallest volume in Table 314.16(A) that holds this (in³)",
          "value": 29.5
        }
      ],
      "basis": "cited",
      "sourceIndex": 1
    }
  ]
}